Site Code | Site Name | Building Code | Building Name | Level | Room No. | Location | Item Description | Material Type | Sample Status? | Friability Removed? | Disturbance | Control Reccomendation | Control Reccomendation | Asbestos Removed? |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
FSFG | Fowlers Gap Field Station | Fowlers Gap New Waste Tip Area | G | - | - | On Ground Surface | Fibre Cement Sheet Debris | Positive - Removed | - | - | - | Item Removed: UNSW site personnel informed RiskTech that fibre cement debris removed. No fibre cement debris sighted by RiskTech during the inspection. | Yes | |
KENC | Kensington Campus | J12 | Newton | 3 | 313 | Under Carpet | Floor Covering | Adhesive attached to Cream Vinyl Tiles | Negative | - | - | - | - | N/A |
FSFG | Fowlers Gap Field Station | Fowlers Gap Old Waste Tip Area | G | - | Eastern Section, Localised Areas (Note: Asbestos warning signage & barrier mesh & fencing present) | On Ground Surface | Fibre Cement Sheet Debris | Positive (Amosite & Chrysotile) | Non-Friable | Low | P3 | Demolition-'Restricted access to this area. 'Remedial works should be undertaken by a Class A/B Contractor within a planned control program. | Yes | |
KENC | Kensington Campus | F10 | Chemical Sciences | G | GQ1 | - | Inside Electrical Cabinet | Electrical Backing Board | - | - | - | - | Item Removed: System upgraded. No removal/clearance documentation was provided. | Yes |
KENC | Kensington Campus | F10 | Chemical Sciences | M | M10 | - | Floor Covering | Vinyl Tiles (olive green) | - | - | - | - | Item removed. No removal/clearance documentation was provided. | Yes |
KENC | Kensington Campus | F10 | Chemical Sciences | 1 | 1Q1 | Electrical Cupboard | Inside Electrical Cabinet | Electrical Backing Board | - | - | - | - | Item Removed: System upgraded. No removal/clearance documentation was provided. | Yes |
KENC | Kensington Campus | F10 | Chemical Sciences | 2 | 2Q1 | Electrical Cupboard | Inside Electrical Cabinet | Electrical Backing Board | - | - | - | - | Item Removed: System upgraded. No removal/clearance documentation was provided. | Yes |
KENC | Kensington Campus | F10 | Chemical Sciences | 4 | 4Q2 | Electrical Cupboard | Inside Electrical Cabinet | Electrical Backing Board | - | - | - | - | Item Removed: System upgraded. No removal/clearance documentation was provided. | Yes |
KENC | Kensington Campus | F10 | Chemical Sciences | 4 | 408 | Under New Flooring Covering | Floor Covering | Adhesive (may be present below new floor covering) | - | - | - | - | Item not present (information provided by Spotless). Item not identified during vinyl tiles removal works undertaken in June 2012 | No |
KENC | Kensington Campus | F10 | Chemical Sciences | 7 | 7Q2 | Electrical Cupboard | Inside Electrical Cabinet | Electrical Backing Board | - | - | - | - | Item Removed: System upgraded. No removal/clearance documentation was provided. | Yes |
KENC | Kensington Campus | F10 | Chemical Sciences | 8 | 8Q2 | Electrical Cupboard | Inside Electrical Cabinet | Electrical Backing Board | - | - | - | - | Item Removed: System upgraded. No removal/clearance documentation was provided. | Yes |
KENC | Kensington Campus | F10 | Chemical Sciences | 8 | 8Q4 | Electrical Cupboard | Inside Electrical Cabinet | Electrical Backing Board | - | - | - | - | Item Removed: System upgraded. No removal/clearance documentation was provided. | Yes |
KENC | Kensington Campus | F10 | Chemical Sciences | 9 | 9Q1 | Electrical Cupboard | Inside Electrical Cabinet | Electrical Backing Board | - | - | - | - | Item Removed: System upgraded. No removal/clearance documentation was provided. | Yes |
KENC | Kensington Campus | F10 | Chemical Sciences | 10 | 10Q1 | Electrical Cupboard | Inside Electrical Cabinet | Electrical Backing Board | - | - | - | - | Item Removed: System upgraded. No removal/clearance documentation was provided. | Yes |
KENC | Kensington Campus | F10 | Chemical Sciences | LR | R3 | Electrical Cupboard | Inside Electrical Cabinet | Electrical Backing Board | - | - | - | - | System upgraded. Item removed. No removal/clearance documention was provided. | Yes |
KENC | Kensington Campus | F25 | Samuels | LG-5 | - | Throughout | No asbestos materials identified | - | Negative | - | - | - | - | N/A |
KENC | Kensington Campus | F25 | Samuels | LG-5 | - | Communications Cupboards | No asbestos materials identified | - | Negative | - | - | - | - | N/A |
KENC | Kensington Campus | F25 | Samuels | LG-5 | - | Toilets Throughout | No asbestos materials identified | - | Negative | - | - | - | - | N/A |
Kenc | Kensington Campus | F8 | Law Building | B-03 | - | Throughout | No asbestos materials identified | - | Negative | - | - | - | - | N/A |
Kenc | Kensington Campus | F8 | Law Building | B-03 | - | Throughout | Electrical Cupboards | No asbestos materials identified | - | - | - | - | - | N/A |
Kenc | Kensington Campus | F8 | Law Building | B-03 | - | Throughout | Comminications Cupboards | No asbestos materials identified | - | - | - | - | - | N/A |
Kenc | Kensington Campus | F8 | Law Building | B-03 | - | Throughout | Chiller Plant Room | No asbestos materials identified | - | - | - | - | - | N/A |
Kenc | Kensington Campus | F8 | Law Building | B-03 | - | Throughout | Mechanical Plant Room | No asbestos materials identified | - | - | - | - | - | N/A |
FSFG | Fowlers Gap Field Station | Fowlers Gap Old Waste Tip Area | G | - | Western Section, Localised Areas (Note: fencing present) | On Ground Surface | Fibre Cement Sheet Debris | Assumed Positive | Non-Friable | Low | P3 | Demolition-'Restricted access to this area. 'Remedial works should be undertaken by a Class A/B Contractor within a planned control program. | Yes | |
FSFG | Fowlers Gap Field Station | Fowlers Gap Old Waste Tip Area | G | - | Western Section, Localised Areas (Note: fencing present) | Former Metal Plant Item | Woven Insulation | Assumed Positive | Friable | Med | P3 | Demolition-'Restricted access to this area. 'Remedial works should be undertaken by a Class A/B Contractor within a planned control program. | Yes | |
KENC | Kensington Campus | G19 | John Niland Scientia | LG-1 | - | Throughout | No asbestos materials identified | - | Negative | - | - | - | - | N/A |
KENC | Kensington Campus | G19 | John Niland Scientia | LG-1 | - | Electrical Cupboards Throughout | No asbestos materials identified | - | Negative | - | - | - | - | N/A |
KENC | Kensington Campus | G19 | John Niland Scientia | LG | LGA04 | Lift Motor Room | Hydraulic Lift | No asbestos materials identified | - | - | - | - | - | N/A |
KENC | Kensington Campus | G19 | John Niland Scientia | LG | LG14B | Lift Motor Room | Hydraulic Lift | No asbestos materials identified | - | - | - | - | - | N/A |
KENC | Kensington Campus | G19 | John Niland Scientia | LG-1 | - | Conference Rooms, Auditoriums and Amenities Areas | No asbestos materials identified | - | Negative | - | - | - | - | N/A |
KENC | Kensington Campus | G19 | John Niland Scientia | LG-1 | - | External Façade | No asbestos materials identified | - | Negative | - | - | - | - | N/A |
FSFG | Fowlers Gap Field Station | Fowlers Gap New Waste Tip Area | G | - | - | No asbestos materials identified | - | Negative | - | - | - | - | N/A | |
Kenc | Kensington Campus | G25CP | Botany Street External Carpark | G | - | Exterior Throughout including Roadways, Gardens, Footpaths | No asbestos materials were identified | - | Negative | - | - | - | - | N/A |
KENC | Kensington Campus | B10 | University Village | G | - | Exterior, Entrance Areas | Awning | Fibre Cement Sheeting | Assumed Negative | - | - | - | - | No |
KENC | Kensington Campus | G6 | Blockhouse | - | R1 | Lift Motor Room | Hydraulic Lift | No asbestos materials identified | - | - | - | - | - | N/A |
KENC | Kensington Campus | G6 | Blockhouse | - | R1 | Lift Motor Room | Lift Controller Cabinet | No asbestos materials identified | - | - | - | - | - | N/A |
KENC | Kensington Campus | H13 | The Red Centre | B-6 | - | Throughout | No asbestos materials identified | - | Negative | - | - | - | - | N/A |
KENC | Kensington Campus | H13 | The Red Centre | B-6 | - | Electrical Cupboards | No asbestos materials identified | - | Negative | - | - | - | - | N/A |
KENC | Kensington Campus | H13 | The Red Centre | B-6 | - | Communicationsl Cupboards | No asbestos materials identified | - | Negative | - | - | - | - | N/A |
KENC | Kensington Campus | H13 | The Red Centre | B-6 | - | Plant Rooms | No asbestos materials identified | - | Negative | - | - | - | - | N/A |
KENC | Kensington Campus | H20 | Civil Engineering | LG | LGQ4 | Fire Exit | Fire Door (tagged Bismac 199_) | Core Insulation | - | - | - | - | Item removed (fire doors tagged Bismac 199_) - No removal documentation provided | Yes |
KENC | Kensington Campus | H20 | Civil Engineering | G | GQ2 | Electrical Cupboard | Electrical Switch Board | Electrical Backing Board | - | - | - | - | Item removed - No removal documentation provided | Yes |
KENC | Kensington Campus | H20 | Civil Engineering | G | GQ2 | Fire Exit, Adjacent GQ7 | Fire Door | Core Insulation | - | - | - | - | Item removed - No removal documentation provided | Yes |
KENC | Kensington Campus | H20 | Civil Engineering | G | GQ5 | Fire Exit | Fire Door | Core Insulation | - | - | - | - | Item removed - No removal documentation provided | Yes |
KENC | Kensington Campus | H20 | Civil Engineering | G | GQ6 | Fire Exit | Fire Door | Core Insulation | - | - | - | - | Item removed - No removal documentation provided | Yes |
KENC | Kensington Campus | H20 | Civil Engineering | 1 | 1Q1 | Electrical Cupboard | Electrical Switch Board | Electrical Backing Board | - | - | - | - | Item removed - No removal documentation provided | Yes |
KENC | Kensington Campus | H20 | Civil Engineering | 1 | 1Q3 | Fire Exit | Fire Door | Core Insulation | - | - | - | - | Item removed - No removal documentation provided | Yes |
KENC | Kensington Campus | H20 | Civil Engineering | 1 | 1Q4 | Fire Exit | Fire Door | Core Insulation | - | - | - | - | Item removed - No removal documentation provided | Yes |
KENC | Kensington Campus | H20 | Civil Engineering | 2 | 2Q1 | Electrical Cupboard | Electrical Switch Board | Electrical Backing Board | - | - | - | - | Item removed - No removal documentation provided | Yes |
KENC | Kensington Campus | H20 | Civil Engineering | 2 | 2Q2 | Fire Exit | Fire Door | Core Insulation | - | - | - | - | Item removed - No removal documentation provided | Yes |
KENC | Kensington Campus | H20 | Civil Engineering | 2 | 2Q3 | Fire Exit | Fire Door | Core Insulation | - | - | - | - | Item removed - No removal documentation provided | Yes |
KENC | Kensington Campus | H20 | Civil Engineering | 3 | 3Q1 | Electrical Cupboard | Electrical Switch Board | Electrical Backing Board | - | - | - | - | Item removed - No removal documentation provided | Yes |
KENC | Kensington Campus | H20 | Civil Engineering | 3 | 3Q2 | Fire Exit | Fire Door | Core Insulation | - | - | - | - | Item removed - No removal documentation provided | Yes |
KENC | Kensington Campus | H20 | Civil Engineering | 3 | 3Q3 | Fire Exit | Fire Door | Core Insulation | - | - | - | - | Item removed - No removal documentation provided | Yes |
KENC | Kensington Campus | H20 | Civil Engineering | 4 | 4Q1 | Electrical Cupboard | Electrical Switch Board | Electrical Backing Board | - | - | - | - | Item removed - No removal documentation provided | Yes |
KENC | Kensington Campus | H20 | Civil Engineering | 4 | 4Q2 | Fire Exit | Fire Door | Core Insulation | - | - | - | - | Item removed - No removal documentation provided | Yes |
KENC | Kensington Campus | H20 | Civil Engineering | 4 | 4Q3 | Fire Exit | Fire Door | Core Insulation | - | - | - | - | Item removed - No removal documentation provided | Yes |
KENC | Kensington Campus | H20 | Civil Engineering | 5 | 5Q1 | Electrical Cupboard | Electrical Switch Board | Electrical Backing Board | - | - | - | - | Item removed - No removal documentation provided | Yes |
KENC | Kensington Campus | H20 | Civil Engineering | 5 | 5Q2 | Fire Exit | Fire Door | Core Insulation | - | - | - | - | Item removed - No removal documentation provided | Yes |
KENC | Kensington Campus | H20 | Civil Engineering | 5 | 5Q3 | Fire Exit | Fire Door | Core Insulation | - | - | - | - | Item removed - No removal documentation provided | Yes |
KENC | Kensington Campus | H20 | Civil Engineering | 6 | 6Q1 | Electrical Cupboard | Electrical Switch Board | Electrical Backing Board | - | - | - | - | Item removed - No removal documentation provided | Yes |
KENC | Kensington Campus | H20 | Civil Engineering | 6 | 6Q2 | Fire Exit | Fire Door | Core Insulation | - | - | - | - | Item removed - No removal documentation provided | Yes |
KENC | Kensington Campus | H20 | Civil Engineering | 6 | 6Q3 | Fire Exit | Fire Door | Core Insulation | - | - | - | - | Item removed - No removal documentation provided | Yes |
KENC | Kensington Campus | H20 | Civil Engineering | 7 | 7Q1 | Electrical Cupboard | Electrical Switch Board | Electrical Backing Board | - | - | - | - | Item removed - No removal documentation provided | Yes |
KENC | Kensington Campus | H20 | Civil Engineering | 7 | 7Q2 | Fire Exit | Fire Door | Core Insulation | - | - | - | - | Item removed - No removal documentation provided | Yes |
KENC | Kensington Campus | H20 | Civil Engineering | 7 | 7Q3 | Fire Exit | Fire Door | Core Insulation | - | - | - | - | Item removed - No removal documentation provided | Yes |
KENC | Kensington Campus | H20 | Civil Engineering | 8 | R1 | Plant Room | Fire Door | Core Insulation | - | - | - | - | Item removed - No removal documentation provided | Yes |
KENC | Kensington Campus | B10 | University Village | G | - | Exterior, Northern Elevation | Balcony Walls | Fibre Cement Sheeting | Negative | - | - | - | - | N/A |
KENC | Kensington Campus | B10 | University Village | LG-7 | - | Throughout | No asbestos materials were identified | - | Negative | - | - | - | - | N/A |
KENC | Kensington Campus | B10 | University Village | LG-7 | - | Within Electrical Cabinets Electrical Backing Boards | No asbestos materials were identified | - | Negative | - | - | - | - | N/A |
KENC | Kensington Campus | B10 | University Village | LG-7 | - | Throughout Communications Cupboards | No asbestos materials were identified | - | Negative | - | - | - | - | N/A |
KENC | Kensington Campus | B10 | University Village | LG-7 | - | Fire Stairs and Entrance To Accommodation Areas Throughout | Fire Doors (Tagged 'Icon, 2009') | Core Insulation | Suspected Negative | - | - | - | - | No |
Kenc | Kensington Campus | B10B | Campus Village Café | G | G01 | Exterior, South Side | Wall Cladding | Fibre Cement Sheeting | Negative | - | - | - | - | N/A |
Kenc | Kensington Campus | B10B | Campus Village Café | G | - | Throughout | No asbestos materials identified | - | Negative | - | - | - | - | N/A |
KENC | Kensington Campus | B12A | Building 12A | G | G02 | North Side, Adjacent East Entrance | Switch Board | Electrical Backing Board | Removed -Positive (Chrysotile) | - | - | - | Item removed. No removal or clearance documentation available. | Yes |
KENC | Kensington Campus | B12A | Building 12A | G | - | Exterior, Roof | Roof Covering | Membrane | Negative | - | - | - | - | N/A |
KENC | Kensington Campus | B12A | Building 12A | G | G02 | West Entrance | Fire Doors (tagged 'Robson Doors, 202-') | Insulation Core | Suspected Negative | - | - | - | - | No |
KENC | Kensington Campus | B12A | Building 12A | G | G02 | South & East Entrances | Fire Doors (tagged 'Wormald, 201-') | Insulation Core | Suspected Negative | - | - | - | - | No |
KENC | Kensington Campus | B12A | Building 12A | G | G02 | Central, Main Switchgear | Within Electrical Cabinets | Electrical Backing Boards | Suspected Negative | - | - | - | - | No |
KENC | Kensington Campus | B12A | Building 12A | G | G01 & G02 | Below Ground Service Trench (beneath metal cover plates) | Conduits | Moulded Fibre Cement Pipes | Suspected Positive | Non-friable | Low | P4 | Further investigation should be undertaken to confirm presence and extent of asbestos materials in the service trences prior to demolition or refurbishment works. | No |
KENC | Kensington Campus | B12A | Building 12A | G | G01 | No access (Ausgrid controlled) | - | - | - | - | - | - | - | No |
KENC | Kensington Campus | H22A | Garbage Disposal Unit H22A | G | 01 | Throughout | No asbestos materials identified | - | Negative | - | - | - | - | N/A |
KENC | Kensington Campus | H25 | Botany Street Parking Station | 01 | F1Q01 F1Q02 F1Q03 F1Q04 | Throughout | Fire Hose Reel Cupboards | No asbestos materials identified | - | - | - | - | - | N/A |
KENC | Kensington Campus | H25 | Botany Street Parking Station | 02 | F2Q01 F2Q02 F2Q03 F2Q04 | Throughout | Fire Hose Reel Cupboards | No asbestos materials identified | - | - | - | - | - | N/A |
KENC | Kensington Campus | H25 | Botany Street Parking Station | 03 | F3Q01 F3Q02 F3Q03 F3Q04 | Throughout | Fire Hose Reel Cupboards | No asbestos materials identified | - | - | - | - | - | N/A |
KENC | Kensington Campus | H25 | Botany Street Parking Station | 04 | F4Q01 F4Q02 F4Q03 F4Q04 | Throughout | Fire Hose Reel Cupboards | No asbestos materials identified | - | - | - | - | - | N/A |
KENC | Kensington Campus | H25 | Botany Street Parking Station | 05 | F5Q01 F5Q02 F5Q03 F5Q04 | Throughout | Fire Hose Reel Cupboards | No asbestos materials identified | - | - | - | - | - | N/A |
KENE | Kensington Environs | BS32 | 32 Botany Street | G | - | Exterior, West Sunroom | Wall Cladding | Fibre Cement Sheeting | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment works. | No |
KENE | Kensington Environs | BS32 | 32 Botany Street | G | 6 | - | Wall Lining | Fibre Cement Sheeting | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment works. | No |
KENE | Kensington Environs | BS32 | 32 Botany Street | G | 7 | - | Ceiling | Fibre Cement Sheeting | Positive (Amosite, Chrysotile and Crocidolite) | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment works. | No |
KENC | Kensington Campus | H8 | Sam Cracknell Pavilion | - | - | Throughout | No asbestos materials identified | - | Negative | - | - | - | - | N/A |
KENC | Kensington Campus | J12 | Newton | G | G17 | On Floor | Duct Work Gasket | Insulation / Debris | - | - | - | - | Item removed - No removal documentation provided | Yes |
KENC | Kensington Campus | J12 | Newton | 1 | 1Q4 | Door | Fire Door | Insulation Core | - | - | - | - | Item Removed: No removal documentation provided. Fire doors tagged 'GRG Fire Doors, 201_'). | Yes |
KENC | Kensington Campus | J12 | Newton | 1 | 1Q5 | Riser Entrance | Fire Door | Insulation Core | - | - | - | - | Item Removed: No removal documentation provided. Fire doors tagged 'TDS 201_'). | Yes |
KENC | Kensington Campus | J12 | Newton | 2 | 2Q5 | Riser Entrance | Fire Door | Insulation Core | - | - | - | - | Item removed (fire door tagged GRG Fire Door, 201_). No removal documentation provided | Yes |
KENC | Kensington Campus | J12 | Newton | 3 | 302A | Plant Room | Toilet Exhaust Duct Work & Fan Joints | Mastic Sealant | Removed - Positive (chrysotile) | - | - | - | Item Removed: Refer to RiskTech Compliance Clearance Certificate dated 3 May 2021. Removed by Pure Contracting. | Yes |
KENC | Kensington Campus | J12 | Newton | 3 | 302A | Plant Room | Calorifier Door | Rope Seal | - | - | - | - | Item removed - No removal documentation provided | Yes |
KENC | Kensington Campus | J12 | Newton | 3 | 3Q3 | Riser Entrance | Fire Door | Insulation Core | - | - | - | - | Item Removed: No removal documentation provided. Fire doors tagged 'TDS 201_'). | Yes |
KENC | Kensington Campus | J12 | Newton | R | RQ01 | Plant Room Entrance | Fire Door | Insulation Core | - | - | - | - | Item Removed: No removal documentation provided. Fire doors tagged 'TDS 201_'). | Yes |
KENC | Kensington Campus | J12 | Newton | R | R02 | Plant Room | Boiler Flue | Rope Seal | - | - | - | - | Item Removed: Refer to Greencap-NAA Clearance Certificate (Ref: C107266:J134461). Removed by ATS 8/8/2015 | Yes |
KENC | Kensington Campus | J12 | Newton | R | R02 | Plant Room | Boiler Pipe Work | Gaskets | - | - | - | - | Item Removed: Refer to Greencap-NAA Clearance Certificate (Ref: C107266:J134461). Removed by ATS 8/8/2015. | Yes |
KENC | Kensington Campus | J17 | Ainsworth Building | - | - | Throughout | No asbestos materials identified | - | Negative | - | - | - | - | N/A |
KENC | Kensington Campus | K14 | Physics Theatre | LG | LG09A | - | Floor Covering | Vinyl Tiles | - | - | - | - | Item Removed 19/8/2017. Refer to RiskTech Asbestos Clearance Certificate dated 19/9/2017. | Yes |
KENC | Kensington Campus | K14 | Physics Theatre | G | G19-G21 | - | Floor Covering | Vinyl Tiles | - | - | - | - | Item Removed 21/2/2009. Refer to NAA Clearance Certificate SS0263:71828 dated 21/2/2009. | Yes |
KENC | Kensington Campus | K15 | Old Main | LG | LG07 | - | Floor Covering | Vinyl Tiles | - | - | - | - | Item Removed 18/06/2007. Refer to NAA Clearance Certificate 54547 and Air Monitoring Report 54547.001. | Yes |
KENC | Kensington Campus | K15 | Old Main | LG | LG08 | - | Ceiling | Fibre Cement Sheeting | - | - | - | - | Item Removed 18/06/2007. Refer to NAA Clearance Certificate 54547 and Air Monitoring Report 54547.001. | Yes |
KENC | Kensington Campus | K15 | Old Main | LG | LG22 | - | Floor Covering | Vinyl Tiles (cream colour) | - | - | - | - | Item Removed. No removal/clearance documentation was provided. | Yes |
KENC | Kensington Campus | K15 | Old Main | LG | LG22A | - | Floor Covering | Vinyl Tiles (cream colour) | - | - | - | - | Item Removed. No removal/clearance documentation was provided. | Yes |
KENC | Kensington Campus | K15 | Old Main | LG | LG23 | - | Floor Covering | Vinyl Tiles (cream colour) | - | - | - | - | Item Removed. No removal/clearance documentation was provided. | Yes |
KENC | Kensington Campus | K15 | Old Main | LG | LG24 | - | Floor Covering | Vinyl Tiles (cream colour) | - | - | - | - | Item Removed. No removal/clearance documentation was provided. | Yes |
KENC | Kensington Campus | K15 | Old Main | LG | LG24A | - | Floor Covering | Vinyl Tiles (cream colour) | - | - | - | - | Item Removed. No removal/clearance documentation was provided. | Yes |
KENC | Kensington Campus | K15 | Old Main | LG | LG24B | - | Floor Covering | Vinyl Tiles (cream colour) | - | - | - | - | Item Removed. No removal/clearance documentation was provided. | Yes |
KENC | Kensington Campus | K15 | Old Main | LG | LG32 | Duct Riser, Redundant on Floor | Flue | Moulded Fibre Cement | - | - | - | - | Item Removed. No removal/clearance documentation was provided. | Yes |
KENC | Kensington Campus | K15 | Old Main | LG | LG32 | Duct Riser | Debris | Pipe Lagging | - | - | - | - | Item Removed 1/3/2008. Refer to NAA Clearance Certificate 62829 and Air Monitoring Reports 62829.006-008. | Yes |
KENC | Kensington Campus | K15 | Old Main | LG | LG44 | - | Air Conditioning Ductwork Heater Bank | Insulation Board | - | - | - | - | Item Removed. No removal/clearance documentation was provided. | Yes |
KENC | Kensington Campus | K15 | Old Main | LG | LG55 | Duct Riser | Ceiling | Fibre Cement Sheeting | - | - | - | - | Item Removed. No removal/clearance documentation was provided. | Yes |
KENC | Kensington Campus | K15 | Old Main | LG | LGQ02 | Throughout | Ceiling | Fibre Cement Sheeting | - | - | - | - | Item Removed on 11/01/2014 by Ashton Demolition Pty Ltd. Refer to Airsafe Clearance Certificate (ref: 21909) dated January 2014. | Yes |
KENC | Kensington Campus | K15 | Old Main | LG | LGQ12 | - | Floor Covering | Vinyl Tiles | - | - | - | - | Item Removed 01/01/2008. Refer to NAA Clearance Certificate 71182 and Air Monitoring Report 71182.001 | Yes |
KENC | Kensington Campus | K15 | Old Main | G | G05 | - | Floor Covering | Vinyl Tiles | - | - | - | - | Item Removed 16/02/2008. Refer to NAA Clearance Certificate 55783 dated February 2008. | Yes |
KENC | Kensington Campus | K15 | Old Main | G | G06 | - | Floor Covering | Vinyl Tiles (green colour) | - | - | - | - | Item Removed. No removal/clearance documentation was provided. | Yes |
KENC | Kensington Campus | K15 | Old Main | G | G16 | - | Ceiling | Fibre Cement Sheeting | - | - | - | - | Item Removed 1/2/2009. Refer to NAA Clearance Certificate 71828 and Air Monitoring Report 71828.001. | Yes |
KENC | Kensington Campus | K15 | Old Main | G | G31 | - | Floor Covering | Vinyl Tiles (grey colour) | - | - | - | - | Item Removed. No removal/clearance documentation was provided. | Yes |
KENC | Kensington Campus | K15 | Old Main | G | G32 | - | Floor Covering | Vinyl Tiles (grey colour) | - | - | - | - | Item Removed. No removal/clearance documentation was provided. | Yes |
KENC | Kensington Campus | K15 | Old Main | G | G36 | - | Floor Covering | Vinyl Tiles (green colour) | - | - | - | - | Item Removed 14/5/2008. Refer to NAA Clearance Certificate 62829 and Air Monitoring Reports 62829.009-010. | Yes |
KENC | Kensington Campus | K15 | Old Main | G | G36 | Under Stud Partition Walls | Floor Covering | Vinyl Tiles (green colour) | - | - | - | - | Item Removed 13/08/2013. Refer to NAA Clearance Certificate 62829 and Air Monitoring Reports 62829.011-012. | Yes |
KENC | Kensington Campus | K15 | Old Main | G | G37 | - | Floor Covering | Vinyl Tiles (green colour) | - | - | - | - | Item Removed 13/08/2013. Refer to NAA Clearance Certificate 62829 and Air Monitoring Reports 62829.011-012. | Yes |
KENC | Kensington Campus | K15 | Old Main | G | G37 | - | Floor Covering | Vinyl Tiles (green colour) | - | - | - | - | Item Removed 13/08/2013. Refer to NAA Clearance Certificate 62829 and Air Monitoring Reports 62829.011-012. | Yes |
KENC | Kensington Campus | K15 | Old Main | G | G37 | Under Stud Partition Walls | Floor Covering | Vinyl Tiles | - | - | - | - | Item Removed. No removal/clearance documentation was provided. | Yes |
KENC | Kensington Campus | K15 | Old Main | G | G38 | - | Floor Covering | Vinyl Tiles (green colour) | - | - | - | - | Item Removed 13/08/2013. Refer to NAA Clearance Certificate 62829 and Air Monitoring Reports 62829.011-012. | Yes |
KENC | Kensington Campus | K15 | Old Main | G | G38 | Under Stud Partition Walls | Floor Covering | Vinyl Tiles | - | - | - | - | Item Removed. No removal/clearance documentation was provided. | Yes |
KENC | Kensington Campus | K15 | Old Main | G | G39 | - | Floor Covering | Vinyl Tiles (green colour) | - | - | - | - | No | |
KENC | Kensington Campus | K15 | Old Main | G | G40 | Mineral Separator Plinth | Bench | Fibre Cement Sheeting | - | - | - | - | Item Removed. No removal/clearance documentation was provided. | Yes |
KENC | Kensington Campus | K15 | Old Main | G | G42 | - | Oven Door Seal | Rope | - | - | - | - | Item Removed. No removal/clearance documentation was provided. | Yes |
KENC | Kensington Campus | K15 | Old Main | G | G43 | - | Pipework Insulation | Lagging | - | - | - | - | Item Removed 13/03/2008. Refer to NAA Clearance Certificate 62928 and Air Monitoring Reports 62829.006-008. | Yes |
KENC | Kensington Campus | K15 | Old Main | G | G46A | - | Ceiling | Fibre Cement Sheeting | - | - | - | - | Item Removed. No removal/clearance documentation was provided. | Yes |
KENC | Kensington Campus | K15 | Old Main | G | G48 | - | Floor Covering | Vinyl Tiles (green colour) | - | - | - | - | Item Removed. No removal/clearance documentation was provided. | Yes |
KENC | Kensington Campus | K15 | Old Main | G | G49A | - | Floor Covering | Vinyl Tiles (green colour) | - | - | - | - | Item Removed. No removal/clearance documentation was provided. | Yes |
KENC | Kensington Campus | K15 | Old Main | G | G49B | - | Floor Covering | Vinyl Tiles (green colour) | - | - | - | - | Item Removed. No removal/clearance documentation was provided. | Yes |
KENC | Kensington Campus | K15 | Old Main | G | G49B | Under Stud Partition Walls | Floor Covering | Vinyl Tiles (green colour) | - | - | - | - | Item Removed. No removal/clearance documentation was provided. | Yes |
KENC | Kensington Campus | K15 | Old Main | G | G50 | - | Floor Covering | Vinyl Tiles (green colour) | - | - | - | - | Item Removed. No removal/clearance documentation was provided. | Yes |
KENC | Kensington Campus | K15 | Old Main | G | G50A | - | Floor Covering | Vinyl Tiles (green colour) | - | - | - | - | Item Removed. No removal/clearance documentation was provided. | Yes |
KENC | Kensington Campus | K15 | Old Main | G | G51 | - | Floor Covering | Vinyl Tiles (green colour) | - | - | - | - | Item Removed 1/4/2008. Refer to NAA Clearance Certificate 62829 and Air Monitoring Reports 62829.009-010. | Yes |
KENC | Kensington Campus | K15 | Old Main | G | G51A | - | Floor Covering | Vinyl Tiles (green colour) | - | - | - | - | Item Removed 1/4/2008. Refer to NAA Clearance Certificate 62829 and Air Monitoring Reports 62829.009-010. | Yes |
KENC | Kensington Campus | K15 | Old Main | G | G51B | - | Floor Covering | Vinyl Tiles (green colour) | - | - | - | - | Item Removed. No removal/clearance documentation was provided. | Yes |
KENC | Kensington Campus | K15 | Old Main | G | G52 | - | Floor Covering | Vinyl Tiles (green colour) | - | - | - | - | Item Removed 1/4/2008. Refer to NAA Clearance Certificate 62829 and Air Monitoring Reports 62829.009-010. | Yes |
KENC | Kensington Campus | K15 | Old Main | G | G53 | - | Floor Covering | Vinyl Tiles (green colour) | - | - | - | - | Item Removed 1/4/2008. Refer to NAA Clearance Certificate 62829 and Air Monitoring Reports 62829.009-010. | Yes |
KENC | Kensington Campus | K15 | Old Main | G | G53A | - | Floor Covering | Vinyl Tiles (green colour) | - | - | - | - | Item Removed 1/4/2008. Refer to NAA Clearance Certificate 62829 and Air Monitoring Reports 62829.009-010. | Yes |
KENC | Kensington Campus | K15 | Old Main | G | G54 | - | Floor Covering | Vinyl Tiles (green colour) | - | - | - | - | Item Removed 1/4/2008. Refer to NAA Clearance Certificate 62829 and Air Monitoring Reports 62829.009-010. | Yes |
KENC | Kensington Campus | K15 | Old Main | G | G55 | - | Floor Covering | Vinyl Tiles (green colour) | - | - | - | - | Item Removed 1/4/2008. Refer to NAA Clearance Certificate 62829 and Air Monitoring Reports 62829.009-010. | Yes |
KENC | Kensington Campus | K15 | Old Main | G | G56 | - | Floor Covering | Vinyl Tiles (green colour) | - | - | - | - | Item Removed 1/4/2008. Refer to NAA Clearance Certificate 62829 and Air Monitoring Reports 62829.009-010. | Yes |
KENC | Kensington Campus | K15 | Old Main | G | G60C | - | Floor Covering | Vinyl Tiles (green colour) | - | - | - | - | Item Removed. No removal/clearance documentation was provided. | Yes |
KENC | Kensington Campus | K15 | Old Main | G | G61 | - | Floor Covering | Vinyl Tiles (green colour) | - | - | - | - | Item Removed 14/01/2011. Refer to NAA Clearance Certificate 77747 and Air Monitoring Report 77747.020. | Yes |
KENC | Kensington Campus | K15 | Old Main | G | G61A | - | Floor Covering | Vinyl Tiles (green colour) | - | - | - | - | Item Removed. No removal/clearance documentation was provided. | Yes |
KENC | Kensington Campus | K15 | Old Main | G | G61C | - | Floor Covering | Vinyl Tiles (green colour) | - | - | - | - | Item Removed 1/1/2011. Refer to NAA Clearance Certificate 77747 and Air Monitoring Report 77747.020. | Yes |
KENC | Kensington Campus | K15 | Old Main | G | G62 | - | Floor Covering | Vinyl Tiles (green colour) | - | - | - | - | Item Removed. No removal/clearance documentation was provided. | Yes |
KENC | Kensington Campus | K15 | Old Main | G | G62B | - | Floor Covering | Vinyl Tiles (green colour) | - | - | - | - | Item Removed. No removal/clearance documentation was provided. | Yes |
KENC | Kensington Campus | K15 | Old Main | G | G62C | - | Floor Covering | Vinyl Tiles (green colour) | - | - | - | - | Item Removed. No removal/clearance documentation was provided. | Yes |
KENC | Kensington Campus | K15 | Old Main | G | G62D | - | Floor Covering | Vinyl Tiles (green colour) | - | - | - | - | Item Removed. No removal/clearance documentation was provided. | Yes |
KENC | Kensington Campus | K15 | Old Main | G | G62D1 | - | Floor Covering | Vinyl Tiles (green colour) | - | - | - | - | Item Removed. No removal/clearance documentation was provided. | Yes |
KENC | Kensington Campus | K15 | Old Main | G | G62F | - | Floor Covering | Vinyl Tiles (green colour) | - | - | - | - | Item Removed. No removal/clearance documentation was provided. | Yes |
KENC | Kensington Campus | K15 | Old Main | G | G64B | - | Floor Covering | Vinyl Tiles (green colour) | - | - | - | - | Item Removed. No removal/clearance documentation was provided. | Yes |
KENC | Kensington Campus | K15 | Old Main | G | GQ12 | - | Floor Covering | Vinyl Tiles (green colour) | - | - | - | - | Item Removed 1/10/2008. Refer to NAA Clearance Certificate 68997 and Air Monitoring Reports 68997.001-002. | Yes |
KENC | Kensington Campus | K15 | Old Main | G | GQ14 | - | Floor Covering | Vinyl Tiles (green colour) | - | - | - | - | Item Removed 11/02/2008. Refer to NAA Clearance Certificate 55783 and Air Monitoring Reports 55783.007-008. | Yes |
KENC | Kensington Campus | K15 | Old Main | G | GQ15 | - | Floor Covering | Vinyl Tiles (green colour) | - | - | - | - | Item Removed 1/02/2008. Refer to NAA Clearance Certificate 55783 and Air Monitoring Reports 55783.007-008. | Yes |
KENC | Kensington Campus | K15 | Old Main | G | GQ18 | - | Floor Covering | Vinyl Tiles (green colour) | - | - | - | - | Item Removed 4/02/2008. Refer to NAA Clearance Certificate 55783 and Air Monitoring Reports 55783.003-004. | Yes |
KENC | Kensington Campus | K15 | Old Main | G | GQ19 | - | Floor Covering | Vinyl Tiles (green colour) | - | - | - | - | Item Removed 1/02/2009. Refer to NAA Clearance Certificate 71828 and Air Monitoring Reports 71828.001 | Yes |
KENC | Kensington Campus | K15 | Old Main | G | GQ20 | - | Floor Covering | Vinyl Tiles (green colour) | - | - | - | - | Item Removed 1/02/2009. Refer to NAA Clearance Certificate 71828 and Air Monitoring Reports 71828.001 | Yes |
KENC | Kensington Campus | K15 | Old Main | G | GQ21 | - | Floor Covering | Vinyl Tiles (green colour) | - | - | - | - | Item Removed 1/02/2009. Refer to NAA Clearance Certificate 71828 and Air Monitoring Reports 71828.001 | Yes |
KENC | Kensington Campus | K15 | Old Main | G | GQ22 | - | Floor Covering | Vinyl Tiles (green colour) | - | - | - | - | Item Removed 1/02/2009. Refer to NAA Clearance Certificate 71828 and Air Monitoring Reports 71828.001 | Yes |
KENC | Kensington Campus | K15 | Old Main | G | GQ25 | - | Floor Covering | Vinyl Tiles (green colour) | - | - | - | - | Item Removed 11/02/2008. Refer to NAA Clearance Certificate 55783 and Air Monitoring Reports 55783.001-002 | Yes |
KENC | Kensington Campus | K15 | Old Main | 01 | 101 | - | Floor Covering | Vinyl Tiles (light grey colour) | - | - | - | - | Item Removed. No removal/clearance documentation was provided. | Yes |
KENC | Kensington Campus | K15 | Old Main | 01 | 101 | - | Floor Covering | Vinyl Tiles (grey colour) | - | - | - | - | Item Removed. No removal/clearance documentation was provided. | Yes |
KENC | Kensington Campus | K15 | Old Main | 01 | 101 | - | Floor Covering | Vinyl Tiles (blue colour) | - | - | - | - | Item Removed. No removal/clearance documentation was provided. | Yes |
KENC | Kensington Campus | K15 | Old Main | 01 | 101A | - | Floor Covering | Vinyl Tiles (light grey colour) | - | - | - | - | Item Removed. No removal/clearance documentation was provided. | Yes |
KENC | Kensington Campus | K15 | Old Main | 01 | 101B | - | Floor Covering | Vinyl Tiles (light grey colour) | - | - | - | - | Item Removed. No removal/clearance documentation was provided. | Yes |
KENC | Kensington Campus | K15 | Old Main | 01 | 101C | Throughout | Floor Covering | Vinyl Tiles (light grey colour) | - | - | - | - | Item removed. No removal/clearance documention was provided. | Yes |
KENC | Kensington Campus | K15 | Old Main | 01 | 101C1 | Throughout | Floor Covering | Vinyl Tiles (light grey colour) | - | - | - | - | Item removed. No removal/clearance documention was provided. | Yes |
KENC | Kensington Campus | K15 | Old Main | 01 | 101C2 | Throughout | Floor Covering | Vinyl Tiles (light grey colour) | - | - | - | - | Item removed. No removal/clearance documention was provided. | Yes |
KENC | Kensington Campus | K15 | Old Main | 01 | 102 | - | Floor Covering | Vinyl Tiles (light grey colour) | - | - | - | - | Item Removed. No removal/clearance documentation was provided. | Yes |
KENC | Kensington Campus | K15 | Old Main | 01 | 102A | Throughout | Floor Covering | Vinyl Tiles (light grey colour) | - | - | - | - | Item removed. No removal/clearance documention was provided. | Yes |
KENC | Kensington Campus | K15 | Old Main | 01 | 102B | Throughout | Floor Covering | Vinyl Tiles (light grey colour) | - | - | - | - | Item removed. No removal/clearance documention was provided. | Yes |
KENC | Kensington Campus | K15 | Old Main | 01 | 102C | Throughout | Floor Covering | Vinyl Tiles (light grey colour) | - | - | - | - | Item removed. No removal/clearance documention was provided. | Yes |
KENC | Kensington Campus | K15 | Old Main | 01 | 105 | - | Floor Covering | Vinyl Tiles (light grey colour) | - | - | - | - | Item Removed. No removal/clearance documentation was provided. | Yes |
KENC | Kensington Campus | K15 | Old Main | 01 | 106 | - | Floor Covering | Vinyl Tiles (light grey colour) | - | - | - | - | Item Removed. No removal/clearance documentation was provided. | Yes |
KENC | Kensington Campus | K15 | Old Main | 01 | 107 | - | Floor Covering | Vinyl Tiles (light grey colour) | - | - | - | - | Item Removed. No removal/clearance documentation was provided. | Yes |
KENC | Kensington Campus | K15 | Old Main | 01 | 108 | Throughout | Floor Covering | Vinyl Tiles (light grey colour) | - | - | - | - | Item removed. No removal/clearance documention was provided. | Yes |
KENC | Kensington Campus | K15 | Old Main | 01 | 113 | - | Floor Covering | Vinyl Tiles (light grey colour) | - | - | - | - | Item Removed. No removal/clearance documentation was provided. | Yes |
KENC | Kensington Campus | K15 | Old Main | 01 | 114 | - | Floor Covering | Vinyl Tiles (grey colour) | - | - | - | - | Item Removed. No removal/clearance documentation was provided. | Yes |
KENC | Kensington Campus | K15 | Old Main | 01 | 115 | - | Floor Covering | Vinyl Tiles (grey colour) | - | - | - | - | Item Removed. No removal/clearance documentation was provided. | Yes |
KENC | Kensington Campus | K15 | Old Main | 01 | 116 | - | Floor Covering | Vinyl Tiles (grey colour) | - | - | - | - | Item Removed. No removal/clearance documentation was provided. | Yes |
KENC | Kensington Campus | K15 | Old Main | 01 | 117 | - | Floor Covering | Vinyl Tiles (grey colour) | - | - | - | - | Item Removed. No removal/clearance documentation was provided. | Yes |
KENC | Kensington Campus | K15 | Old Main | 01 | 118 | - | Floor Covering | Vinyl Tiles (grey colour) | - | - | - | - | Item Removed. No removal/clearance documentation was provided. | Yes |
KENC | Kensington Campus | K15 | Old Main | 01 | 119 | - | Floor Covering | Vinyl Tiles (grey colour) | - | - | - | - | Item Removed. No removal/clearance documentation was provided. | Yes |
KENC | Kensington Campus | K15 | Old Main | 01 | 119A | - | Floor Covering | Vinyl Tiles (grey colour) | - | - | - | - | Item Removed. No removal/clearance documentation was provided. | Yes |
KENC | Kensington Campus | K15 | Old Main | 01 | 120 | - | Floor Covering | Vinyl Tiles (grey colour) | - | - | - | - | Item Removed. No removal/clearance documentation was provided. | Yes |
KENC | Kensington Campus | K15 | Old Main | 01 | 121 | - | Floor Covering | Vinyl Tiles (grey colour) | - | - | - | - | Item Removed. No removal/clearance documentation was provided. | Yes |
KENC | Kensington Campus | K15 | Old Main | 01 | 122 | - | Floor Covering | Vinyl Tiles (grey colour) | - | - | - | - | Item Removed. No removal/clearance documentation was provided. | Yes |
KENC | Kensington Campus | K15 | Old Main | 01 | 129 | - | Floor Covering | Vinyl Tiles (grey colour) | - | - | - | - | Item Removed. No removal/clearance documentation was provided. | Yes |
KENC | Kensington Campus | K15 | Old Main | 01 | 130 | - | Floor Covering | Vinyl Tiles (grey colour) | - | - | - | - | Item Removed. No removal/clearance documentation was provided. | Yes |
KENC | Kensington Campus | K15 | Old Main | 01 | 131 | - | Floor Covering | Vinyl Tiles (grey colour) | - | - | - | - | Item Removed. No removal/clearance documentation was provided. | Yes |
KENC | Kensington Campus | K15 | Old Main | 01 | 132 | - | Floor Covering | Vinyl Tiles (grey colour) | - | - | - | - | Item Removed. No removal/clearance documentation was provided. | Yes |
KENC | Kensington Campus | K15 | Old Main | 01 | 133 | - | Floor Covering | Vinyl Tiles (grey colour) | - | - | - | - | Item Removed. No removal/clearance documentation was provided. | Yes |
KENC | Kensington Campus | K15 | Old Main | 01 | 133A | - | Floor Covering | Vinyl Tiles (grey colour) | - | - | - | - | Item Removed. No removal/clearance documentation was provided. Room no longer present or relocated. | Yes |
KENC | Kensington Campus | K15 | Old Main | 01 | 135 | - | Floor Covering | Vinyl Tiles (light grey colour) | - | - | - | - | Item Removed. No removal/clearance documentation was provided. Room no longer present or relocated. | Yes |
KENC | Kensington Campus | K15 | Old Main | 01 | 137 | - | Floor Covering | Vinyl Tiles (light grey colour) | - | - | - | - | Item Removed. No removal/clearance documentation was provided. Room no longer present or relocated. | Yes |
KENC | Kensington Campus | K15 | Old Main | 01 | 137A | - | Floor Covering | Vinyl Tiles (light grey colour) | - | - | - | - | Item Removed. No removal/clearance documentation was provided. Room no longer present or relocated. | Yes |
KENC | Kensington Campus | K15 | Old Main | 01 | 137B | - | Floor Covering | Vinyl Tiles (light grey colour) | - | - | - | - | Item Removed. No removal/clearance documentation was provided. Room no longer present or relocated. | Yes |
KENC | Kensington Campus | K15 | Old Main | 01 | 137C | - | Floor Covering | Vinyl Tiles (light grey colour) | - | - | - | - | Item Removed. No removal/clearance documentation was provided. Room no longer present or relocated. | Yes |
KENC | Kensington Campus | K15 | Old Main | 01 | 137D | - | Floor Covering | Vinyl Tiles (light grey colour) | - | - | - | - | Item Removed. No removal/clearance documentation was provided. Room no longer present or relocated. | Yes |
KENC | Kensington Campus | K15 | Old Main | 01 | 138A | - | Floor Covering | Vinyl Tiles (light grey colour) | - | - | - | - | Item Removed. No removal/clearance documentation was provided. Room no longer present or relocated. | Yes |
KENC | Kensington Campus | K15 | Old Main | 01 | 138B | - | Floor Covering | Vinyl Tiles (light grey colour) | - | - | - | - | Item Removed. No removal/clearance documentation was provided. Room no longer present or relocated. | Yes |
KENC | Kensington Campus | K15 | Old Main | 01 | 138C | - | Floor Covering | Vinyl Tiles (light grey colour) | - | - | - | - | Item Removed. No removal/clearance documentation was provided. Room no longer present or relocated. | Yes |
KENC | Kensington Campus | K15 | Old Main | 01 | 138D | - | Floor Covering | Vinyl Tiles (light grey colour) | - | - | - | - | Item Removed. No removal/clearance documentation was provided. Room no longer present or relocated. | Yes |
KENC | Kensington Campus | K15 | Old Main | 01 | 139 | - | Floor Covering | Vinyl Tiles (light grey colour) | - | - | - | - | Item Removed. No removal/clearance documentation was provided. | Yes |
KENC | Kensington Campus | K15 | Old Main | 01 | 141A | Above Suspended Ceiling | Ceiling | Fibre Cement Sheeting | - | - | - | - | Item Removed 21/03/2015 by Pure Contracting. Refer to Greencap Clearance Certificate 132192 dated March 2015. | Yes |
KENC | Kensington Campus | K15 | Old Main | 01 | 144 | - | Floor Covering | Vinyl Tiles (grey colour) | - | - | - | - | Item Removed. No removal/clearance documentation was provided. | Yes |
KENC | Kensington Campus | K15 | Old Main | 01 | 144A | - | Floor Covering | Vinyl Tiles (grey colour) | - | - | - | - | Item Removed. No removal/clearance documentation was provided. | Yes |
KENC | Kensington Campus | K15 | Old Main | 01 | 145 | - | Floor Covering | Vinyl Tiles (grey colour) | - | - | - | - | Item Removed 21/11/2015. Refer to Airsafe Asbestos Clearance Certificate dated 23/11/2015 (report reference: 29259). | Yes |
KENC | Kensington Campus | K15 | Old Main | 01 | 145A | - | Floor Covering | Vinyl Tiles (grey colour) | - | - | - | - | Item Removed. No removal/clearance documentation was provided. | Yes |
KENC | Kensington Campus | K15 | Old Main | 01 | 146 | - | Floor Covering | Vinyl Tiles (grey colour) | - | - | - | - | Item Removed 21/11/2015. Refer to Airsafe Asbestos Clearance Certificate dated 23/11/2015 (report reference: 29259). | Yes |
KENC | Kensington Campus | K15 | Old Main | 01 | 148 | - | Floor Covering | Vinyl Tiles (grey colour) | - | - | - | - | Item Removed 15/9/2009. Refer to Clearance Report (ref:SS0263:76754 dated 15 September 2009) | Yes |
KENC | Kensington Campus | K15 | Old Main | 01 | 152 | - | Floor Covering | Vinyl Tiles (grey colour) | - | - | - | - | Item Removed 15/2/2014. Refer to NAA Clearance Certificate J124675 dated 17/2/2014. | Yes |
KENC | Kensington Campus | K15 | Old Main | 01 | 153 | Duct Riser | Pipework Insulation | Lagging | - | - | - | - | Item Removed 1/3/2009. Refer to NAA Clearance Certificate 62829 and Air Monitoring Reports 62829.006-008. | Yes |
KENC | Kensington Campus | K15 | Old Main | 01 | 154 | - | Ceiling | Fibre Cement Sheeting | - | - | - | - | Item Removed. No removal/clearance documentation was provided. | Yes |
KENC | Kensington Campus | K15 | Old Main | 01 | 155 | - | Floor Covering | Vinyl Tiles (grey colour) | - | - | - | - | Item Removed 29-31/1/2008. Refer to Clearance Certificate SU0013:62829 dated 2 January 2008 dated 31 January 2008 | Yes |
KENC | Kensington Campus | K15 | Old Main | 01 | 156 | - | Floor Covering | Vinyl Tiles (grey colour) | - | - | - | - | Item Removed 1/1/2008. Refer to NAA Clearance Certificate 62829 and Air Monitoring Reports 62829.001-003. | Yes |
KENC | Kensington Campus | K15 | Old Main | 01 | 157 | - | Floor Covering | Vinyl Tiles (grey colour) | - | - | - | - | Item Removed. No removal/clearance documentation was provided. | Yes |
KENC | Kensington Campus | K15 | Old Main | 01 | 158 | - | Floor Covering | Vinyl Tiles (grey colour) | - | - | - | - | Item removed 1/1/2008. Refer to NAA Clearance Certificate 62829 and Air Monitoring Reports 62829.001-003. | Yes |
KENC | Kensington Campus | K15 | Old Main | 01 | 158 | Floor Under Bench and Stud Partition Walls and Doors or North & Eastern Area | Floor Covering | Vinyl Tiles | - | - | - | - | Item Removed. No removal/clearance documentation was provided. | Yes |
KENC | Kensington Campus | K15 | Old Main | 01 | 158A | - | Floor Covering | Vinyl Tiles (grey colour) | - | - | - | - | Item Removed. No removal/clearance documentation was provided. | Yes |
KENC | Kensington Campus | K15 | Old Main | 01 | 158B | - | Floor Covering | Vinyl Tiles (grey colour) | - | - | - | - | Item Removed. No removal/clearance documentation was provided. | Yes |
KENC | Kensington Campus | K15 | Old Main | 01 | 159 | - | Floor Covering | Vinyl Tiles (grey colour) | - | - | - | - | Item Removed. No removal/clearance documentation was provided. | Yes |
KENC | Kensington Campus | K15 | Old Main | 01 | 159 | Under East Stud Partition Wall | Floor Covering | Vinyl Tiles (grey colour) | - | - | - | - | Item Removed. No removal/clearance documentation was provided. | Yes |
KENC | Kensington Campus | K15 | Old Main | 01 | 159A | - | Floor Covering | Vinyl Tiles (grey colour) | - | - | - | - | Item Removed 1/1/2008. Refer to NAA Clearance Certificate 62829 and Air Monitoring Reports 62829.001-003. | Yes |
KENC | Kensington Campus | K15 | Old Main | 01 | 159B | - | Floor Covering | Vinyl Tiles (grey colour) | - | - | - | - | Item Removed 1/1/2008. Refer to NAA Clearance Certificate 62829 and Air Monitoring Reports 62829.001-003. | Yes |
KENC | Kensington Campus | K15 | Old Main | 01 | 159C | - | Floor Covering | Vinyl Tiles (grey colour) | - | - | - | - | Item Removed 1/1/2008. Refer to NAA Clearance Certificate 62829 and Air Monitoring Reports 62829.001-003. | Yes |
KENC | Kensington Campus | K15 | Old Main | 01 | 159D | - | Floor Covering | Vinyl Tiles (grey colour) | - | - | - | - | Item Removed 1/1/2008. Refer to NAA Clearance Certificate 62829 and Air Monitoring Reports 62829.001-003. | Yes |
KENC | Kensington Campus | K15 | Old Main | 01 | 159E | - | Floor Covering | Vinyl Tiles (grey colour) | - | - | - | - | Item Removed 1/1/2008. Refer to NAA Clearance Certificate 62829 and Air Monitoring Reports 62829.001-003. | Yes |
KENC | Kensington Campus | K15 | Old Main | 01 | 159F | - | Floor Covering | Vinyl Tiles (grey colour) | - | - | - | - | Item Removed 1/1/2008. Refer to NAA Clearance Certificate 62829 and Air Monitoring Reports 62829.001-003. | Yes |
KENC | Kensington Campus | K15 | Old Main | 01 | 163 | - | Floor Covering | Vinyl Tiles (grey colour) | - | - | - | - | Item Removed. No removal/clearance documentation was provided. | Yes |
KENC | Kensington Campus | K15 | Old Main | 01 | 164 | - | Floor Covering | Vinyl Tiles (grey colour) | - | - | - | - | Item Removed. No removal/clearance documentation was provided. | Yes |
KENC | Kensington Campus | K15 | Old Main | 01 | 1Q10 | - | Floor Covering | Vinyl Tiles (grey colour) | - | - | - | - | Item Removed. No removal/clearance documentation was provided. | Yes |
KENC | Kensington Campus | K15 | Old Main | 01 | 1Q12 | - | Floor Covering | Vinyl Tiles (grey colour) | - | - | - | - | Item Removed 1/5/2010. Refer to NAA Clearance Certificate 77747 and Air Monitoring Report 77747.010. | Yes |
KENC | Kensington Campus | K15 | Old Main | 01 | 1Q12 | - | Floor Covering | Vinyl Tiles (grey colour) | - | - | - | - | Item Removed 1/5/2010. Refer to NAA Clearance Certificate 77747 and Air Monitoring Report 77747.010. | Yes |
KENC | Kensington Campus | K15 | Old Main | 01 | 1Q15 | - | Floor Covering | Vinyl Tiles (grey colour) | - | - | - | - | Item Removed. No removal/clearance documentation was provided. | Yes |
KENC | Kensington Campus | K15 | Old Main | 01 | 1Q16 | - | Floor Covering | Vinyl Tiles (grey colour) | - | - | - | - | Item Removed. No removal/clearance documentation was provided. | Yes |
KENC | Kensington Campus | K15 | Old Main | 01 | 1Q17 | - | Floor Covering | Vinyl Tiles (grey colour) | - | - | - | - | Item Removed 1/2/2009. Refer to NAA Clearance Certificate 71705 and Air Monitoring Report 71705.001. | Yes |
KENC | Kensington Campus | K15 | Old Main | 01 | 1Q18 | - | Floor Covering | Vinyl Tiles (light grey colour) | - | Item removed 1/2/2008. Refer to NAA Clearance Certificate 55783 and Air Monitoring Reports 55783.005--006. | Yes | |||
KENC | Kensington Campus | K15 | Old Main | 01 | 1Q19 | - | Floor Covering | Vinyl Tiles (grey colour) | - | - | - | - | Item Removed. No removal/clearance documentation was provided. | Yes |
KENC | Kensington Campus | K15 | Old Main | 02 | 210C | Duct Riser | Pipework Insulation | Lagging | - | - | - | - | Item Removed 1/3/2008. Refer to NAA Clearance Certificate 62829 and Air Monitoring Reports 62829.006-008. | Yes |
KENC | Kensington Campus | K15 | Old Main | 02 | 224 | - | Floor Covering | Vinyl Tiles (green and cream colour) | - | - | - | - | Item Removed 21/6/2014. Refer to Greencap Clearance Certificate J127216 dated June 2014. | Yes |
KENC | Kensington Campus | K15 | Old Main | 02 | 228 | Beneath Partition Walls | Floor Covering | Vinyl Tiles | - | - | - | - | Item Removed 9/11/2013 by Aston Demolition. Refer to Airsafe Air Monitoring and Clearance Reports 21307 dated November 2013. | Yes |
KENC | Kensington Campus | K15 | Old Main | 02 | 228 | - | Floor Covering | Vinyl Tiles | - | - | - | - | Item Removed 19/2/2011. Refer to NAA Clearance Certificate SS0263:77747 dated 19/2/2011. | Yes |
KENC | Kensington Campus | K15 | Old Main | 02 | 229 | Beneath Partition Walls | Floor Covering | Vinyl Tiles | - | - | - | - | Item Removed 9/11/2013 by Aston Demolition. Refer to Airsafe Air Monitoring and Clearance Reports 21307 dated November 2013. | Yes |
KENC | Kensington Campus | K15 | Old Main | 02 | 229 | - | Floor Covering | Vinyl Tiles | - | - | - | - | Item Removed 19/2/2011. Refer to NAA Clearance Certificate SS0263:77747 dated 19/2/2011. | Yes |
KENC | Kensington Campus | K15 | Old Main | 02 | 230 | Beneath Partition Walls | Floor Covering | Vinyl Tiles | - | - | - | - | Item Removed 9/11/2013 by Aston Demolition. Refer to Airsafe Air Monitoring and Clearance Reports 21307 dated November 2013. | Yes |
KENC | Kensington Campus | K15 | Old Main | 02 | 230 | Entry Way | Floor Covering | Vinyl Tiles | - | - | - | - | Item Removed 9/11/2013 by Aston Demolition. Refer to Airsafe Air Monitoring and Clearance Reports 21307 dated November 2013. | Yes |
KENC | Kensington Campus | K15 | Old Main | 02 | 233 | Entry Way | Floor Covering | Vinyl Tiles | - | - | - | - | Item Removed 9/11/2013 by Aston Demolition. Refer to Airsafe Air Monitoring and Clearance Reports 21307 dated November 2013. | Yes |
KENC | Kensington Campus | K15 | Old Main | 02 | 234 | - | Floor Covering | Vinyl Tiles | - | - | - | - | Item Removed 9/11/2013 by Aston Demolition. Refer to Airsafe Air Monitoring and Clearance Reports 21307 dated November 2013. | Yes |
KENC | Kensington Campus | K15B | Substation 31 | G | - | Substation 31 | - | No asbestos materials identified | Negative | - | - | - | - | N/A |
KENC | Kensington Campus | K17 | Building K17 | 1 | 1Q04 | Fire Exit | Fire Door | Core Insulation | - | - | - | - | Item removed. No removal/clearance documention was provided. | Yes |
KENC | Kensington Campus | K17 | Building K17 | 3 | 301 | West | Fire Door (Tagged 1972) | Core Insulation | - | - | - | - | Item removed. No removal/clearance documention was provided. | Yes |
KENC | Kensington Campus | K17 | Building K17 | 4 | 401 | West | Fire Door (No tag) | Core Insulation | - | - | - | - | Item removed. No removal/clearance documention was provided. | Yes |
KENC | Kensington Campus | L5 | Building L5 | - | - | Throughout Building | No asbestos materials identified or suspected | - | Negative | - | - | - | - | N/A |
Kenc | Kensington Campus | M15 | Rupert Myers | 01-05 | - | Male and Female Toilets | No asbestos materials identified | - | Negative | - | - | - | - | N/A |
Kenc | Kensington Campus | M15 | Rupert Myers | 01-05 | - | Accessible Toilets | No asbestos materials identified | - | Negative | - | - | - | - | N/A |
Kenc | Kensington Campus | M15 | Rupert Myers | 01-05 | - | Electrical and Mechanical Riser Cupboards | Inside Electrical Cabinets | Electrical Backing Boards | Suspected Negative | - | - | - | - | N/A |
Kenc | Kensington Campus | M15 | Rupert Myers | 01-05 | - | Fire Hose Reel Cupboards | No asbestos materials identified | - | Negative | - | - | - | - | N/A |
KENE | Kensington Environs | BS32 | 32 Botany Street | G | 7 | - | Wall Lining | Fibre Cement Sheeting | Assumed Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment works. | No |
KENE | Kensington Environs | BS32 | 32 Botany Street | G | - | Exterior, East | Eaves | Fibre Cement Sheeting | Assumed Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment works. | No |
Kenc | Kensington Campus | N13 | Barker Apartments | - | - | Throughout Building | No asbestos materials identified | - | Negative | - | - | - | - | N/A |
Kenc | Kensington Campus | N18 | Barker Street Parking Station | - | - | Throughout | No asbestos materials identified | - | Negative | - | - | - | - | N/A |
Kenc | Kensington Campus | N18 | Barker Street Parking Station | 01 | 1Q4 | North | Electrical Switchboard | No asbestos materials identified | - | - | - | - | - | N/A |
KENE | Kensington Environs | BS32 | 32 Botany Street | G | - | Exterior, East and South-East | Gable | Fibre Cement Sheeting | Assumed Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment works. | No |
KENC | Kensington Campus | SST1D | Main Service Tunnel H13 Branch | G | - | Throughout | No asbestos materials Identified | - | Negative | - | - | - | - | N/A |
KENC | Kensington Campus | SST1E | Main Service Tunnel G14 Mid Branch | G | - | Throughout | No asbestos materials Identified | - | Negative | - | - | - | - | N/A |
KENC | Kensington Campus | SST1F | Main Service Tunnel G17 Branch | G | - | Throughout | No asbestos materials Identified | - | Negative | - | - | - | - | N/A |
KENC | Kensington Campus | SST1B | Main Service Tunnel F13 Branch | G | - | Throughout | No asbestos materials Identified | - | Negative | - | - | - | - | N/A |
KENC | Kensington Campus | SST1A | Main Service Tunnel F12 Branch | G | - | Throughout | No asbestos materials Identified | - | Negative | - | - | - | - | N/A |
KENE | Kensington Environs | BS22 | Tiggers Place | - | - | Throughout Building | No asbestos materials identified | - | Negative | - | - | - | - | N/A |
KENE | Kensington Environs | BS26 | 26 Botany Street | G | - | - | No asbestos materials identified | - | Negative | - | - | - | - | N/A |
KENE | Kensington Environs | HS30 | 30 High Street | G - 1 | - | Throughout | No asbestos materials identified | - | Negative | - | - | - | - | N/A |
KENE | Kensington Environs | HS32 | 32 High Street | G - 1 | - | Throughout | No asbestos items identified | - | Negative | - | - | - | - | N/A |
KENE | Kensington Environs | BS32 | 32 Botany Street | G | - | Exterior | Gable Verge Lining | Fibre Cement Sheeting | Negative | - | - | - | - | N/A |
KENE | Kensington Environs | WR45 | 45 Wansey Road | G - 1 | - | - | No asbestos materials identified | - | Negative | - | - | - | - | N/A |
MANV | Manly Vale | MV1 | Laboratory 1 | G | - | Throughout | No asbestos materials identified | - | - | - | - | - | - | N/A |
KENE | Kensington Environs | BS32 | 32 Botany Street | G | - | Exterior, South-East | Within Electrical Cabinet | Electrical Backing Board | Suspected Negative | - | - | - | - | No |
KENE | Kensington Environs | BS32 | 32 Botany Street | G | - | Exterior, South-East | Within Electrical Cabinet | Electrical Backing Board | Suspected Positive - Removed | - | - | - | - | Yes |
MANV | Manly Vale | MV5 | Toilet Block | G | - | Throughout or Localised Area(s) (beneath cement, plaster or similar material) | Soffit Formwork (Underside of Concrete Roof Slab) | Fibre Cement Sheeting | Suspected Positive | Non-friable | Low | P4 | Investigate the presence of asbestos containing fibre cement sheet formwork in other areas prior to demolition or refurbishment. | No |
KENC | Kensington Campus | C19 | Garbage Disposal Unit | G | G01 | Exterior Throughout | Wall | Fibre Cement Sheeting | Negative | - | - | - | - | N/A |
MANV | Manly Vale | MV7 | Laboratory 4 | G | - | Throughout | No asbestos materials identified | - | - | - | - | - | - | N/A |
MANV | Manly Vale | MV9 | Laboratory 3 | G | - | Throughout | No asbestos materials identified | - | - | - | - | - | - | N/A |
KENC | Kensington Campus | C19 | Garbage Disposal Unit | G | G01 | Exterior Throughout | Wall Cladding | Fibre Cement Sheeting | Negative | - | - | - | - | N/A |
RANC | Randwick Campus | R14 | Institute of Languages | G - 2 | - | Ground Level to Level 3, Communications Riser Cupboard | Fire Doors Door tagged ' Australasian Fire Doors, 1999' | Core Insulation | Suspected Negative | - | - | - | - | N/A |
RANC | Randwick Campus | R17 | Substation R17 | G | - | Substation 6958 | No asbestos materials identified | - | - | - | - | - | - | N/A |
RANC | Randwick Campus | R1a | Randwick R1a | G | - | Throughout | No asbestos materials identified | - | - | - | - | - | - | N/A |
RANC | Randwick Campus | R1b | Randwick R1b | G | - | Throughout | No asbestos materials identified | - | - | - | - | - | - | N/A |
RANC | Randwick Campus | R1c | Randwick R1c | G | - | Throughout | No asbestos materials identified | - | - | - | - | - | - | N/A |
RANC | Randwick Campus | R1d | Randwick R1d | G | - | Throughout | No asbestos materials identified | - | - | - | - | - | - | N/A |
RANC | Randwick Campus | R1e | Randwick R1e | G | - | Throughout | No asbestos materials identified | - | - | - | - | - | - | N/A |
KENC | Kensington Campus | C19 | Garbage Disposal Unit | G | G01 | Throughout | No asbestos materials identified | - | Negative | - | - | - | - | N/A |
RANC | Randwick Campus | R4 | Randwick R4 | G | - | Throughout | No asbestos materials identified | - | - | - | - | - | - | N/A |
RANC | Randwick Campus | R6 | Randwick R6 | G | - | Throughout | No asbestos materials identified | - | - | - | - | - | - | N/A |
RANC | Randwick Campus | R8 | Switchroom Throughout | G | Switchroom | Throughout | No asbestos materials identified | - | - | - | - | - | - | N/A |
Kenc | Kensington Campus | C20 | Morven Brown External Car Park | G | - | Exterior Throughout including Roadways, Gardens, Footpaths | No asbestos materials identified | - | Negative | - | - | - | - | N/A |
KENC | Kensington Campus | H20 | Civil Engineering | 5 | 512 | Throughout (beneath carpet) | Floor Covering | Vinyl Tiles (Aqua Colour) | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | H20 | Civil Engineering | 2 | - | Exterior, UCA Roof Area | Floor Covering & Base of Wall (beneath concrete pavers) | Bituminous Membrane | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | H20 | Civil Engineering | 2 | - | Exterior, UCA Roof Area | Inside Electrical Cabinet | Electrical Backing Board | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | F23 | Mathews Building | 18 | - | Roof Above Level 18 | Roof (beneath concrete plinths supporting plant & equipment eg; antennas, vents & covers) | Bituminous Membrane | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | E4 | Squarehouse | 03 | 301 | East | Window Frames (between frame & pane) | Mastic Sealant (black colour) | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | E4 | Squarehouse | 01 | 1Q4 | Fire Services Riser Cupboard & Hydraulic Duct Riser Cupboard | Ductwork Joint & Joins | Mastic Sealant (red/green colour) | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | E4 | Squarehouse | 01 | 114 | East | Window Frames (between frame & pane) | Mastic Sealant (black colour) | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | B5 | Fitness and Aquatic Centre | 01 | 141 | Squash Courts (B7), Duct Riser | Ductwork Joins | Mastic Sealant (red colour) | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | G27 | AGSM | 4 | 405 | Plant Room, Entrance | Fire Door (tagged 'Masterbilt') | Core Insulation | Door removed & replaced with new door 2020 | Yes | ||||
KENC | Kensington Campus | C22 | Chancellery | LG | LG20 | Serive Tunnel off LG20, Southern End, Floor Slab | Conduit | Moulded Fibre Cement Pipes | Positive | Non-friable | Low | P3 | Seal exposed edges of the pipes under controlled conditions. Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | F10 | Chemical Sciences | LR | R1Q01 | Exterior, Throughout, Trafficable Roof Area | Floor Covering (below concrete pavers) | Bituminous Membrane | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | F10 | Chemical Sciences | RL2 | R5 | Lift Motor Room | Lift Motors (installed 2005) | Brake Pads | Suspected Negative | - | - | - | - | No |
KENC | Kensington Campus | F10 | Chemical Sciences | RL2 | R2Q01 | Exterior | Roof Floor Covering | Bituminous Membrane | Positive (chrysotile) | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | F10 | Chemical Sciences | RL2 | R2Q02 | Exterior | Roof Floor Covering | Bituminous Membrane | Positive (chrysotile) | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | F10 | Chemical Sciences | LG | LGQ3 | Switch Room / Substation No.9, Adjacent Entrance - on Floor | Conduit | Moulded Fibre Cement | Positive | Non-friable | Low | P3 | Seal damaged edges. Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | N8 | House at Pooh Corner | G | G1 | Throughout (except majority of northern section - vinyl floor tiles present beneath walls and fixtures / benches) | Floor Covering | Vinyl Floor Tiles (beneath carpet tiles) | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | N8 | House at Pooh Corner | G | G13 | Throughout (except majority of northern section - vinyl floor tiles present beneath walls and fixtures / benches) | Floor Covering | Vinyl Floor Tiles (beneath carpet tiles) | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | N8 | House at Pooh Corner | G | G14 | East | Wall | Fibre Cement Sheeting | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | N8 | House at Pooh Corner | G | G23 | Throughout (except majority of northern section - vinyl floor tiles present beneath walls and fixtures / benches) | Floor Covering | Vinyl Floor Tiles (beneath carpet tiles) | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | G6 | Blockhouse | G | G8C | - | Conduit | Moulded Fibre Cement Pipe | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | G6 | Blockhouse | 1 | 109 | North, Behind New Window Panelling | Window Beading | Sealant Mastic | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | G6 | Blockhouse | 1 | 1Q03 | East | Window Beading | Sealant Mastic | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | F21 | Library | 1 | 1Q25 | Service Tunnel, East End, South Wall | Conduits | Moulded Fibre Cement Pipes & Bituminous Material | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | F21 | Library | 11 | - | Roof Terrace, Covered Terrace & Roof Above SE Fire Stairs (11Q9) | Roof Covering & Parapet Walls (assumed beneath new membrane and/or concrete topping) | Bituminous Membrane | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | F21 | Library | Roof | - | Roof | Roof Covering (beneath new membrane) | Bituminous Membrane Remnants | Positive (chrysotile) | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | F20 | Goodsell | 01 | 139 | - | Window Beading | Sealant Mastic | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | F20 | Goodsell | G | - | Exterior, Surround Doors | Expansion Joints | Sealant Mastic | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | F20 | Goodsell | B - 03 | - | Exterior, Below Windows | Expansion Wall Joints | Sealant Mastic | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | F10 | Chemical Sciences | 1 | 1Q1 | - | Floor Covering | Vinyl Tiles (olive green) | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | F10 | Chemical Sciences | 1 | 1Q4 | - | Floor Covering | Adhesive (attached to vinyl tile) | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | F10 | Chemical Sciences | 1 | 1Q1 | - | Floor Covering | Adhesive (attached to vinyl tile) | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | F10 | Chemical Sciences | 1 | 1Q4 | - | Floor Covering | Vinyl Tiles (olive green) | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | F10 | Chemical Sciences | 2 | 2Q1 | - | Floor Covering | Adhesive (attached to vinyl tile) | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | F10 | Chemical Sciences | 2 | 2Q4 | - | Floor Covering | Adhesive (attached to vinyl tile) | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | F10 | Chemical Sciences | 2 | 2Q1 | - | Floor Covering | Vinyl Tiles (olive green) | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | F10 | Chemical Sciences | 2 | 2Q4 | - | Floor Covering | Vinyl Tiles (olive green) | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | F10 | Chemical Sciences | 3 | 3Q1 | - | Floor Covering | Adhesive (attached to vinyl tile) | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | F10 | Chemical Sciences | 3 | 3Q2 | - | Floor Covering | Adhesive (attached to vinyl tile) | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | F10 | Chemical Sciences | 3 | 3Q4 | - | Floor Covering | Adhesive (attached to vinyl tile) | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | F10 | Chemical Sciences | 3 | 3Q1 | - | Floor Covering | Vinyl Tiles (olive green) | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | F10 | Chemical Sciences | 3 | 3Q2 | - | Floor Covering | Vinyl Tiles (olive green) | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | F10 | Chemical Sciences | 3 | 3Q4 | - | Floor Covering | Vinyl Tiles (olive green) | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | F10 | Chemical Sciences | 4 | 4Q1 | - | Floor Covering | Adhesive (attached to vinyl tile) | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | F10 | Chemical Sciences | 4 | 4Q4 | - | Floor Covering | Adhesive (attached to vinyl tile) | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | F10 | Chemical Sciences | 4 | 4Q1 | - | Floor Covering | Vinyl Tiles (olive green) | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | F10 | Chemical Sciences | 4 | 4Q4 | - | Floor Covering | Vinyl Tiles (olive green) | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | F10 | Chemical Sciences | 5 | 5Q1 | - | Floor Covering | Adhesive (attached to vinyl tile) | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | F10 | Chemical Sciences | 5 | 5Q2 | - | Floor Covering | Adhesive (attached to vinyl tile) | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | F10 | Chemical Sciences | 5 | 5Q4 | - | Floor Covering | Adhesive (attached to vinyl tile) | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | F10 | Chemical Sciences | 5 | 5Q1 | - | Floor Covering | Vinyl Tiles (olive green) | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | F10 | Chemical Sciences | 5 | 5Q2 | - | Floor Covering | Vinyl Tiles (olive green) | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | F10 | Chemical Sciences | 5 | 5Q4 | - | Floor Covering | Vinyl Tiles (olive green) | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | F10 | Chemical Sciences | 6 | 6Q1 | - | Floor Covering | Adhesive (attached to vinyl tile) | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | F10 | Chemical Sciences | 6 | 6Q2 | - | Floor Covering | Adhesive (attached to vinyl tile) | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | F10 | Chemical Sciences | 6 | 6Q4 | - | Floor Covering | Adhesive (attached to vinyl tile) | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | F10 | Chemical Sciences | 6 | 6Q1 | - | Floor Covering | Vinyl Tiles (olive green) | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | F10 | Chemical Sciences | 6 | 6Q2 | - | Floor Covering | Vinyl Tiles (olive green) | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | F10 | Chemical Sciences | 6 | 6Q4 | - | Floor Covering | Vinyl Tiles (olive green) | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | F10 | Chemical Sciences | 7 | 7Q1 | - | Floor Covering | Adhesive (attached to vinyl tile) | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | F10 | Chemical Sciences | 7 | 7Q2 | - | Floor Covering | Adhesive (attached to vinyl tile) | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | F10 | Chemical Sciences | 7 | 7Q4 | - | Floor Covering | Adhesive (attached to vinyl tile) | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | F10 | Chemical Sciences | 7 | 7Q1 | - | Floor Covering | Vinyl Tiles (olive green) | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | F10 | Chemical Sciences | 7 | 7Q2 | - | Floor Covering | Vinyl Tiles (olive green) | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | F10 | Chemical Sciences | 7 | 7Q4 | - | Floor Covering | Vinyl Tiles (olive green) | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | F10 | Chemical Sciences | 8 | 8Q1 | - | Floor Covering | Adhesive (attached to vinyl tile) | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | F10 | Chemical Sciences | 8 | 8Q2 | - | Floor Covering | Adhesive (attached to vinyl tile) | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | F10 | Chemical Sciences | 8 | 8Q4 | - | Floor Covering | Adhesive (attached to vinyl tile) | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | F10 | Chemical Sciences | 8 | 8Q1 | - | Floor Covering | Vinyl Tiles (olive green) | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | F10 | Chemical Sciences | 8 | 8Q2 | - | Floor Covering | Vinyl Tiles (olive green) | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | F10 | Chemical Sciences | 8 | 8Q4 | - | Floor Covering | Vinyl Tiles (olive green) | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | F10 | Chemical Sciences | 9 | 9Q1 | - | Floor Covering | Adhesive (attached to vinyl tile) | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | F10 | Chemical Sciences | 9 | 9Q2 | - | Floor Covering | Adhesive (attached to vinyl tile) | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | F10 | Chemical Sciences | 9 | 9Q4 | - | Floor Covering | Adhesive (attached to vinyl tile) | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | F10 | Chemical Sciences | 9 | 9Q1 | - | Floor Covering | Vinyl Tiles (olive green) | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | F10 | Chemical Sciences | 9 | 9Q2 | - | Floor Covering | Vinyl Tiles (olive green) | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | F10 | Chemical Sciences | 9 | 9Q4 | - | Floor Covering | Vinyl Tiles (olive green) | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENE | Kensington Environs | BS34 | 34 to 36 Botany Street | G | G20B | Toilet Cubicle | Partitioning | Compressed Fibre Cement Sheeting | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENE | Kensington Environs | BS34 | 34 to 36 Botany Street | G | G20B | - | Ceiling | Fibre Cement Sheeting | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENE | Kensington Environs | O14 | Kangas House | G | - | Exterior, Western Building, Outside Rooms 1 - 8F | Eaves | Fibre Cement Sheeting | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENE | Kensington Environs | O14 | Kangas House | G | GQ01 | Exterior, Electrical Cupboard | Meter Board | Electrical Backing Board | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | G17 | Electrical Engineering | G | GQ20 | Substation 7 | Floor Penetrations, Electrical Conduits | Moulded Fibre Cement | Positive | Non-Friable | Low | P4 | Maintain in good condition. Remove under controlled conditions prior to demolition or refurbishment. | No |
CCS | Cliffbrook Campus | CC4 | Building CC4 | 02 | - | Exterior, Surrounding | Eaves | Fibre Cement Sheeting | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | F21 | Library | 1 | 1Q11 | - | Beneath Sheet Vinyl | Adhesive | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | K15 | Old Main | G | G12 | - | Air Conditioning Ductwork Heater Bank | Insulation Board | Positive | Friable | Low | P3 | Not sighted during inspection. Heater bank may be present above suspended ceiling tiles. If present, remedial works should be undertaken by a Class A Contractor within a planned control program. | No |
KENC | Kensington Campus | C22 | Chancellery | LG | LG35 | West Side, SW Corner | Conduit | Moulded Fibre Cement Pipes | Positive | Non-friable | Low | P3 | Seal exposed edges of the pipes under controlled conditions. Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | C22 | Chancellery | LG | LGQ8 | Adjacent LG23, Riser | Conduit | Moulded Fibre Cement Pipe | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | C22 | Chancellery | 03 | - | Exterior Throughout | Eaves | Fibre Cement Sheeting | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | C22 | Chancellery | G | UGQ1 | Exterior, East Side, Main Entrance | Awning Ceiling | Fibre Cement Sheeting | Positive - Removed | - | - | - | Item Removed: Refer to RiskTech Clearance Certificate dated 22 December 2016. | Yes |
KENC | Kensington Campus | C22 | Chancellery | G | G23 | - | Fire Door (tagged ' Metabilt, 1970') | Core Insulation | Positive - Removed | - | - | - | Item Removed: Refer to RiskTech Clearance Certificate dated 10 April 2019. | Yes |
KENC | Kensington Campus | C22 | Chancellery | G | G20A | - | Fire Door | Core Insulation | Positive - Removed | - | - | - | Item Removed: No removal/clearance documentation was provided. New appearance fire door tagged ' Bismac, 2014'. | Yes |
KENC | Kensington Campus | C22 | Chancellery | G | G21 | - | Fire Door | Core Insulation | Positive - Removed | - | - | - | Item Removed: No removal/clearance documentation was provided. New appearance fire door tagged ' Bismac, 2014'. | Yes |
KENC | Kensington Campus | C22 | Chancellery | G | G22 | - | Fire Door (tagged 'Metabilt, 1970') | Core Insulation | Positive - Removed | - | - | - | Item Removed: Refer to RiskTech Clearance Certificate dated 10 April 2019. | Yes |
KENC | Kensington Campus | K14 | Physics Theatre | LG | LG11C | - | Floor Covering | Vinyl Tiles (green colour) | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | H20 | Civil Engineering | 8 | 802 | Throughout | Windows | Mastic Sealant | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | C22 | Chancellery | G | G24 | - | Fire Door | Core Insulation | Positive - Removed | - | - | - | Item Removed: Refer to Greencap Clearance Certificate dated 28 September 2015. New appearance fire door tagged ' TDF, 2015'. | Yes |
KENC | Kensington Campus | C22 | Chancellery | 01 | 142 | - | Fire Door | Core Insulation | Positive - Removed | - | - | - | Item Removed: Refer to Greencap Clearance Certificate dated 28 September 2015. New appearance fire door tagged ' TDF, 2015'. | Yes |
MANV | Manly Vale | MV4 | Workshop | G | G03 | - | Floor Covering | Vinyl Tiles (grey colour) | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
MANV | Manly Vale | MV3 | Laboratory 2 | G | - | Exterior, Eastern Office/Amenities Section | Eaves | Fibre Cement Sheeting | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
MANV | Manly Vale | MV3 | Laboratory 2 | G | G01 | East | Wall | Fibre Cement Sheeting | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | C22 | Chancellery | 02 | 242 | - | Fire Door | Core Insulation | Positive - Removed | - | - | - | Item removed prior to Greencap 2014 inspection. No removal documentation provided. | Yes |
KENC | Kensington Campus | C22 | Chancellery | 03 | 310B | Plant Room | Fire Door | Core Insulation | Positive - Removed | - | - | - | Item Removed: Refer to RiskTech Clearance Certificate dated 21 October 2017. | Yes |
KENC | Kensington Campus | C22 | Chancellery | LG | LG29 | East Side, Access to Service Tunnel | Fire Door (no tag) | Core Insulation | Positive (Amosite) | Non-friable | Med | P3 | Remedial works should be undertaken by a Class A Contractor within a planned control program. | No |
KENC | Kensington Campus | C22 | Chancellery | B | B08 | - | Ductwork Flange Joints | Sealant Mastic | Positive (Chrysotile) | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | C22 | Chancellery | LG | LG12 | Former Lift Motor Room, South Wall | Board (labelled 'Zelemite') | Electrical Backing Board | Positive (Chrysotile) | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | C22 | Chancellery | 01 | 113-126 | North Wing, Under Carpet | Floor Covering | Vinyl Tiles | Assumed Negative | - | - | - | - | No |
KENC | Kensington Campus | C22 | Chancellery | 01 | 146-159 | South Wing, Under Carpet | Floor Covering | Vinyl Tiles | Assumed Negative | - | - | - | - | No |
KENC | Kensington Campus | C22 | Chancellery | 01 | 1Q1 | North Wing, Under Carpet | Floor Covering | Vinyl Tiles | Assumed Negative | - | - | - | - | No |
KENC | Kensington Campus | C22 | Chancellery | LG | LG03-LG04 | Various Locations - | Ceiling | Decorative Coating (vermiculite) | Assumed Negative | - | - | - | - | No |
KENC | Kensington Campus | C22 | Chancellery | LG | LG29 | - | Ceiling | Decorative Coating (vermiculite) | Assumed Negative | - | - | - | - | No |
KENC | Kensington Campus | C22 | Chancellery | LG | LG29A | - | Ceiling | Decorative Coating (vermiculite) | Assumed Negative | - | - | - | - | No |
KENC | Kensington Campus | C22 | Chancellery | LG | LG29B | - | Ceiling | Decorative Coating (vermiculite) | Assumed Negative | - | - | - | - | No |
KENC | Kensington Campus | C22 | Chancellery | LG | LG29C | - | Ceiling | Decorative Coating (vermiculite) | Assumed Negative | - | - | - | - | No |
KENC | Kensington Campus | C22 | Chancellery | G | G01-G38 | - | Ceiling | Decorative Coating (vermiculite) | Assumed Negative | - | - | - | - | No |
KENC | Kensington Campus | C22 | Chancellery | G | GQ1-GQ15 | Throughout Ceiling | Sprayed Insulation | Vermiculite | Assumed Negative | - | - | - | - | No |
KENC | Kensington Campus | C22 | Chancellery | 02 | 201-257 | - | Ceiling | Decorative Coating (vermiculite) | Assumed Negative | - | - | - | - | No |
KENC | Kensington Campus | C22 | Chancellery | 02 | 2Q1-2Q11 | - | Ceiling | Decorative Coating (vermiculite) | Assumed Negative | - | - | - | - | No |
KENC | Kensington Campus | C22 | Chancellery | 03 | 301-310 | Roof Space, Throughout Ceiling Beams | Sprayed Insulation | Vermiculite | Assumed Negative | - | - | - | - | No |
KENC | Kensington Campus | C22 | Chancellery | 03 | 3Q1-3Q6 | Throughout Ceiling Beams | Sprayed Insulation | Vermiculite | Assumed Negative | - | - | - | - | No |
KENC | Kensington Campus | C22 | Chancellery | LG | LGQ8 | - | Ceiling | Decorative Coating (vermiculite) | Assumed Negative | - | - | - | - | No |
KENC | Kensington Campus | C22 | Chancellery | B | B08A | - | Ductwork Flange Joints | Sealant Mastic | Assumed Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | C22 | Chancellery | LG | LG15B | - | Ductwork Flange Joins (old ductwork only) | Sealant Mastic | Assumed Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | K17 | Building K17 | 6 | 6Q05 | Cleaners Cupboard | Floor Covering | Vinyl Tiles Debris | Positive | Non-friable | Low | P3 | Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | K17 | Building K17 | 1 | 1Q02 | Under Carpet | Floor Covering | Vinyl Tiles | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | K17 | Building K17 | 2 | 2Q03 | Cleaners Cupboard | Floor Covering | Vinyl Tiles | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | K17 | Building K17 | 4 | 4Q06 | Under Carpet | Floor Covering | Vinyl Tiles | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | K17 | Building K17 | 4 | 4Q08 | Cleaners Cupboard | Floor Covering | Vinyl Tiles | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | K17 | Building K17 | 5 | 5Q01 | Under Carpet | Floor Covering | Vinyl Tiles | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | K14 | Physics Theatre | 01 | - | Exterior, South Side | Infill Wall Panelling (Fascia) | Fibre Cement Sheeting | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | K15 | Old Main | 01 | 1Q18 | Corridor to Newtown Building | Floor Covering | Vinyl Tiles (beige colour) | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment | No |
KENC | Kensington Campus | K15 | Old Main | 02 | - | Exterior, North, South & East | Eaves | Fibre Cement Sheeting | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | H20 | Civil Engineering | 2 | 2Q1 | Throughout | Floor Covering | Vinyl Tiles (Blue, Grey & White Colour) | Positive - removed | - | - | - | Item removed. Refer Risktech clearance cert dated Sept 2023 | Yes |
KENC | Kensington Campus | H20 | Civil Engineering | 2 | 2Q4 | Throughout | Floor Covering | Vinyl Tiles (Blue, Grey & White Colour) | Positive - removed | - | - | - | Item removed. Refer Risktech clearance cert dated Sept 2023 | Yes |
KENC | Kensington Campus | H20 | Civil Engineering | 3 | 3Q1 | Throughout | Floor Covering | Vinyl Tiles (Blue, Grey & White Colour) | Positive - removed | - | - | - | Item removed. Refer RiskTech clearance cert dated Sept 2023 | Yes |
KENC | Kensington Campus | H20 | Civil Engineering | 3 | 3Q4 | Throughout | Floor Covering | Vinyl Tiles (Blue, Grey & White Colour) | Positive - removed | - | - | - | Item removed. Refer RiskTech clearance cert dated Sept 2023 | Yes |
KENC | Kensington Campus | H20 | Civil Engineering | 4 | 4Q1 | Throughout | Floor Covering | Vinyl Tiles (Blue, Grey & White Colour) | Positive - removed | - | - | - | Item removed. Refer Risktech clearance cert dated 19 Aug 2023 | Yes |
KENC | Kensington Campus | H20 | Civil Engineering | 4 | 4Q4 | Throughout | Floor Covering | Vinyl Tiles (Blue, Grey & White Colour) | Positive - removed | - | - | - | Item removed. Refer Risktech clearance cert dated 19 Aug 2023 | Yes |
KENC | Kensington Campus | H20 | Civil Engineering | 5 | 5Q1 | Throughout | Floor Covering | Vinyl Tiles (Blue, Grey & White Colour) | Positive - removed | - | - | - | - | Yes |
KENC | Kensington Campus | H20 | Civil Engineering | 5 | 5Q4 | Throughout | Floor Covering | Vinyl Tiles (Blue, Grey & White Colour) | Positive - removed | - | - | - | - | Yes |
KENC | Kensington Campus | H20 | Civil Engineering | 1 | 1Q1 | Throughout | Floor Covering | Vinyl Tiles (Blue, Grey & White Colour) | Removed Positive | - | - | - | Item removed. Refer RiskTech clearance cert dated 9th Sept 23 | Yes |
KENC | Kensington Campus | H20 | Civil Engineering | 1 | 1Q6 | Throughout | Floor Covering | Vinyl Tiles (Blue, Grey & White Colour) | Removed Positive | - | - | - | Item removed. Refer RiskTech clearance cert dated 9th Sept 23 | Yes |
KENC | Kensington Campus | H20 | Civil Engineering | 2 | 206 | Throughout | Floor Covering | Vinyl Tiles (Light Green Colour) | Positive - removed | - | - | - | Item removed. Refer Risktech clearance cert dated Sept 2023 | Yes |
KENC | Kensington Campus | H20 | Civil Engineering | 3 | 301 | Throughout | Floor Covering | Vinyl Tiles (Grey & Aqua Colour) | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | H20 | Civil Engineering | 4 | 408 | Throughout | Floor Covering | Vinyl Tiles (Blue & Black Colour) | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | H20 | Civil Engineering | 6 | 601 | Throughout (beneath carpet) | Floor Covering | Vinyl Tiles (Blue Colour) | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | H20 | Civil Engineering | 6 | 601A | Throughout (beneath carpet) | Floor Covering | Vinyl Tiles (Blue Colour) | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | H20 | Civil Engineering | 6 | 601B | Throughout (beneath carpet) | Floor Covering | Vinyl Tiles (Blue Colour) | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | H20 | Civil Engineering | 6 | 603 | Throughout (beneath carpet) | Floor Covering | Vinyl Tiles (Blue Colour) | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | H20 | Civil Engineering | 6 | 604 | Throughout (beneath carpet) | Floor Covering | Vinyl Tiles (Blue Colour) | Removed | - | - | - | Item removed. Refer RiskTech Clearance cert dated 22nd November 2022 | Yes |
KENC | Kensington Campus | H20 | Civil Engineering | 6 | 607 | Throughout (beneath carpet) | Floor Covering | Vinyl Tiles (Blue Colour) | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | H20 | Civil Engineering | 6 | 608 | Throughout (beneath carpet) | Floor Covering | Vinyl Tiles (Blue Colour) | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | H20 | Civil Engineering | 6 | 612 | Throughout (beneath carpet) | Floor Covering | Vinyl Tiles (Blue Colour) | Positive - removed | - | - | - | Item removed. Refer RiskTech clearance cert dated 15 July 2023 | Yes |
KENC | Kensington Campus | H20 | Civil Engineering | 6 | 617 | Throughout (beneath carpet) | Floor Covering | Vinyl Tiles (Blue Colour) | Positive - removed | - | - | - | Item removed. Refer RiskTech clearance cert dated Oct 2023 | Yes |
KENC | Kensington Campus | H20 | Civil Engineering | 6 | 6Q1 | Throughout | Floor Covering | Vinyl Tiles (Blue, Grey & White Colour) | Positive - removed | - | - | - | Item removed. Refer RiskTech clearance cert dated Oct 2023 | Yes |
KENC | Kensington Campus | H20 | Civil Engineering | 6 | 6Q4 | Throughout | Floor Covering | Vinyl Tiles (Blue, Grey & White Colour) | Positive - removed | - | - | - | Item removed. Refer RiskTech clearance cert dated Oct 2023 | Yes |
KENC | Kensington Campus | H20 | Civil Engineering | 7 | 7Q1 | Throughout | Floor Covering | Vinyl Tiles (Blue, Grey & White Colour) | Positive - removed | - | - | - | Item removed. Refer Risktech clearance cert dated Oct 23 | Yes |
KENC | Kensington Campus | H20 | Civil Engineering | 7 | 7Q4 | Throughout | Floor Covering | Vinyl Tiles (Blue, Grey & White Colour) | Positive - removed | - | - | - | Item removed. Refer Risktech clearance cert dated Oct 23 | Yes |
KENC | Kensington Campus | H20 | Civil Engineering | LG | LGQ1 | Throughout | Floor Covering | Vinyl Tiles (Mustard & Aqua Colour) | Positive - removed | - | - | - | Item removed. Refer RiskTech clearance cert dated Dec 2023 | Yes |
KENC | Kensington Campus | H20 | Civil Engineering | LG | LGQ2 | Throughout | Floor Covering | Vinyl Tiles (Mustard & Aqua Colour) | Positive - removed | - | - | - | Item removed. Refer RiskTech clearance cert dated Dec 2023 | Yes |
KENC | Kensington Campus | H20 | Civil Engineering | G | GQ2 | Hallway Adjacent Lift Lobby | Floor Covering | Vinyl Tiles (Grey & Blue Colour) | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | H20 | Civil Engineering | 7 | 709 | Throughout | Floor Covering | Vinyl Tiles (Light Green Colour) | Positive - removed | - | - | - | Item removed. Refer Risktech clearance cert dated Oct 23 | Yes |
KENC | Kensington Campus | H20 | Civil Engineering | 4 | 401 | Throughout (beneath carpet) | Floor Covering | Vinyl Tiles (Grey Colour) | Positive - removed | - | - | - | Item removed. Refer Risktech clearance cert dated 05/08/2023 | Yes |
KENC | Kensington Campus | H20 | Civil Engineering | 4 | 401A | Throughout (beneath carpet) | Floor Covering | Vinyl Tiles (Grey Colour) | Positive - removed | - | - | - | Item removed. Refer Risktech clearance cert dated 05/08/2023 | Yes |
KENC | Kensington Campus | H20 | Civil Engineering | 4 | 402 | Throughout (beneath carpet) | Floor Covering | Vinyl Tiles (Grey Colour) | Positive - removed | - | - | - | Item removed. Refer Risktech clearance cert dated 05/08/2023 | Yes |
KENC | Kensington Campus | H20 | Civil Engineering | 4 | 404 | Throughout (beneath carpet) | Floor Covering | Vinyl Tiles (Grey Colour) | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | H20 | Civil Engineering | 4 | 404A | Throughout (beneath new flooring) | Floor Covering | Vinyl Tiles (Grey Colour) | Positive - removed | - | - | - | Item removed. Refer RiskTech Clearance cert dated 30/05/2022 | Yes |
KENC | Kensington Campus | H20 | Civil Engineering | 4 | 416 | Throughout (beneath carpet) | Floor Covering | Vinyl Tiles (Grey Colour) | Positive - removed | - | - | - | Item removed. Refer Risktech clearance cert dated 19 Aug 2023 | Yes |
KENC | Kensington Campus | H20 | Civil Engineering | 7 | 702 | Throughout (beneath carpet) | Floor Covering | Vinyl Tiles (Blue Colour) | Removed - Positive | - | - | - | Item Removed: Refer to RiskTech Compliance Clearance Certificate dated 4 November 2019. Removed by Pure Contracting. | Yes |
KENC | Kensington Campus | H20 | Civil Engineering | 7 | 703 | Throughout (beneath carpet) | Floor Covering | Vinyl Tiles (Blue Colour) | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | H20 | Civil Engineering | 7 | 705 | Throughout (beneath carpet) | Floor Covering | Vinyl Tiles (Blue Colour) | Tiles removed | Refer Risktech Clearance Certificate dated 20210206 | Yes | |||
KENC | Kensington Campus | H20 | Civil Engineering | 7 | 706 | Throughout (beneath carpet) | Floor Covering | Vinyl Tiles (Blue Colour) | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | H20 | Civil Engineering | 7 | 710 | Throughout (beneath carpet) | Floor Covering | Vinyl Tiles (Blue Colour) | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | H20 | Civil Engineering | 7 | 712 | Throughout (beneath carpet) | Floor Covering | Vinyl Tiles (Blue Colour) | Positive - removed | - | - | - | Item removed. Refer Risktech clearance cert dated 15 July 2023 | Yes |
KENC | Kensington Campus | H20 | Civil Engineering | 7 | 715 | Throughout (beneath carpet) | Floor Covering | Vinyl Tiles (Blue Colour) | Removed - Positive | - | - | - | Item Removed: Refer to RiskTech Compliance Clearance Certificate dated 4 November 2019. Removed by Pure Contracting. | Yes |
KENC | Kensington Campus | H20 | Civil Engineering | 7 | 716 | Throughout (beneath carpet) | Floor Covering | Vinyl Tiles (Blue Colour) | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | H20 | Civil Engineering | 7 | 717 | Beneath Partition Walls | Floor Covering | Vinyl Tiles (Blue Colour) | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | H20 | Civil Engineering | 7 | 717A | Beneath Partition Walls | Floor Covering | Vinyl Tiles (Blue Colour) | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | H20 | Civil Engineering | 7 | 717B | Beneath Partition Walls | Floor Covering | Vinyl Tiles (Blue Colour) | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | H20 | Civil Engineering | 7 | 717C | Beneath Partition Walls | Floor Covering | Vinyl Tiles (Blue Colour) | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | H20 | Civil Engineering | 7 | 718 | Throughout (beneath carpet) | Floor Covering | Vinyl Tiles (Blue Colour) | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | H20 | Civil Engineering | 7 | 719 | Throughout (beneath carpet) | Floor Covering | Vinyl Tiles (Blue Colour) | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | H20 | Civil Engineering | 7 | 720 | Throughout | Floor Covering | Vinyl Tiles (Grey Colour) | Positive - removed | - | - | - | Item removed. Refer Risktech clearance cert dated Oct 23 | Yes |
Kenc | Kensington Campus | G15 | Robert Webster Theatres | 01 | 191 | West, Interior & Exterior | Window Frames (Between Frame and Pane) | Mastic Sealant | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | C22 | Chancellery | LG | LG18 | - | Ductwork Flange Joins (old ductwork only) | Sealant Mastic | Assumed Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | F22 | Bank | - | - | Exterior, South Side, SW Corner (Common Joint with Library Building F21) | Wall Expansion Joints | Mastic Sealant | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | F22 | Bank | 01 | 104 | Australia Post - Store | Floor Covering | Vinyl Tiles (cream & green colour) | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | F22 | Bank | 2 | 210 | Formerly Room 208 | Ceiling Access Manhole Cover | Fibre Cement Sheeting | Removed: Positive | - | - | - | Item Removed: No removal/clearance documentation was provided. | Yes |
KENC | Kensington Campus | F22 | Bank | 2 | 210 | Formerly Room 208, 208A & 208B | Floor Covering (suspected vinyl tiles beneath new sheet vinyl) | Vinyl Tiles (brown colour) | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | F22 | Bank | 2 | 211 | Formerly Room 210 & 211 | Floor Covering (suspected under new floor covering) | Vinyl Tiles (brown colour) | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | F20 | Goodsell | B | - | North Side, Service Duct | Conduit | Moulded Fibre Cement Pipes | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | F13 | Science Theatre | G | G18 | Mid-South | Wall | Fibre Cement Sheeting | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | F13 | Science Theatre | 1 | 106 | Area Above Room 106, North and South | Wall Lining | Fibre Cement Sheeting | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | F13 | Science Theatre | 1 | 104 | Area Above Room 104 | Wall Lining | Fibre Cement Sheeting | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | E4 | Squarehouse | 03 | 3Q4 | South Electrical Cupboard (Sub-Board) | Wall Lining | Fibre Cement Sheeting | Removed: Positive | - | - | - | Item Removed. No removal or clearance documentation available. | Yes |
KENC | Kensington Campus | E4 | Squarehouse | 02 | East | Exterior Veranda | Window Frames (between frame and pane) | Mastic Sealant | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | E4 | Squarehouse | 03 | 3Q7 | West Entry | Fire Door (no tag) | Core Insulation | Positive (chrysotile) | Friable | Low | P2 | Remove fire door by a Class A Contractor within a planned control program. Note: Localised delamination of timber skin at base of door | No |
Kenc | Kensington Campus | D9 | IO Myers Studio | G | G08A | East and North | Walls | Fibre Cement Sheeting | Positive | Non-friable | Low | P4 | Maintain in good condition. Removed under controlled conditions by a Class A/B contractor prior to demolition or refurbishment works. | Yes |
Kenc | Kensington Campus | D9 | IO Myers Studio | G | G05 | Toilets, Central | Partition Wall | Compressed Fibre Cement Sheeting | Positive | Non-friable | Low | P4 | Maintain in good condition. Removed under controlled conditions by a Class A/B contractor prior to demolition or refurbishment works. | Yes |
Kenc | Kensington Campus | D9 | IO Myers Studio | G | G05 | North, East and South | Walls | Fibre Cement Sheeting | Positive | Non-friable | Low | P4 | Maintain in good condition. Removed under controlled conditions by a Class A/B contractor prior to demolition or refurbishment works. | Yes |
CCS | Cliffbrook Campus | CC2 | Building CC2 | G | - | Exterior, surrounding | Eaves | Fibre Cement Sheeting | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | C22 | Chancellery | LG | LG20 | Serive Tunnel off LG20 | Ductwork Flange Joins (old ductwork only) | Sealant Mastic | Assumed Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | C22 | Chancellery | LG | LG35 | - | Ductwork Flange Joins (old ductwork only) | Sealant Mastic | Assumed Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | C22 | Chancellery | G | G25 | Ceiling Space | Ductwork Flange Joins | Sealant Mastic | Assumed Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | C22 | Chancellery | G | G25 | Plumbling Duct off Toilets | Ductwork Flange Joins | Sealant Mastic | Assumed Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | C20 | Morven Brown | LG | LGQ3A | Wall Void | Conduits | Moulded Fibre Cement | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | C20 | Morven Brown | LG | LGQ11 | Electrical Cupboard | Within Electrical Cabinet | Electrical Backing Board | Positive | Non-friable | Low | P4 | Not sighted during RT2018 inspection. Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | C20 | Morven Brown | LG | LG56 | Exterior | Window Sill Expansion Joint | Mastic Sealant | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | C20 | Morven Brown | G | GQ10 | Electrical Cupboard | Within Electrical Cabinet | Electrical Backing Board | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | C20 | Morven Brown | G | GQ7 | Throughout | Wall Expansion Joint | Mastic Sealant | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | C20 | Morven Brown | 1 | 1Q4 | Electrical Cupboard | Within Electrical Cabinet | Electrical Backing Board | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | C20 | Morven Brown | 1 | 1Q10 | Electrical Cupboard | Within Electrical Cabinet | Electrical Backing Board | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | C20 | Morven Brown | 1 | 1Q7 | Exterior | Window Beading (between frame and pane) | Mastic Sealant | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | C20 | Morven Brown | 1 | 1Q7 | Throughout | Wall Expansion Joint | Mastic Sealant | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | C20 | Morven Brown | 2 | 2Q11 | Stairwell | Fire Door (No Door Tag) | Core Insulation | Positive | Friable | Low | P3 | Remedial works should be undertaken by a Class A Contractor within a planned control program. | No |
KENC | Kensington Campus | C20 | Morven Brown | 2 | 2Q10 | Electrical Cupboard | Within Electrical Cabinet | Electrical Backing Board | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | C20 | Morven Brown | 2 | 2Q7 | Throughout | Wall Expansion Joint | Mastic Sealant | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | C20 | Morven Brown | 3 | 3Q7 | Throughout | Wall Expansion Joint | Mastic Sealant | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | C20 | Morven Brown | 2 | 2Q7 | Throughout | Window Beading (between frame and pane) | Mastic Sealant | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | C20 | Morven Brown | 2 | 2Q7 | Throughout | Window Beading (between frame and pane) | Mastic Sealant | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | C20 | Morven Brown | 3 | 3Q7 | Throughout | Window Beading (between frame and pane) | Mastic Sealant | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | C20 | Morven Brown | 3 | 338 | South | Window Beading (between frame and pane) | Mastic Sealant | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | C22 | Chancellery | G | G26 | Ceiling Space | Ductwork Flange Joins | Sealant Mastic | Assumed Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | C22 | Chancellery | G | G26 | Plumbling Duct off Toilets | Ductwork Flange Joins | Sealant Mastic | Assumed Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | B5 | Fitness and Aquatic Centre | LG | LGQ01 | Pool (B4), Perimeter Throughout | Pipework Sleeves | Moulded Fibre Cement | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | B5 | Fitness and Aquatic Centre | LG | LGQ01 | Pool (B4), Perimeter Throughout | Pipework | Moulded Fibre Cement | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
Kenc | Kensington Campus | B21 | Repository | G | G01 | Perimeter & Throughout | Floor Expansion Joints | Mastic Sealant | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENE | Kensington Environs | AS14 | 14 Arthur Street | G | - | Exterior, South and East | Wall Cladding | Fibre Cement Sheeting | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment works. | No |
KENE | Kensington Environs | AS12 | 12 Arthur Street | G | - | Exterior, South and West | Wall | Fibre Cement Sheeting | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment works. | No |
KENE | Kensington Environs | AS10 | 10 Arthur Street | G | - | Exterior, Eastern Side, Surrounding Door | Infill Panels | Fibre Cement Sheeting | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment works. | No |
KENE | Kensington Environs | AS10 | 10 Arthur Street | G | G08 | - | Ceiling | Fibre Cement Sheeting | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment works. | No |
KENE | Kensington Environs | AS10 | 10 Arthur Street | G | G07 | West | Wall | Fibre Cement Sheeting | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment works. | No |
KENE | Kensington Environs | AS8 | 8 Arthur Street | G | - | Exterior, Garage, Surrounding | Eaves | Fibre Cement Sheeting | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment works. | No |
KENE | Kensington Environs | AS8 | 8 Arthur Street | G | - | Ceiling Space | Upper Ceiling | Fibre Cement Sheeting | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment works. | No |
KENE | Kensington Environs | AS8 | 8 Arthur Street | G | - | Corridor | Ceiling Access Panel | Fibre Cement Sheeting | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment works. | No |
KENE | Kensington Environs | A27 | Golf House | G | - | Exterior, North, South and East | Eaves | Fibre Cement Sheeting | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment works. | No |
KENC | Kensington Campus | C22 | Chancellery | G | G26A | Ceiling Space | Ductwork Flange Joins | Sealant Mastic | Assumed Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | C22 | Chancellery | 01 | 146 | Ceiling Space | Ductwork Flange Joins | Sealant Mastic | Assumed Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | C22 | Chancellery | 01 | 147 | Ceiling Space | Ductwork Flange Joins | Sealant Mastic | Assumed Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | C22 | Chancellery | 01 | 147A | Ceiling Space | Ductwork Flange Joins | Sealant Mastic | Assumed Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | C22 | Chancellery | 02 | 2Q14 | Ceiling Space | Ductwork Flange Joins | Sealant Mastic | Assumed Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | C22 | Chancellery | 02 | 2Q15 | Ceiling Space | Ductwork Flange Joins | Sealant Mastic | Assumed Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | C22 | Chancellery | 02 | 2Q16 | Ceiling Space | Ductwork Flange Joins | Sealant Mastic | Assumed Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | C22 | Chancellery | G | GQ5 | - | Fire Doors (tagged 'Wormald, 198-') | Core Insulation | Assumed Positive | Friable | Low | P3 | Undertake sampling of fire doors under controlled conditions. If positive, remedial works should be undertaken by a Class A Contractor within a planned control program. | No |
KENC | Kensington Campus | C22 | Chancellery | G | GQ8 | - | Fire Doors (tagged 'Wormald, 198-') | Core Insulation | Assumed Positive | Friable | Low | P3 | Undertake sampling of fire doors under controlled conditions. If positive, remedial works should be undertaken by a Class A Contractor within a planned control program. | No |
KENC | Kensington Campus | C22 | Chancellery | G | GQ9 | - | Fire Doors (tagged 'Wormald, 198-') | Core Insulation | Assumed Positive | Friable | Low | P3 | Undertake sampling of fire doors under controlled conditions. If positive, remedial works should be undertaken by a Class A Contractor within a planned control program. | No |
KENC | Kensington Campus | C22 | Chancellery | 01 | 135 | - | Fire Doors (tagged 'Wormald, 198-') | Core Insulation | Assumed Positive | Friable | Low | P3 | Undertake sampling of fire doors under controlled conditions. If positive, remedial works should be undertaken by a Class A Contractor within a planned control program. | No |
KENC | Kensington Campus | C22 | Chancellery | 01 | 136 | - | Fire Doors (tagged 'Wormald, 198-') | Core Insulation | Assumed Positive | Friable | Low | P3 | Undertake sampling of fire doors under controlled conditions. If positive, remedial works should be undertaken by a Class A Contractor within a planned control program. | No |
RANC | Randwick Campus | R1 | Randwick R1 | G | G28/ G29 | Canteen | Window Frames | Mastic Sealant | Positive | Non-Friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | F23 | Mathews Building | 1 | 1Q13 | Storage Cupboards (Ducts) | Ceiling | Fibre Cement Sheeting | Positive | Non-friable | Low | P3 | Remedial works should be undertaken by a Class A Contractor within a planned control program. | No |
KENC | Kensington Campus | F23 | Mathews Building | 2 | 209A | - | On Top of Blockwork Walls | Sealant Mastic | Removed -Positive | - | - | - | Item Removed: No removal / clearance documentation provided. | No |
KENC | Kensington Campus | F23 | Mathews Building | 2 | 210 | Throughout | Window Beading | Sealant Mastic | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | F23 | Mathews Building | 3 | 304 | Duct off Room 304 | Packing Material | Fibre Cement Sheeting | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | F23 | Mathews Building | 4 | 4Q8 | - | On Top of Blockwork Walls & Vertical Expansion Wall Joints | Sealant Mastic | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | F23 | Mathews Building | 6 | 604 | - | Window Beading | Sealant Mastic | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | F23 | Mathews Building | 6 | 6Q3 | North & East | On Top of Blockwork Walls & Vertical Expansion Wall Joints | Sealant Mastic | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | F23 | Mathews Building | 5 | 5Q6 | North & East | On Top of Blockwork Walls & Vertical Expansion Wall Joints | Sealant Mastic | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | F23 | Mathews Building | 5 | 5Q1 | - | Window Beading | Sealant Mastic | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | F23 | Mathews Building | 7 | 701 | - | Window Beading | Sealant Mastic | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | F23 | Mathews Building | 7 | 7Q3 | North & East | On Top of Blockwork Walls & Vertical Expansion Wall Joints | Sealant Mastic | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | F23 | Mathews Building | 10 | 1024 | - | Window Beading | Sealant Mastic | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | F23 | Mathews Building | 10 | 10Q3 | North & East | On Top of Blockwork Walls & Vertical Expansion Wall Joints | Sealant Mastic | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | F23 | Mathews Building | 8 | 812A | - | Window Beading | Sealant Mastic | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | F23 | Mathews Building | 8 | 8Q1 | North & East | On Top of Blockwork Walls & Vertical Expansion Wall Joints | Sealant Mastic | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | F23 | Mathews Building | 9 | 901 | - | Window Beading | Sealant Mastic | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | F23 | Mathews Building | 11 | 11Q2 | South & West | On Top of Blockwork Walls & Vertical Expansion Wall Joints | Sealant Mastic | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | F23 | Mathews Building | 12 | 12Q2 | South & West | On Top of Blockwork Walls & Vertical Expansion Wall Joints | Sealant Mastic | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | F23 | Mathews Building | 13 | 13Q2 | West & South | On Top of Blockwork Walls & Vertical Expansion Wall Joints | Sealant Mastic | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | F23 | Mathews Building | 13 | 1301 | - | Window Beading | Sealant Mastic | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | F23 | Mathews Building | 14 | 14Q2 | West & South | On Top of Blockwork Walls & Vertical Expansion Wall Joints | Sealant Mastic | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | F23 | Mathews Building | 15 | 1517A | - | Window Beading | Sealant Mastic | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | C22 | Chancellery | 01 | 137 | - | Fire Doors (tagged 'Wormald, 198-') | Core Insulation | Assumed Positive | Friable | Low | P3 | Undertake sampling of fire doors under controlled conditions. If positive, remedial works should be undertaken by a Class A Contractor within a planned control program. | No |
KENC | Kensington Campus | C22 | Chancellery | 01 | 1Q5 | - | Fire Doors (tagged 'Wormald, 198-') | Core Insulation | Assumed Positive | Friable | Low | P3 | Undertake sampling of fire doors under controlled conditions. If positive, remedial works should be undertaken by a Class A Contractor within a planned control program. | No |
KENC | Kensington Campus | C22 | Chancellery | 02 | 2Q7 | - | Fire Doors (tagged 'Wormald, 198-') | Core Insulation | Removed | - | - | - | Item removed. Refer Risktech clearance cert dated 18th Sept 2023 | Yes |
KENC | Kensington Campus | C22 | Chancellery | 02 | 2Q9 | - | Fire Doors (tagged 'Wormald, 198-') | Core Insulation | Assumed Positive | Friable | Low | P3 | Undertake sampling of fire doors under controlled conditions. If positive, remedial works should be undertaken by a Class A Contractor within a planned control program. | No |
KENC | Kensington Campus | C22 | Chancellery | 03 | 310A | Service Cupboard, Roof Space | Ceiling (Eaves) | Fibre Cement Sheeting | Assumed Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | C22 | Chancellery | - | - | Exterior Throughout | Eaves | Fibre Cement Sheeting | Assumed Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | C22 | Chancellery | 01 | M1Q03 | Plumbling Duct off Room 146 Toilets | Ductwork Flange Joins | Sealant Mastic | Assumed Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | C22 | Chancellery | 01 | M1Q04 | Plumbling Duct off Room 147 Toilets | Ductwork Flange Joins | Sealant Mastic | Assumed Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | C22 | Chancellery | 02 | 2Q14 | Plumbling Duct off Toilets | Ductwork Flange Joins | Sealant Mastic | Assumed Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | C22 | Chancellery | 02 | 2Q15 | Plumbling Duct off Toilets | Ductwork Flange Joins | Sealant Mastic | Assumed Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | K17 | Building K17 | 3 | 303 | Under Carpet | Floor Covering | Vinyl Tiles | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | F10 | Chemical Sciences | 10 | 10Q2A | Gas Storage Cupboard | Floor Covering | Adhesive (attached to vinyl tile) | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | F10 | Chemical Sciences | 10 | 10Q2A | Gas Storage Cupboard | Floor Covering | Vinyl Tiles (olive green) | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | F10 | Chemical Sciences | LR | R1 | Western End, Plant Room | Hot Water Pipework (steam header) | Gasket | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | G6 | Blockhouse | 2 | 204 | North, Behind New Window Panelling | Window Beading | Sealant Mastic | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | J12 | Newton | G | G14 | Room WG8, North, East & South | Wall Lining | Fibre Cement Sheeting | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
MANV | Manly Vale | MV4 | Workshop | G | G03 | - | Ceiling | Fibre Cement Sheeting | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | J12 | Newton | 1 | 102 | South Wall | Wall Lining | Fibre Cement Sheeting | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | J12 | Newton | G | G14 | Room WG8A, Internal & External | Wall Lining | Fibre Cement Sheeting | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | J12 | Newton | G | G14 | Mezzanine Area (Room GM8), North & East | Wall Lining | Fibre Cement Sheeting | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | F23 | Mathews Building | 7 | 723 | - | Window Frames | Sealant Mastic | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | F21 | Library | LG | LGQ08 | Redundant Chiller Plant Room | Chiller Units, Pipework Flange Joints | Gaskets | Removed -Positive | - | - | - | Item Removed: Refer to RiskTech Clearance Certificate dated 23 December 2000. | Yes |
KENC | Kensington Campus | E4 | Squarehouse | 01 | - | Exterior | Window Frames (between frame & pane) | Mastic Sealant (grey colour) | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
COFA | Paddington Campus | CFAE | Block E | G | - | Exterior, North and South Elevations | Pebble Stone Horizontal Wall Joints (between concrete columns & wall panel sections) | Pointing | Positive | Non-friable | Low | P4 | Maintain in current condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
CCS | Cliffbrook Campus | CC4 | Building CC4 | 02 | - | Exterior, East, Outside Room 210-219A | Balcony Floor Covering | Bituminous Membrane | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | F21 | Library | 15 | - | Exterior, Perimeter (access via door in NE Fire Stairs (15Q1) | Roof Covering (assumed beneath new membrane) | Bituminous Membrane | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | C22 | Chancellery | 03 | 310B | Plant Room Entrance | Fire Door (no tag) | Core Insulation | Assumed Positive | Friable | Low | P3 | Undertake sampling of fire doors under controlled conditions. If positive, remedial works should be undertaken by a Class A Contractor within a planned control program. | No |
KENC | Kensington Campus | C22 | Chancellery | LG | LG35 | West Side | Wall | Bituminous Membrane | Negative | - | - | - | - | N/A |
KENC | Kensington Campus | K15 | Old Main | LG | LG45 | - | Air Conditioning Ductwork Heater Bank | Insulation Board | Positive (Removed) | - | - | - | Item Removed. No removal/clearance documentation was provided. | Yes |
KENC | Kensington Campus | K15 | Old Main | LG | LG55 | Duct Riser | Bituminous Flue (redundant material) | Moulded Fibre Cement | Positive (Removed) | - | - | - | Item Removed. No removal/clearance documentation was provided. | Yes |
KENC | Kensington Campus | K15 | Old Main | LG | LG55 | Duct Riser | Bituminous Flue | Moulded Fibre Cement | Positive (Removed) | - | - | - | Item removed. No removal/clearance documentation was provided. | Yes |
KENC | Kensington Campus | K14 | Physics Theatre | LG | LG12 | - | Flue | Moulded Fibre Cement | Removed - Positive | - | - | - | Item removed. No removal/clearance documentation was provided. | Yes |
KENC | Kensington Campus | K15 | Old Main | G | G34 | - | Floor Covering | Vinyl Tiles (green colour) | Positive (Removed) | - | - | - | Item Removed 10/2/2018. Refer to RiskTech Clearance Certificate dated 10/2/2018. | Yes |
KENC | Kensington Campus | K15 | Old Main | G | G57 | - | Floor Covering | Vinyl Tiles (green colour) | Positive (Removed) | - | - | - | Item Removed. No removal/clearance documentation was provided. | Yes |
KENC | Kensington Campus | K15 | Old Main | G | G58 | - | Floor Covering | Vinyl Tiles (green colour) | Positive (Removed) | - | - | - | Item Removed. No removal/clearance documentation was provided. | Yes |
KENC | Kensington Campus | K15 | Old Main | G | G59 | - | Floor Covering | Vinyl Tiles (green colour) | Positive (Removed) | - | - | - | Item Removed. No removal/clearance documentation was provided. | Yes |
KENC | Kensington Campus | K15 | Old Main | G | G59A | - | Floor Covering | Vinyl Tiles (green colour) | Positive (Removed) | - | - | - | Item Removed. No removal/clearance documentation was provided. | Yes |
KENC | Kensington Campus | K15 | Old Main | G | G59C | - | Floor Covering | Vinyl Tiles (green colour) | Positive (Removed) | - | - | - | Item Removed. No removal/clearance documentation was provided. | Yes |
KENC | Kensington Campus | K15 | Old Main | G | G59D | - | Floor Covering | Vinyl Tiles (green colour) | Positive (Removed) | - | - | - | Item Removed. No removal/clearance documentation was provided. | Yes |
KENC | Kensington Campus | K15 | Old Main | G | G59E | - | Floor Covering | Vinyl Tiles (green colour) | Positive (Removed) | - | - | - | Item Removed. No removal/clearance documentation was provided. | Yes |
KENC | Kensington Campus | K15 | Old Main | G | G59F | - | Floor Covering | Vinyl Tiles (green colour) | Positive (Removed) | - | - | - | Item Removed. No removal/clearance documentation was provided. | Yes |
KENC | Kensington Campus | K15 | Old Main | G | G59G | - | Floor Covering | Vinyl Tiles (green colour) | Positive (Removed) | - | - | - | Item Removed. No removal/clearance documentation was provided. | Yes |
KENC | Kensington Campus | K15 | Old Main | G | G59H | - | Floor Covering | Vinyl Tiles (green colour) | Positive (Removed) | - | - | - | Item Removed. No removal/clearance documentation was provided. | Yes |
KENC | Kensington Campus | K15 | Old Main | 02 | 236A | Ceiling Space, on Top of Ceiling | Bitumen Pipe Collar | Moulded Fibre Cement | Positive (Removed) | - | - | - | Item Removed. No removal/clearance documentation was provided. | Yes |
KENC | Kensington Campus | E6 | Roundhouse | 01 | Former Room 103 | Throughout | Flue | Moulded Fibre Cement | Positive - Removed | - | - | - | Item removed 22/03/2014. Refer to NAA Clearance Certificate C107946:J125290. | Yes |
KENC | Kensington Campus | E6 | Roundhouse | 01 | Former Room 114A | Throughout | Flue | Moulded Fibre Cement | Positive - Removed | - | - | - | Item removed 22/03/2014. Refer to NAA Clearance Certificate C107946:J125290. | Yes |
Kenc | Kensington Campus | C24 | Clancy Auditorium | R | - | South-East Corner | Flue | Moulded Fibre Cement | Positive (Removed) | - | - | - | Item Removed 4/3/2009. Refer to NAA Clearance Certificate SS0263:72214 and Air Monitoring Report 71828.001-003. | Yes |
Kenc | Kensington Campus | C24 | Clancy Auditorium | R | - | - | Wall Cladding Joints | Fibre Cement Sheeting | Positive (Removed) | - | - | - | Item Removed 13/07/2013. Refer to Safe Work & Environments Clearance Report dated 15/07/2013 | Yes |
Kenc | Kensington Campus | C24 | Clancy Auditorium | R | - | - | Wall Cladding | Fibre Cement Sheeting | Positive (Removed) | - | - | - | Item Removed 13/07/2013. Refer to Safe Work & Environments Clearance Report dated 15/07/2013 | Yes |
KENC | Kensington Campus | C22 | Chancellery | LG | LG12 | Entrance | Fire Door (tagged ' Fire Research - Installed 198-') | Core Insulation | Negative | - | - | - | - | N/A |
KENC | Kensington Campus | C22 | Chancellery | 01 | 1Q1 | Stairwell | Fire Door | Core Insulation | Negative | - | - | - | - | N/A |
KENC | Kensington Campus | C20 | Morven Brown | LG | LG69-71, LG57A & LG58 | Above Ceiling Tiles | Ceiling | Vermiculite | Positive - Removed | - | - | - | Item not sighted during 2014 or 2018 inspection. Further investigation may be required prior to refurbishment works in this area. | Yes |
KENC | Kensington Campus | E6 | Roundhouse | G | Former Rooms G05, G05B, G06B, G06D, G06H, G07, G09, G10, G19, G19B, GQ06, GQ13 | Throughout | Ceilings | Fibre Cement Sheeting | Positive - Removed | - | - | - | Item removed. No removal/clearance documentation was provided. | Yes |
KENC | Kensington Campus | K17 | Building K17 | 6 | 622 | Under Carpet | Floor Covering | Vinyl Tiles | Positive - Removed | - | - | - | Item removed by Pure Contracting on 23/7/2016 - Naa Clearance Certifcate (Ref: C107859:J145884) | Yes |
KENC | Kensington Campus | K17 | Building K17 | 6 | 623 | Under Carpet | Floor Covering | Vinyl Tiles | Positive - Removed | - | - | - | Item removed by Pure Contracting on 23/7/2016 - Naa Clearance Certifcate (Ref: C107859:J145884) | Yes |
KENC | Kensington Campus | K17 | Building K17 | 6 | 624 | Under Carpet | Floor Covering | Vinyl Tiles | Positive - Removed | - | - | - | Item removed by Pure Contracting on 23/7/2016 - Naa Clearance Certifcate (Ref: C107859:J145884) | Yes |
KENC | Kensington Campus | K17 | Building K17 | 6 | 625 | Under Carpet | Floor Covering | Vinyl Tiles | Positive - Removed | - | - | - | Item removed by Pure Contracting on 23/7/2016 - Naa Clearance Certifcate (Ref: C107859:J145884) | Yes |
RANC | Randwick Campus | R1 | Randwick R1 | G | G30 | Store Room, Entry | Fire Door | Core Insulation | Removed - Positive | - | - | - | Item Removed: Refer to RiskTech Clearance Certificate dated 24 April 2019. | Yes |
KENC | Kensington Campus | F23 | Mathews Building | 18 | - | Roof Above Level 18 | Roof | Bituminous Membrane | Removed -Positive | - | - | - | Item Removed: Refer to RiskTech Clearance Certificate dated 21 February 2019 | Yes |
KENC | Kensington Campus | C22 | Chancellery | G | UGQ1 | Exterior, East Side, Main Entrance | Soffit | Decorative Coating (vermiculite) | Negative | - | - | - | - | N/A |
KENC | Kensington Campus | E4 | Squarehouse | R | RQ1 | West | Fire Door (no tag) | Core Insulation | Positive (Removed) | - | - | - | Item Removed by Pure Contracting on 23/01/2019. Refer to RiskTech Clearance and Air Monitoring Reports dated 23/01/2019. | Yes |
KENC | Kensington Campus | K14 | Physics Theatre | G | G29 | - | Bench Top | Compressed Fibre Cement Sheeting | Removed -Positive (chrysotile) | - | - | - | Item Removed 18/3/2017. Refer to RiskTech Clearance Certificate dated 18/3/2017. | Yes |
KENC | Kensington Campus | K15 | Old Main | 02 | 2Q8 | Fire Hydrant Cupboard | Floor Covering | Vinyl Tiles (brittle blue colour) | Positive (Removed) | - | - | - | Item Removed 29/4/2019 by Pure Contracting. Refer to RiskTech Clearance Certificate dated 29/4/2019. | Yes |
KENC | Kensington Campus | K15 | Old Main | 02 | 2Q7 | Electrical Cupboard | Floor Covering | Viny Tiles (green colour) | Positive (Removed) | - | - | - | Item Removed 29/4/2019 by Pure Contracting. Refer to RiskTech Clearance Certificate dated 29/4/2019. | Yes |
MANV | Manly Vale | MV3 | Laboratory 2 | B | - | Sub-Floor Space, Beneath Eastern Office/Amenities | Ground Surface, Debris | Fibre Cement Sheeting | Positive (Removed) | - | - | - | Item removed as part of the sampling process by RiskTech in July 2018. | Yes |
KENC | Kensington Campus | G27 | AGSM | 3 | 3Q3 | Fire Stairwell | Fire Door (tagged 'Masterbilt') | Core Insulation | Positive - Removed | - | - | - | Item Removed 2/6/2017 by ATS. Refer to RiskTech Clearance Certificate | Yes |
KENC | Kensington Campus | G27 | AGSM | 1 | 1Q3 | Fire Stairwell | Fire Door (tagged 'Masterbilt') | Core Insulation | Positive - Removed | - | - | - | Item Removed 2/6/2017 by ATS. Refer to RiskTech Clearance Certificate | Yes |
KENC | Kensington Campus | G27 | AGSM | 1 | 1Q2 | Fire Stairwell | Fire Door (tagged 'Masterbilt') | Core Insulation | Positive - Removed | - | - | - | Item Removed 2/6/2017 by ATS. Refer to RiskTech Clearance Certificate | Yes |
KENC | Kensington Campus | G27 | AGSM | G | GQ4 | Fire Stairwell | Fire Door (tagged 'Masterbilt') | Core Insulation | Positive - Removed | - | - | - | Item Removed 2/6/2017 by ATS. Refer to RiskTech Clearance Certificate | Yes |
KENC | Kensington Campus | G27 | AGSM | LG | LGQ3 | Fire Stairwell | Fire Door (no tag) | Core Insulation | Positive - Removed | - | - | - | Item Removed 2/6/2017 by ATS. Refer to RiskTech Clearance Certificate | Yes |
KENC | Kensington Campus | C22 | Chancellery | 01 | 132 | Under Carpet | Floor Covering | Vinyl Tiles | Negative | - | - | - | - | N/A |
KENC | Kensington Campus | K17 | Building K17 | G | - | Exterior, Façade | Façade Panel Expansion Joints | Mastic Sealant | Positive - Removed | - | - | - | Item removed by Pure Contracting Between November 2017 & March 2018 - Refer to RiskTech Clearance Certifcates | Yes |
KENC | Kensington Campus | K17 | Building K17 | 1 | - | Exterior, Façade | Façade Panel Expansion Joints | Mastic Sealant | Positive - Removed | - | - | - | Item removed by Pure Contracting Between November 2017 & March 2018 - Refer to RiskTech Clearance Certifcates | Yes |
KENC | Kensington Campus | K17 | Building K17 | 2 | - | Exterior, Façade | Façade Panel Expansion Joints | Mastic Sealant | Positive - Removed | - | - | - | Item removed by Pure Contracting Between November 2017 & March 2018 - Refer to RiskTech Clearance Certifcates | Yes |
KENC | Kensington Campus | K17 | Building K17 | 4 | - | Exterior, Façade | Façade Panel Expansion Joints | Mastic Sealant | Positive - Removed | - | - | - | Item removed by Pure Contracting Between November 2017 & March 2018 - Refer to RiskTech Clearance Certifcates | Yes |
KENC | Kensington Campus | K17 | Building K17 | 5 | - | Exterior, Façade | Façade Panel Expansion Joints | Mastic Sealant | Positive - Removed | - | - | - | Item removed by Pure Contracting Between November 2017 & March 2018 - Refer to RiskTech Clearance Certifcates | Yes |
KENC | Kensington Campus | K17 | Building K17 | 6 | - | Exterior, Façade | Façade Panel Expansion Joints | Mastic Sealant | Positive - Removed | - | - | - | Item removed by Pure Contracting Between November 2017 & March 2018 - Refer to RiskTech Clearance Certifcates | Yes |
KENC | Kensington Campus | K17 | Building K17 | 3 | - | Exterior, Façade | Façade Panel Expansion Joints | Mastic Sealant | Positive - Removed | - | - | - | Item removed by Pure Contracting Between November 2017 & March 2018 - Refer to RiskTech Clearance Certifcates | Yes |
KENC | Kensington Campus | B5 | Fitness and Aquatic Centre | G | P09 | Pool (B4), Throughout | Air Conditioning Ductwork | Moulded Fibre Cement | Positive - Removed | - | - | - | Item removed 8/5/2014. Refer to Airsafe Clearance Certificate (Job No. 23011). | Yes |
KENC | Kensington Campus | C22 | Chancellery | 01 | 1Q5 | Under Carpet | Floor Covering | Vinyl Tiles (light brown colour) | Negative | - | - | - | - | N/A |
KENC | Kensington Campus | C22 | Chancellery | B | B10 | - | Wall | Fibre Cement Sheeting | Negative | - | - | - | - | N/A |
KENC | Kensington Campus | F23 | Mathews Building | 18 | 1801 | North & East | Inside Electrical Cabinet (Note: new appearance cabinet) | Electrical Backing Board | Removed -Positive | - | - | - | Item Removed: No removal / clearance documentation provided. | Yes |
KENC | Kensington Campus | G6 | Blockhouse | G | G8C | - | Inside Electrical Cabinet | Electrical Backing Boards | Removed -Positive | - | - | - | Item Removed: 05-02-2014. No removal/clearance documentation was provided. New electrical cabinet present. | Yes |
KENC | Kensington Campus | G6 | Blockhouse | G | G10E | Electrical Room | Inside Electrical Cabinet | Electrical Backing Boards | Removed -Positive | - | - | - | Item Removed: 05-02-2014. No removal/clearance documentation was provided. New electrical cabinet present. | Yes |
Kenc | Kensington Campus | G15 | Robert Webster Theatres | 01 | 191B | South, Electrical Cupboard | Inside Electrical Cabinet | Electrical Backing Board | Positive (Removed) | - | - | - | Item Removed: No removal/clearance documentation was provided. | Yes |
KENC | Kensington Campus | C20 | Morven Brown | G | GQ4 | Electrical Cupboard | Within Electrical Cabinet | Electrical Backing Board | Positive - Removed | - | - | - | Item removed. No removal/clearance documentation was provided. | Yes |
KENC | Kensington Campus | C22 | Chancellery | B | BQ1 | - | Fire Door (tagged 'Cecon, 199_') | Core Insulation | Negative | - | - | - | - | N/A |
KENC | Kensington Campus | C20 | Morven Brown | LG | LG47 | Throughout | Floor Covering | Vinyl Floor Tiles (grey colour) | Positive - Removed | - | - | - | Removed 10-03-2014. Refer to NAA Clearance Certificate SS0263:77747 and Air Monitoring Report SS0263:77747.022. | Yes |
KENC | Kensington Campus | C20 | Morven Brown | LG | LGQ8 | Stairwell | Fire Door | Core Insulation | Positive - Removed | - | - | - | Removed 22-08-2018 by Pure Contracting. Refer to RiskTech Clearance and Air Monitoirng Report dated 22-08-2018. | Yes |
KENC | Kensington Campus | F20 | Goodsell | LG | LGQ6 | - | Floor Covering | Vinyl Floor Tiles (beige colour) | Positive - Removed | - | - | - | Item Removed: Refer to NAA Clearance Certificate dated 4 September 2008 (Ref: 68276). | Yes |
KENC | Kensington Campus | N8 | House at Pooh Corner | G | G1 | Northern Section Only | Floor Covering | Vinyl Floor Tiles (beneath vinyl sheeting) | Positive - Removed | - | - | - | Item Removed: Refer to RiskTech Clearance Report dated 23 December 2017. | Yes |
KENC | Kensington Campus | N8 | House at Pooh Corner | G | G13 | Northern Section Only | Floor Covering | Vinyl Floor Tiles (beneath vinyl sheeting) | Positive - Removed | - | - | - | Item Removed: Refer to RiskTech Clearance Report dated 23 December 2017. | Yes |
KENC | Kensington Campus | N8 | House at Pooh Corner | G | G14 | Southern Section | Floor Covering | Vinyl Floor Tiles (beneath vinyl sheeting) | Positive - Removed | - | - | - | Item Removed: Refer to RiskTech Clearance Report dated 23 December 2017. | Yes |
KENC | Kensington Campus | N8 | House at Pooh Corner | G | G23 | Northern Section Only | Floor Covering | Vinyl Floor Tiles (beneath vinyl sheeting) | Positive - Removed | - | - | - | Item Removed: Refer to RiskTech Clearance Report dated 23 December 2017. | Yes |
KENC | Kensington Campus | F21 | Library | 4 | 499A | Toilet | Ceiling | Fibre Cement Sheeting | Removed - Positive | - | - | - | Item Removed: No removal / clearance documentation provided. | Yes |
KENC | Kensington Campus | F21 | Library | 11 | 1199A | Toilet | Ceiling | Fibre Cement Sheeting | Removed - Positive | - | - | - | Item Removed: No removal / clearance documentation provided. | Yes |
KENC | Kensington Campus | F21 | Library | 9 | 999A | Toilet | Ceiling | Fibre Cement Sheeting | Removed - Positive | - | - | - | Item Removed: No removal / clearance documentation provided. | Yes |
KENC | Kensington Campus | F21 | Library | 10 | 1099A | Toilet | Ceiling | Fibre Cement Sheeting | Removed - Positive | - | - | - | Item Removed: No removal / clearance documentation provided. | Yes |
KENC | Kensington Campus | F21 | Library | 13 | 1399A | Toilet | Ceiling | Fibre Cement Sheeting | Removed - Positive | - | - | - | Item Removed: No removal / clearance documentation provided. | Yes |
KENC | Kensington Campus | F21 | Library | 14 | 1499A | Toilet | Ceiling | Fibre Cement Sheeting | Removed -Assumed Positive | - | - | - | Item Removed: No removal / clearance documentation provided. | Yes |
KENC | Kensington Campus | F21 | Library | 16 | 1604 | Lift Motor Room | Fire Door | Core Insulation | Removed - Positive | - | - | - | Item Removed: No removal / clearance documentation provided. | Yes |
KENC | Kensington Campus | C22 | Chancellery | B | BQ2 | - | Ceiling | Decorative Coating (vermiculite) | Negative | - | - | - | - | N/A |
KENC | Kensington Campus | K17 | Building K17 | G | GQ06 | Cleaners Cupboard | Floor Covering | Vinyl Tiles (brown colour) | Positive - Removed | - | - | - | Item removed. No removal/clearance documention was provided. | Yes |
KENC | Kensington Campus | G27 | AGSM | LG | LG01 | Riser Cupboard | Electrical Penetration | Insulation Material | Positive - Removed | - | - | - | Item Removed 20/3/2009. Refer to NAA Clearance Certificate SS0263:72606 | Yes |
KENC | Kensington Campus | G27 | AGSM | G | G02 | Riser Cupboard | Electrical Penetration | Insulation Material | Positive - Removed | - | - | - | Item Removed 20/3/2009. Refer to NAA Clearance Certificate SS0263:72606 | Yes |
KENC | Kensington Campus | G27 | AGSM | 1 | 112 | Riser Cupboard | Electrical Penetration | Insulation Material | Positive - Removed | - | - | - | Item Removed 20/3/2009. Refer to NAA Clearance Certificate SS0263:72606 | Yes |
KENC | Kensington Campus | G27 | AGSM | 2 | 234 | Riser Cupboard | Electrical Penetration | Insulation Material | Positive - Removed | - | - | - | Item Removed 20/3/2009. Refer to NAA Clearance Certificate SS0263:72606 | Yes |
KENC | Kensington Campus | G27 | AGSM | 3 | 321 | Riser Cupboard | Electrical Penetration | Insulation Material | Positive - Removed | - | - | - | Item Removed 20/3/2009. Refer to NAA Clearance Certificate SS0263:72606 | Yes |
DPFS | David Phillips Field | DP4 | Grounds Depot | G | G02 | Shower | Ceiling | Fibre Cement Sheeting | Positive - Removed | - | - | - | - | Yes |
KENC | Kensington Campus | H20 | Civil Engineering | 3 | 315, 316 & 316B | Previously 310 & 310A, Room 310 | Fume Cupboard | Millboard Lining | Positive - Removed | - | - | - | Item removed - No removal documentation provided | Yes |
KENC | Kensington Campus | H20 | Civil Engineering | 8 | ROQ2 | Lift Motor Room | Lift Controller Cabinet | Electrical Backing Board | Positive - Removed | - | - | - | Item removed - No removal documentation provided | Yes |
KENC | Kensington Campus | H20 | Civil Engineering | 8 | ROQ2 | Lift Motor Room | Lift Motors | Brake Pads | Positive - Removed | - | - | - | Item removed - No removal documentation provided | Yes |
MANV | Manly Vale | MV5 | Toilet Block | G | G01 | - | Boiler Pipe | Rope Lagging | Positive (removed) | - | - | - | No removal/clearance documentation was provided. | Yes |
MANV | Manly Vale | MV3 | Laboratory 2 | G | GQ2 | - | Floor Covering | Vinyl Tiles (light green colour) | Positive (Removed) | - | - | - | Item removed. No removal/clearance documentation was provided. | Yes |
MANV | Manly Vale | MV3 | Laboratory 2 | B | Under G03-G09 | Sub-Floor Space | Ground Surface, Debris | Fibre Cement Sheeting | Positive (Removed) | - | - | - | Item removed 21/7/2012. Refer to NAA Clearance Certificate C107859:J111468 dated July 2012. | Yes |
KENC | Kensington Campus | C22 | Chancellery | B | BQ2 | Throughout | Floor Covering | Vinyl Tiles | Negative | - | - | - | - | N/A |
KENC | Kensington Campus | C22 | Chancellery | LG | LG18 | Entrance | Fire Door | Core Insulation | Negative | - | - | - | Item Removed: Prior to Greencap 2014 inspection. No removal documentation provided. | Yes |
MANV | Manly Vale | MV1 | Laboratory 1 | G | G01 | Water Research Service Pit | Pipes and Collars | Moulded Fibre Cement | Positive (Removed) | - | - | - | Item removed 21/09/2018 by Pure Contracting. Refer to RiskTech Clearance Certificate dated September 2018. | Yes |
MANV | Manly Vale | MV1 | Laboratory 1 | G | G03 | - | Floor Covering | Vinyl Tiles (grey colour) | Positive (Removed) | - | - | - | Item removed 21/08/2013 by Pure Contracting. Refer to NAA Clearance Certificate C107859:J121666-01. | Yes |
MANV | Manly Vale | MV1 | Laboratory 1 | G | G01 | South-West Wall | Within Electrical Cabinet | Electrical Backing Board | Positive (Removed) | - | - | - | Item removed. No removal documentation was provided. | Yes |
KENC | Kensington Campus | C22 | Chancellery | LG | LG17 | - | Ceiling | Decorative Coating (vermiculite) | Negative | - | - | - | - | N/A |
KENC | Kensington Campus | C22 | Chancellery | LG | LG18 | - | Floor Covering | Vinyl Tiles | Negative | - | - | - | - | N/A |
KENC | Kensington Campus | C22 | Chancellery | LG | LG17E | - | Floor Covering | Vinyl Tiles (black colour) | Negative | - | - | - | - | N/A |
KENC | Kensington Campus | C22 | Chancellery | LG | LG15 | Under Carpet | Floor Covering | Vinyl Tiles (brown colour) | Negative | - | - | - | - | N/A |
KENC | Kensington Campus | C22 | Chancellery | G | GQ8 | Under Carpet | Floor Covering | Vinyl Tiles | Negative | - | - | - | - | N/A |
KENC | Kensington Campus | C22 | Chancellery | G | G24 | Throughout | Floor Covering | Vinyl Tiles | Negative | - | - | - | N/A | |
KENC | Kensington Campus | C22 | Chancellery | 01 | 1Q5 | - | Ceiling | Decorative Coating (vermiculite) | Negative | - | - | - | - | N/A |
KENC | Kensington Campus | K17 | Building K17 | 7 | 701 | Throughout | Floor Covering | Vinyl Tiles (brown colour) | Positive - Removed | - | - | - | Item removed by Pure Contracting on 18/7/2015 - NAA Clearance Certifcate (Ref: C107859:J134209) | Yes |
KENC | Kensington Campus | K15 | Old Main | LG | - | Exterior, at LG12 | Flue | Moulded Fibre Cement | Positive (removed) | - | - | - | Item Removed. No removal/clearance documentation was provided. | Yes |
KENC | Kensington Campus | K15 | Old Main | LG | LG44 | - | Flue | Moulded Fibre Cement | Positive (Removed) | - | - | - | Item Removed. No removal/clearance documentation was provided. | Yes |
KENC | Kensington Campus | K15 | Old Main | G | G43 | Riser | Flue | Moulded Fibre Cement | Positive (Removed) | - | - | - | Item Removed. No removal/clearance documentation was provided. | Yes |
KENC | Kensington Campus | K15 | Old Main | G | G69A | Duct Riser | Flue | Moulded Fibre Cement | Positive (Removed) | - | - | - | Item Removed. No removal/clearance documentation was provided. | Yes |
KENC | Kensington Campus | K15 | Old Main | G | G69A | Duct Riser | Pipework Insulation | Lagging | Positive (Removed) | - | - | - | Item Removed. No removal/clearance documentation was provided. | Yes |
KENC | Kensington Campus | K15 | Old Main | 01 | 153 | Duct Riser | Flue | Moulded Fibre Cement | Positive (Removed) | - | - | - | Item Removed. No removal/clearance documentation was provided. | Yes |
KENC | Kensington Campus | K15 | Old Main | 01 | 142 | - | Floor Covering | Vinyl Tiles (blue colour) | Positive (Removed) | - | - | - | Item Removed 21/11/2015. Refer to Airsafe Asbestos Clearance Certificate dated 23/11/2015 (report reference: 29259). | Yes |
KENC | Kensington Campus | K15 | Old Main | 01 | 141A | Duct Riser | Flue | Moulded Fibre Cement | Positive (Removed) | - | - | - | Item Removed. No removal/clearance documentation was provided. | Yes |
KENC | Kensington Campus | K15 | Old Main | 02 | 210C | Duct Riser | Flue | Moulded Fibre Cement | Positive (Removed) | - | - | - | Item Removed. No removal/clearance documentation was provided. | Yes |
KENC | Kensington Campus | K15 | Old Main | 02 | 236A | Duct Riser | Flue | Moulded Fibre Cement | Positive (Removed) | - | - | - | Item Removed. No removal/clearance documentation was provided. | Yes |
KENC | Kensington Campus | K15 | Old Main | 02 | 236A | Duct Riser | Pipework Insulation | Lagging | Positive (Removed) | - | - | - | Item Removed. No removal/clearance documentation was provided. | Yes |
KENC | Kensington Campus | K15 | Old Main | 02 | 236A | Cleaner's Cupboard | Ceiling | Fibre Cement Sheeting | Positive (Removed) | - | - | - | Item Removed. No removal/clearance documentation was provided. | Yes |
KENC | Kensington Campus | K15 | Old Main | 01 | 141A | Duct Riser | Pipework Insulation | Lagging | Positive (Removed) | - | - | - | Item Removed. No removal/clearance documentation was provided. | Yes |
KENC | Kensington Campus | H20 | Civil Engineering | LG | LGQ2 | Central, Hallway | Oven Door Seal | Rope Insulation | Positive - Removed | - | - | - | Item removed - No removal documentation provided | Yes |
KENC | Kensington Campus | H20 | Civil Engineering | 3 | 315, 316 & 316B | Previously 310 & 310A, Throughout | Floor Covering | Vinyl Tiles (Blue, Grey & White Colour) | Positive - Removed | - | - | - | Item removed - No removal documentation provided | Yes |
KENC | Kensington Campus | H20 | Civil Engineering | LG | LG6 | Throughout | Floor Covering | Vinyl Tiles (Aqua Colour) | Positive - Removed | - | - | - | Item removed 14/7/2014 by Pure Contracting - Airsafe Asbestos Clearance Certificate (Ref: 23811) | Yes |
KENC | Kensington Campus | H20 | Civil Engineering | LG | LG6A | Throughout | Floor Covering | Vinyl Tiles (Aqua, Grey & White Colour) | Positive - Removed | - | - | - | Item removed 25/7/2010 by Cardinal Project Services - NAA Asbestos Clearance Certificate (Ref: SS0263:77747) | Yes |
KENC | Kensington Campus | H20 | Civil Engineering | G | G8 | Throughout | Floor Covering | Vinyl Tiles (Green Colour) | Positive - Removed | - | - | - | Item removed 8/11/2014 by Pure Contracting - Greencap-NAA Clearance Certificate (Ref: J107859:J130066) | Yes |
KENC | Kensington Campus | H20 | Civil Engineering | 6 | 602 | Throughout (beneath carpet) | Floor Covering | Vinyl Tiles (Blue Colour) | Positive - Removed | - | - | - | Item removed - No removal documentation provided | Yes |
KENC | Kensington Campus | H20 | Civil Engineering | 6 | 602A | Throughout (beneath carpet) | Floor Covering | Vinyl Tiles (Blue Colour) | Positive - Removed | - | - | - | Item removed 13/5/2009 by Cardinal Project Services - NAA Clearance Certificate (Ref: SU0013:738014) | Yes |
KENC | Kensington Campus | H20 | Civil Engineering | 6 | 605 | Throughout (beneath carpet) | Floor Covering | Vinyl Tiles (Blue Colour) | Positive - Removed | - | - | - | Item removed - No removal documentation provided | Yes |
KENC | Kensington Campus | H20 | Civil Engineering | 6 | 610 | Throughout (beneath carpet) | Floor Covering | Vinyl Tiles (Blue Colour) | Positive - Removed | - | - | - | Item removed 25/8/2012 by Pure Contracting - NAA Clearance Certificate (Ref: C107946:J105057) | Yes |
KENC | Kensington Campus | H20 | Civil Engineering | 6 | 611 | Throughout (beneath carpet) | Floor Covering | Vinyl Tiles (Blue Colour) | Positive - Removed | - | - | - | Item removed - No removal documentation provided | Yes |
KENC | Kensington Campus | H20 | Civil Engineering | 6 | 611A | Throughout (beneath carpet) | Floor Covering | Vinyl Tiles (Blue Colour) | Positive - Removed | - | - | - | Item removed - No removal documentation provided | Yes |
KENC | Kensington Campus | H20 | Civil Engineering | 6 | 611B | Throughout (beneath carpet) | Floor Covering | Vinyl Tiles (Blue Colour) | Positive - Removed | - | - | - | Item removed - No removal documentation provided | Yes |
KENC | Kensington Campus | H20 | Civil Engineering | 6 | 613 | Throughout (beneath carpet) | Floor Covering | Vinyl Tiles (Blue Colour) | Positive - Removed | - | - | - | Item removed 10/5/2014 by Pure Contracting - NAA Clearance Certificate (Ref: C107946:J126339) | Yes |
KENC | Kensington Campus | H20 | Civil Engineering | 6 | 614 | Throughout (beneath carpet) | Floor Covering | Vinyl Tiles (Blue Colour) | Positive - Removed | - | - | - | Item removed 26/9/2012 by Pure Contracting - NAA Clearance Certificate (Ref: C107946:J115471) | Yes |
KENC | Kensington Campus | H20 | Civil Engineering | 6 | 615 | Throughout (beneath carpet) | Floor Covering | Vinyl Tiles (Blue Colour) | Positive - Removed | - | - | - | Item removed 26/9/2012 by Pure Contracting - NAA Clearance Certificate (Ref: C107946:J115471) | Yes |
KENC | Kensington Campus | H20 | Civil Engineering | 6 | 616 | Throughout (beneath carpet) | Floor Covering | Vinyl Tiles (Blue Colour) | Positive - Removed | - | - | - | Item removed - No removal documentation provided | Yes |
KENC | Kensington Campus | H20 | Civil Engineering | LG | LG11 | Throughout | Floor Covering | Vinyl Tiles (Green Colour) | Positive - Removed | - | - | - | Item removed 1/12/2011 by Pure Contracting - NAA Clearance Certificate (Ref: SU0263:96374) | Yes |
KENC | Kensington Campus | H20 | Civil Engineering | LG | LG3 | Throughout | Floor Covering | Vinyl Tiles (Mustard Colour) | Positive - Removed | - | - | - | Item removed 1/8/2013 by Pure Contracting - NAA Clearance Certificate (Ref: C107859:J121395) | Yes |
KENC | Kensington Campus | H20 | Civil Engineering | G | G6 | Throughout | Floor Covering | Vinyl Tiles (Green Colour) | Positive - Removed | - | - | - | Item removed 13/6/2015 by Pure Contracting - Greencap-NAA Clearance Certificate (Ref: J107859:J133139) | Yes |
KENC | Kensington Campus | H20 | Civil Engineering | 5 | 501 | Throughout (previously rooms 501A, 501B, 501C, 501D, 501E & 501F | Floor Covering | Vinyl Tiles (Aqua, White & Light Green Colour) | Positive - Removed | - | - | - | Item removed - No removal documentation provided | Yes |
KENC | Kensington Campus | H20 | Civil Engineering | 4 | 406A | Throughout (beneath carpet) | Floor Covering | Vinyl Tiles (Grey Colour) | Positive - Removed | - | - | - | Item removed 18/9/2009 by Cardinal Project Services - NAA Clearance Certificate (Ref: SS0263:76754) | Yes |
KENC | Kensington Campus | H20 | Civil Engineering | 4 | 406 | Throughout (beneath carpet) | Floor Covering | Vinyl Tiles (Grey Colour) | Positive - Removed | - | - | - | Item removed - No removal documentation provided | Yes |
KENC | Kensington Campus | H20 | Civil Engineering | 7 | 701 | Throughout (beneath carpet) | Floor Covering | Vinyl Tiles (Blue Colour) | Positive - Removed | - | - | - | Item removed 18/7/2015 by Pure Contracting - Greencap-NAA Clearance Certificate (Ref: C107859:J134209) | Yes |
KENC | Kensington Campus | H20 | Civil Engineering | 7 | 704 | Throughout (beneath carpet) | Floor Covering | Vinyl Tiles (Blue Colour) | Positive - Removed | - | - | - | Item removed - No removal documentation provided | Yes |
KENC | Kensington Campus | H20 | Civil Engineering | 7 | 707 | Throughout (beneath carpet) | Floor Covering | Vinyl Tiles (Blue Colour) | Positive - Removed | - | - | - | Item removed 23/3/2019 by Pure Contracting - RiskTech Clearance Certifcate dated 25/3/2019 | Yes |
KENC | Kensington Campus | H20 | Civil Engineering | 7 | 708 | Throughout (beneath carpet) | Floor Covering | Vinyl Tiles (Blue Colour) | Positive - Removed | - | - | - | Item removed 25/8/2012 by Pure Contracting - NAA Clearance Certificate (Ref: C107946:J105057) | Yes |
KENC | Kensington Campus | H20 | Civil Engineering | 7 | 713 | Throughout | Floor Covering | Vinyl Tiles (Blue Colour) | Positive - Removed | - | - | - | Item removed - No removal documentation provided for review | Yes |
KENC | Kensington Campus | H20 | Civil Engineering | 7 | 717 | Throughout (beneath carpet) | Floor Covering | Vinyl Tiles (Blue Colour) | Positive - Removed | - | - | - | Item removed 17/11/2018 by Pure Contracting - RiskTech Clearance Certifcate dated 17/11/2018 | Yes |
KENC | Kensington Campus | H20 | Civil Engineering | 7 | 717A | Throughout (beneath carpet) | Floor Covering | Vinyl Tiles (Blue Colour) | Positive - Removed | - | - | - | Item removed 17/11/2018 by Pure Contracting - RiskTech Clearance Certifcate dated 17/11/2018 | Yes |
KENC | Kensington Campus | H20 | Civil Engineering | 7 | 717B | Throughout (beneath carpet) | Floor Covering | Vinyl Tiles (Blue Colour) | Positive - Removed | - | - | - | Item removed 17/11/2018 by Pure Contracting - RiskTech Clearance Certifcate dated 17/11/2018 | Yes |
KENC | Kensington Campus | H20 | Civil Engineering | 7 | 717C | Throughout (beneath carpet) | Floor Covering | Vinyl Tiles (Blue Colour) | Positive - Removed | - | - | - | Item removed 17/11/2018 by Pure Contracting - RiskTech Clearance Certifcate dated 17/11/2018 | Yes |
KENC | Kensington Campus | H20 | Civil Engineering | 7 | 711 | Throughout | Floor Covering | Vinyl Tiles (Grey & Dark Blue Colour) | Positive - Removed | - | - | - | Item removed - No removal documentation provided for review | Yes |
KENC | Kensington Campus | H20 | Civil Engineering | 7 | 711A | Throughout | Floor Covering | Vinyl Tiles (Grey & Dark Blue Colour) | Positive - Removed | - | - | - | Item removed - No removal documentation provided for review | Yes |
KENC | Kensington Campus | H20 | Civil Engineering | 8 | 802 | Throughout (beneath carpet) | Floor Covering | Vinyl Tiles (Blue Colour) | Positive - Removed | - | - | - | Item removed 17/11/2018 by Pure Contracting - RiskTech Clearance Certifcate dated 17/11/2018 | Yes |
KENC | Kensington Campus | H20 | Civil Engineering | 8 | 802A | Throughout (beneath carpet) | Floor Covering | Vinyl Tiles (Blue Colour) | Positive - Removed | - | - | - | Item removed 17/11/2018 by Pure Contracting - RiskTech Clearance Certifcate dated 17/11/2018 | Yes |
KENC | Kensington Campus | G27 | AGSM | LG | LGQ18 | (Previously Room LG08), Throughout | Ceiling | Fibre Cement Sheeting | Positive - Removed | - | - | - | Item Removed. No removal/clearance documentation was provided. | Yes |
KENC | Kensington Campus | G27 | AGSM | LG | LGQ17 | (Previously Room LG09), Throughout | Ceiling | Fibre Cement Sheeting | Positive - Removed | - | - | - | Item Removed. No removal/clearance documentation was provided. | Yes |
KENC | Kensington Campus | G27 | AGSM | 2 | 2Q3 | Fire Stairwell | Fire Door (tagged 'Masterbilt') | Core Insulation | Positive - Removed | - | - | - | Item Removed. No removal/clearance documentation was provided. | Yes |
KENC | Kensington Campus | F22 | Bank | - | - | Exterior, West Side | Window Frames (between frame and pane) | Mastic Sealant | Removed - Positive | - | - | - | Item Removed: No removal/clearance documentation was provided. New appearance window framework - rubber seals. | Yes |
KENC | Kensington Campus | F13 | Science Theatre | LG | LG1 | Northern End, Eastern Side | Fire Door | Core Insulation | Positive - Removed | - | - | - | Item removed 27/2/2016 by ATS. Refer to Greencap Clearance Certificate dated 29/2/2016 (reference: C106266:J143335). | Yes |
KENC | Kensington Campus | F13 | Science Theatre | 1 | 1Q7 | Under Stair | Floor Lining | Fibre Cement Sheeting | Positive - Removed | - | - | - | Item Removed by Pure Contracting. Refer to RiskTech Clearance Certificate dated 3/6/2017. | Yes |
KENC | Kensington Campus | E6 | Roundhouse | G | - | Exterior, Surrounding | Awning Ceiling | Fibre Cement Sheeting | Positive - Removed | - | - | - | Item removed. No removal/clearance documentation was provided. | Yes |
KENC | Kensington Campus | E6 | Roundhouse | 01 | - | Exterior, Surrounding | Awning Ceiling | Fibre Cement Sheeting | Positive - Removed | - | - | - | Item removed. No removal/clearance documentation was provided. | Yes |
KENC | Kensington Campus | E6 | Roundhouse | R | - | Under Air Conditioning Unit, covered by Loose Insulation Material | Floor Lining | Fibre Cement Sheeting | Positive - Removed | - | - | - | Item removed. No removal/clearance documentation was provided. | Yes |
KENC | Kensington Campus | E6 | Roundhouse | 01 | Former Room 102 | Throughout | Flue | Moulded Fibre Cement | Positive - Removed | - | - | - | Item removed 5/6/2010. Refer to NAA Clearance Certificate SS0263:77747 dated June 2010. | Yes |
KENC | Kensington Campus | E6 | Roundhouse | 01 | Former Room 102 | Ceiling Space | Pipework | Lagging | Positive - Removed | - | - | - | Item removed 5/6/2010. Refer to NAA Clearance Certificate SS0263:77747 dated June 2010. | Yes |
KENC | Kensington Campus | E4 | Squarehouse | G | G19 | Ceiling Space, Attached to Nail Heads | Debris | Fibre Cement Sheeting | Positive (Removed) | - | - | - | - | Yes |
KENC | Kensington Campus | D23 | Mathews Theatres | 01 | 150 | Plant Room, On Top of Air Handling Unit | Debris | Pipe Lagging | Removed - Positive | - | - | - | Item Removed 1/6/2007. Refer to NAA Clearance Certificate 57647. | Yes |
KENC | Kensington Campus | D23 | Mathews Theatres | 03 | 304 | - | Fire Door | Core Insulation | Positive (Removed) | - | - | - | Item removed. No removal/clearance documentation was provided. | Yes |
Kenc | Kensington Campus | D16 | Goldstein Hall | 01 | 105 | - | Floor Covering | Vinyl Tiles (black colour) | Positive (Removed) | - | - | - | Item Removed 21/01/2011. Refer to NAA Clearance Report SS0263:77747. | Yes |
Kenc | Kensington Campus | D16 | Goldstein Hall | 02 | 201 | - | Wall | Fibre Cement Sheeting | Positive (Removed) | - | - | - | Item Removed. No removal documentation provided. | Yes |
Kenc | Kensington Campus | D16 | Goldstein Hall | 02 | 201 | - | Floor Covering | Vinyl Tiles | Positive (Removed) | - | - | - | Item Removed. No removal documentation provided. | Yes |
COFA | Paddington Campus | CFAC | Block C | 02 | C201 | Throughout | Floor Covering | Vinyl Tiles | Positive (Removed) | - | - | - | - | Yes |
COFA | Paddington Campus | CFAC | Block C | G | CG11 | Throughout | Ceiling | Fibre Cement Sheeting | Positive (Removed) | - | - | - | - | Yes |
COFA | Paddington Campus | CFAC | Block C | 01 | C1Q3 | Cupboard | Ceiling | Fibre Cement Sheeting | Positive (Removed) | - | - | - | - | Yes |
COFA | Paddington Campus | CFAC | Block C | 02 | C2Q3 | Throughout | Floor Covering | Vinyl Tiles | Negative (Removed) | - | - | - | - | Yes |
KENC | Kensington Campus | F20 | Goodsell | 01 | 1Q6A | Plumbling Duct Adjacent Room 126A Toilets | - | Insulation Debris | Positive - Removed | - | - | - | Item Removed: Refer to NAA Clearance Certificate dated 3 September 2007 (Ref: 59392). | Yes |
KENC | Kensington Campus | F20 | Goodsell | 01 | 115A | Cleaners Room/Store | Pipework | Insulation | Positive - Removed | - | - | - | Item Removed: Refer to NAA Clearance Certificate dated 3 September 2007 (Ref: 59392). | Yes |
KENC | Kensington Campus | F20 | Goodsell | 01 | 1Q6A | Plumbling Duct Adjacent Room 126A Toilets | Pipework | Insulation | Positive - Removed | - | - | - | Item Removed: Refer to NAA Clearance Certificate dated 3 September 2007 (Ref: 59392). | Yes |
KENC | Kensington Campus | F20 | Goodsell | 02 | 217 | Cleaners Room/Store | Pipework | Insulation | Positive - Removed | - | - | - | Item Removed: Refer to NAA Clearance Certificate dated 3 September 2007 (Ref: 59392). | Yes |
KENC | Kensington Campus | C22 | Chancellery | 02 | 242 | - | Ceiling | Decorative Coating (vermiculite) | Negative | - | - | - | - | N/A |
KENC | Kensington Campus | C22 | Chancellery | 02 | 242 | Under Carpet | Floor Covering | Vinyl Tiles | Negative | - | - | - | - | N/A |
KENC | Kensington Campus | F20 | Goodsell | G | G15 | Cleaners Room/Store | Pipework | Insulation | Positive - Removed | - | - | - | Item Removed: Refer to NAA Clearance Certificate dated 3 September 2007 (Ref: 59392). | Yes |
KENC | Kensington Campus | F20 | Goodsell | 02 | 2Q3A | Plumbling Duct off Room 238 Toilets | Pipework | Insulation | Positive - Removed | - | - | - | Item Removed: Refer to NAA Clearance Certificate dated 3 September 2007 (Ref: 59392). | Yes |
KENC | Kensington Campus | C22 | Chancellery | 03 | 3Q2 | Under Carpet | Floor Covering | Vinyl Tiles (brown colour) | Negative | - | - | - | - | N/A |
KENC | Kensington Campus | C20 | Morven Brown | LG | LGQ10 | Above Ceiling Tiles | Ceiling | Vermiculite | Positive - Removed | - | - | - | Item not sighted during 2014 inspection. Further investigation may be required prior to refurbishment works in this area. | Yes |
KENC | Kensington Campus | C20 | Morven Brown | G | GQ11 | Stairwell | Fire Door | Core Insulation | Positive - Removed | - | - | - | Item removed. No removal/clearance documentation was provided. | Yes |
KENC | Kensington Campus | C20 | Morven Brown | 3 | 3Q12 | Ceiling Space | Ductwork Reheat Unit | Millboard Insulation | Positive - Removed | - | - | - | Item removed 30-06-2007. Refer to NAA Clearance Report SU0013:57917 | Yes |
KENC | Kensington Campus | C20 | Morven Brown | 3 | 3Q12 | Roof Space Access Door | Fire Door | Core Insulation | Positive - Removed | - | - | - | Item removed. No removal/clearance documentation was provided. | Yes |
KENC | Kensington Campus | C20 | Morven Brown | 3 | 3Q6 | Roof Space Access Door | Fire Door | Core Insulation | Positive - Removed | - | - | - | Item removed. No removal/clearance documentation was provided. | Yes |
KENC | Kensington Campus | C20 | Morven Brown | 3 | 3Q2 | Roof Space Access Door | Fire Door | Core Insulation | Positive - Removed | - | - | - | Item removed. No removal/clearance documentation was provided. | Yes |
KENE | Kensington Environs | BS26 | 26 Botany Street | G | - | Exterior, Under Gate Column | Packer | Fibre Cement Sheeting | Positive - Removed | - | - | - | Item removed. No removal/clearance documentation was provided. | Yes |
KENC | Kensington Campus | B5 | Fitness and Aquatic Centre | G | G43 | Squash Courts (B7) | Partition Wall | Fibre Cement Sheeting | Positive - Removed | - | - | - | No removal/clearance documentation was provided. | Yes |
COFA | Paddington Campus | CFAC | Block C | B | CBQ5 | - | Awning ceiling | Fibre Cement Sheeting | Positive (Removed) | - | - | - | - | Yes |
COFA | Paddington Campus | CFAC | Block C | G | - | Covered Walkway | Ceiling | Fibre Cement Sheeting | Positive (Removed) | - | - | - | - | Yes |
RANC | Randwick Campus | R1 | Randwick R1 | G | G34A/G35A | Female Toilets, South | Ceiling | Fibre Cement Sheeting | Positive (Removed) | - | - | - | Item removed. No removal/clearance documentation was provided. | Yes |
RANC | Randwick Campus | R1 | Randwick R1 | G | - | Exterior, Windows | Infill Panels | Fibre Cement Sheeting | Positive (Removed) | - | - | - | Item removed by Uniport Australia Pty Ltd. Date of removal unknown. | Yes |
RANC | Randwick Campus | R1 | Randwick R1 | G | G28 | Adjacent Canteen Exit Door, West Side | Wall Panelling Surrounding Door | Fibre Cement Sheeting | Positive (Removed) | - | - | - | Item removed. No removal/clearance documentation was provided. | Yes |
KENC | Kensington Campus | H20 | Civil Engineering | LG | LG11 | Above Entrance | Duct Heater Banks x2 | Millboard | Positive - Removed | - | - | - | Item removed - No removal documentation provided | Yes |
KENC | Kensington Campus | F23 | Mathews Building | 7 | 730 | Service Duct Entry off Room 730 | Fire Door | Core Insulation | Removed - Positive | - | - | - | Item Removed: Refer to Greencap-NAA Clearance Certificate dated 16 March 2015 (Ref: J131981.002). Removed by Pure Contracting. | Yes |
KENC | Kensington Campus | F23 | Mathews Building | 7 | 7Q3 | - | Fire Door | Core Insulation | Removed - Positive | - | - | - | Item Removed: No removal / clearance documentation provided. | Yes |
KENC | Kensington Campus | F23 | Mathews Building | 10 | 10Q3 | - | Fire Door | Core Insulation | Removed - Positive | - | - | - | Item Removed: No removal / clearance documentation provided. | Yes |
KENC | Kensington Campus | F23 | Mathews Building | 8 | 838 | - | Fire Door | Core Insulation | Removed - Positive | - | - | - | Item Removed: No removal / clearance documentation provided. | Yes |
KENC | Kensington Campus | F23 | Mathews Building | 8 | 837 | Service Duct Entry | Fire Door | Core Insulation | Removed - Positive | - | - | - | Item Removed: No removal / clearance documentation provided. | Yes |
KENC | Kensington Campus | F23 | Mathews Building | 18 | 1801 | - | Fire Door | Core Insulation | Removed -Positive | - | - | - | Item Removed: No removal / clearance documentation provided. | Yes |
KENC | Kensington Campus | F23 | Mathews Building | 18 | 1803 | - | Fire Door | Core Insulation | Removed -Positive | - | - | - | Item Removed: No removal / clearance documentation provided. | Yes |
KENC | Kensington Campus | F23 | Mathews Building | 9 | 931 | - | Fire Door | Core Insulation | Removed - Positive | - | - | - | Item Removed: No removal / clearance documentation provided. | Yes |
KENC | Kensington Campus | F23 | Mathews Building | 11 | 11Q2 | - | Fire Door | Core Insulation | Removed - Positive | - | - | - | Item Removed: No removal / clearance documentation provided. | Yes |
KENC | Kensington Campus | F23 | Mathews Building | 14 | 1428 | Service Duct Entry off Room 1428 | Fire Door | Core Insulation | Removed -Positive | - | - | - | Item Removed: Refer to Greencap-NAA Clearance Certificate dated 16 March 2015 (Ref: J131981.002). Removed by Pure Contracting. | Yes |
KENC | Kensington Campus | F23 | Mathews Building | 14 | 1429 | - | Fire Door | Core Insulation | Removed -Positive | - | - | - | Item Removed: No removal / clearance documentation provided. | Yes |
KENC | Kensington Campus | F23 | Mathews Building | 13 | 13Q2 | - | Fire Door | Core Insulation | Removed -Positive | - | - | - | Item Removed: No removal / clearance documentation provided. | Yes |
KENC | Kensington Campus | F23 | Mathews Building | 13 | 13Q3 | - | Fire Door | Core Insulation | Removed -Positive | - | - | - | Item Removed: No removal / clearance documentation provided. | Yes |
KENC | Kensington Campus | F23 | Mathews Building | 14 | 14Q2 | - | Fire Door | Core Insulation | Removed -Positive | - | - | - | Item Removed: No removal / clearance documentation provided. | Yes |
KENC | Kensington Campus | F23 | Mathews Building | 17 | 1703 | - | Wall | Fibre Cement Sheeting | Removed -Positive | - | - | - | Item Removed: No removal / clearance documentation provided. | Yes |
KENC | Kensington Campus | C22 | Chancellery | 03 | 3Q3 | Roof Space, Throughout Ceiling Beams | Sprayed Insulation | Vermiculite | Negative | - | - | - | - | N/A |
KENC | Kensington Campus | C22 | Chancellery | 02 | 206 | - | Wall | Core Insulation | Negative | - | - | - | - | N/A |
KENC | Kensington Campus | C22 | Chancellery | 02 | 2Q3 | Exterior, Stairwell | Window Frames (between frame and pane) | Mastic Sealant | Negative | - | - | - | - | N/A |
KENC | Kensington Campus | C22 | Chancellery | 01 | - | Exterior, West Wing, North and South | Roof Covering | Bituminous Membrane | Negative | - | - | - | - | N/A |
KENC | Kensington Campus | C22 | Chancellery | LG | LGQ1 | - | Floor Covering and Adhesive | Vinyl Tiles | Negative | - | - | - | - | N/A |
KENC | Kensington Campus | C22 | Chancellery | LG | LG35 | North | Fire Doors (tagged 'Bismac 2013'') | Core Insulation | Negative | - | - | - | - | N/A |
KENC | Kensington Campus | C22 | Chancellery | LG | LG29 LG29A LG29B LG29C | - | Floor Covering and Adhesive | Vinyl Tiles | Negative | - | - | - | - | N/A |
KENC | Kensington Campus | C22 | Chancellery | LG | LGQ8 | Under Carpet | Floor Covering | Vinyl Tiles and Adhesive (brown colour) | Negative | - | - | - | - | N/A |
KENC | Kensington Campus | C22 | Chancellery | G | G24 | - | Ceiling | Decorative Coating (vermiculite) | Negative | - | - | - | - | N/A |
KENC | Kensington Campus | C22 | Chancellery | LG | LGQ4 | Stairwell | Fire Door (tagged 'Cecon, 199_') | Core Insulation | Suspected Negative | - | - | - | - | No |
KENC | Kensington Campus | C22 | Chancellery | LG | LGQ7 | Stairwell | Fire Door (tagged 'Cecon, 199_') | Core Insulation | Suspected Negative | - | - | - | - | No |
KENC | Kensington Campus | C22 | Chancellery | LG | LGQ9 | Stairwell | Fire Door (tagged 'Cecon, 199_') | Core Insulation | Suspected Negative | - | - | - | - | No |
KENC | Kensington Campus | C22 | Chancellery | LG | LGQ10 | Stairwell | Fire Door (tagged 'Cecon, 199_') | Core Insulation | Suspected Negative | - | - | - | - | No |
KENC | Kensington Campus | C22 | Chancellery | G | G10 | - | Fire Door (tagged 'Bismac, 2014') | Core Insulation | Suspected Negative | - | - | - | - | No |
KENC | Kensington Campus | C22 | Chancellery | G | G11 | West | Fire Door (tagged 'Cecon, 199_') | Core Insulation | Suspected Negative | - | - | - | - | No |
KENC | Kensington Campus | C22 | Chancellery | G | G15 | West | Fire Door (tagged 'Cecon, 199_') | Core Insulation | Suspected Negative | - | - | - | - | No |
KENC | Kensington Campus | C22 | Chancellery | G | GQ1 | Stairwell | Fire Door (tagged 'Cecon, 199_') | Core Insulation | Suspected Negative | - | - | - | - | No |
KENC | Kensington Campus | C22 | Chancellery | G | GQ2 | Stairwell | Fire Door (tagged 'Cecon, 199_') | Core Insulation | Suspected Negative | - | - | - | - | No |
KENC | Kensington Campus | C22 | Chancellery | G | GQ10 | Stairwell | Fire Doors (tagged ' Bismac, 2014') | Core Insulation | Suspected Negative | - | - | - | - | No |
KENC | Kensington Campus | C22 | Chancellery | G | GQ13 | Stairwell | Fire Door (no tag) | Core Insulation | Suspected Negative | - | - | - | - | No |
KENC | Kensington Campus | C22 | Chancellery | G | GQ14 | Stairwell | Fire Door | Core Insulation | Suspected Negative | - | - | - | - | No |
Kenc | Kensington Campus | D26 | Library | G | - | Biosciences North, | Awning Ceiling | Fibre Cement Sheeting | Positive - Removed | - | - | - | Item Removed: No removal / clearance documentation provided. | Yes |
KENC | Kensington Campus | C22 | Chancellery | 01 | 1Q2 | Stairwell | Fire Door (tagged 'Cecon, 199_') | Core Insulation | Suspected Negative | - | - | - | - | No |
KENC | Kensington Campus | K17 | Building K17 | 3 | 301 | Cleaners Cupboard | Floor Covering | Vinyl Tiles (dark brown colour) | Positive - Removed | - | - | - | Item removed. No removal/clearance documention was provided. | Yes |
KENC | Kensington Campus | C22 | Chancellery | 01 | 1Q7 | Stairwell | Fire Door (tagged 'Cecon, 199_') | Core Insulation | Suspected Negative | - | - | - | - | No |
KENC | Kensington Campus | K15 | Old Main | 02 | 208A | - | Floor Covering | Vinyl Tiles & Adhesive (green colour) | Positive (Removed) | - | - | - | Item removed. No removal/clearance documentation was provided. | Yes |
Kenc | Kensington Campus | G15 | Robert Webster Theatres | 02 | 290A | Lecture Theatre B, East Side, Projector Room, Ceiling Space, Above Ceiling | Ceiling | Fibre Cement Sheeting | Positive (Removed) | - | - | - | Item Removed by Pure Contracting on 10/6/2016. Refer to Greencap Clearance Certificate (C107859/J145185) dated 14/6/18. | Yes |
KENC | Kensington Campus | F23 | Mathews Building | 8 | 815 | - | Fire Door | Core Insulation | Removed - Positive | - | - | - | Item Removed: No removal / clearance documentation provided. | Yes |
KENC | Kensington Campus | F23 | Mathews Building | 8 | 8Q1 | - | Fire Door | Core Insulation | Removed - Positive | - | - | - | Item Removed: No removal / clearance documentation provided. | Yes |
KENC | Kensington Campus | F23 | Mathews Building | 8 | 8Q6 | - | Fire Door | Core Insulation | Removed - Positive | - | - | - | Item Removed: No removal / clearance documentation provided. | Yes |
KENC | Kensington Campus | F23 | Mathews Building | 17 | RQ01 | Western Roof Section, Near NW Corner, Surrounding Roof Opening to Duct Riser | Roof | Bituminous Membrane | Removed -Positive | - | - | - | Item Removed: Refer to RiskTech Clearance Certificate dated 25 May 2019. | Yes |
KENC | Kensington Campus | E6 | Roundhouse | G | Former Room G06 | Throughout Former Kitchen | Ceiling | Fibre Cement Sheeting | Positive - Removed | - | - | - | Item removed. No removal/clearance documentation was provided. | Yes |
KENC | Kensington Campus | E6 | Roundhouse | G | Former Room G05 | Throughout | Ceiling | Fibre Cement Sheeting | Positive - Removed | - | - | - | Item removed. No removal/clearance documentation was provided. | Yes |
KENC | Kensington Campus | E6 | Roundhouse | G | Former Room GQ06 | East Hallway | Floor Covering | Vinyl Tiles (brown colour) | Positive - Removed | - | - | - | Item removed. No removal/clearance documentation was provided. | Yes |
KENC | Kensington Campus | E6 | Roundhouse | G | Former Room G02B | Under Carpet Tiles | Floor Covering | Vinyl Tiles (blue and black colour) | Positive - Removed | - | - | - | Item removed. No removal/clearance documentation was provided. | Yes |
KENC | Kensington Campus | E6 | Roundhouse | R | - | Under Air Conditioning Unit, covered by Loose Insulation Material | Floor Lining | Fibre Cement Sheeting Debris | Positive - Removed | - | - | - | Item removed. No removal/clearance documentation was provided. | Yes |
KENC | Kensington Campus | E6 | Roundhouse | 01 | 1Q1, 1Q4, 1Q7 | Throughout, Beneath Purple Carpet | Floor Covering | Vinyl Tiles (blue and black colour) | Positive - Removed | - | - | - | Item removed. No removal/clearance documentation was provided. | Yes |
KENC | Kensington Campus | C22 | Chancellery | 01 | 1Q9 | Stairwell | Fire Doors (tagged 'Cecon, 199_') | Core Insulation | Suspected Negative | - | - | - | - | No |
Kenc | Kensington Campus | D9 | IO Myers Studio | G | G06 | East and South | Walls | Fibre Cement Sheeting | Positive - Removed | - | - | - | Item Removed by Pure Contracting on 19/03/2016. Refer to Greencap Clearance Certificate C107859:J143853 dated 21/03/16. | Yes |
FSFG | Fowlers Gap Field Station | FG4 | Fowlers Gap Cottage 5 | G | - | Exterior, Surrounding Cottage | Ground Surface | Fibre Cement Sheet Debris | Positive - Removed | - | - | - | Item Removed: UNSW site personnel informed RiskTech that fibre cement debris removed. RiskTech also removed fibre cement debris as part of the inspection process. | Yes |
FSFG | Fowlers Gap Field Station | FG18 | Fowlers Gap Cottage 4 | G | - | Exterior, Surrounding Cottage | On Ground Surface | Fibre Cement Sheet Debris | Positive - Removed | - | - | - | Item removed: UNSW site personnel informed RiskTech that fibre cement debris removed. RiskTech also removed fibre cement debris as part of the inspection process. | Yes |
FSFG | Fowlers Gap Field Station | FG5 | Fowlers Gap Cottage 2 | G | - | Exterior, Surrounding Cottage | On Ground Surface | Fibre Cement Sheet Debris | Positive - Removed | - | - | - | Item Removed: UNSW site personnel informed RiskTech that fibre cement debris removed. RiskTech also removed fibre cement debris as part of the inspection process. | Yes |
FSFG | Fowlers Gap Field Station | FG14 | Fowlers Gap Laboratory | G | - | Exterior, Surrounding Building | On Ground Surfaces | Fibre Cement Sheet Debris | Positive - Removed | - | - | - | Item removed. UNSW informed RiskTech that fibre cement debris removed. RiskTech also removed fibre cement debris as part of the inspection process. | Yes |
KENC | Kensington Campus | C22 | Chancellery | 02 | 239 | - | Fire Door (no tag) | Core Insulation | Suspected Negative | - | - | - | - | No |
KENC | Kensington Campus | C22 | Chancellery | 02 | 239A | - | Fire Door (no tag) | Core Insulation | Suspected Negative | - | - | - | - | No |
FSFG | Fowlers Gap Field Station | FG10 | Fowlers Gap Nissan Hut | G | - | Exterior, Surrounding Shed | On Ground Surface | Fibre Cement Sheet Debris | Positive - Removed | - | - | - | Demolished-Item Removed: UNSW site personnel informed RiskTech that fibre cement debris removed. RiskTech also removed fibre cement debris as part of the inspection process. | Yes |
FSFG | Fowlers Gap Field Station | FG10 | Fowlers Gap Nissan Hut | G | G01 | Storage Racks | Stored Pipes | Moulded Fibre Cement Pipes (x 2) | Positive - Removed | - | - | - | Demolished-Item Removed: UNSW site personnel informed RiskTech that fibre cement pipes removed. No stored asbestos containing fibre cement pipes sighted by RiskTech during the inspection. | Yes |
FSFG | Fowlers Gap Field Station | FG6 | Fowlers Gap Machinery Shed | G | - | Exterior, Surrounding Shed | On Ground Surface | Fibre Cement Sheet Debris | Positive - Removed | - | - | - | Item Removed: UNSW site personnel informed RiskTech that fibre cement debris removed. No fibre cement debris sighted by RiskTech during the inspection. | Yes |
KENC | Kensington Campus | C22 | Chancellery | 02 | 239B | - | Fire Door (no tag) | Core Insulation | Suspected Negative | - | - | - | - | No |
DPFS | David Phillips Field | DP4 | Grounds Depot | G | G02 | Shower | Cubicle Partitions | Fibre Cement Sheeting | Positive - Removed | - | - | - | Item Removed by Pure Contracting on 15/8/2017. Refer to RiskTech Clearance Report dated 15/08/2017. | Yes |
COFA | Paddington Campus | CFAC | Block C | SB | CSB04 | North | Floor Covering | Vinyl Tiles (grey colour) | Positive (Removed) | - | - | - | - | Yes |
COFA | Paddington Campus | CFAC | Block C | SB | CSB04 | North | Floor Covering | Vinyl Tiles (cream colour) | Positive (Removed) | - | - | - | - | Yes |
COFA | Paddington Campus | CFAA | Block A | G | AG14 | - | Flue | Bituminous Material | Positive (Removed) | - | - | - | Item removed prior to RiskTech inspection. No asbestos removal documentation was available for review. | Yes |
CCS | Cliffbrook Campus | CC2 | Building CC2 | G | - | Exterior, North | Communications Pit | Moulded Fibre Cement | Positive - Removed | - | - | - | Item removed. No removal/clearance documentation was provided. | Yes |
KENE | Kensington Environs | BS30 | 30 Botany Street | 1 | 104 | Kitchen, Beneath Grey Vinyl | Floor Covering | Sheet Vinyl (beige colour) | Positive - Removed | - | - | - | Item removed. No removal/clearance documentation provided. | Yes |
KENE | Kensington Environs | HS46 | 46 High Street | G | - | Switch Room, West Wall | Electrical Cabinet | Electrical Backing Board | Positive - Removed | - | - | - | Item Removed: No removal/clearance documentation was provided. | Yes |
KENC | Kensington Campus | F13 | Science Theatre | LG | LG1B | Boiler Room | Boiler, Pipe Flange Joint | Gasket | Positive - Removed | - | - | - | Item removed. No removal/clearance documentation was provided. | Yes |
KENC | Kensington Campus | B5 | Fitness and Aquatic Centre | G | G44 | Squash Courts (B7), Door Labelled '35 Store Room' | Floor Covering | Vinyl Tiles (orange/tan colour) | Positive - Removed | - | - | - | Item removed 8/5/2014. Refer to Airsafe Clearance Certificate (Job No. 23011). | Yes |
KENE | Kensington Environs | BS34 | 34 to 36 Botany Street | G | G07 | Interior, Throughout | Flooring | Compressed Fibre Cement Sheeting | Positive - Removed | - | - | - | Item Removed: 24-05-2014. Refer to Airsafe Inspection Report dated 24-05-2014 | Yes |
COFA | Paddington Campus | CFAA | Block A | B | AB3 | Plant Room | Air Conditioning Ductwork - Reheat Unit | Millboard Lining | Positive (Removed) | - | - | - | FM advised that this item had been removed prior to 27/07/2016. No asbestos removal documentation was available for review. | Yes |
COFA | Paddington Campus | CFAA | Block A | B | AB4 | Plant Room, West Side | Flue | Bituminous Material | Positive (Removed) | - | - | - | Item removed prior to RiskTech inspection. No asbestos removal documentation was available for review. | Yes |
COFA | Paddington Campus | CFAA | Block A | B | AB5 | Southern End | Flue | Bituminous Material | Positive (Removed) | - | - | - | Item removed prior to RiskTech inspection. No asbestos removal documentation was available for review. | Yes |
COFA | Paddington Campus | CFAA | Block A | B | AB2 | Exterior, Ceiling Penetration | Flue | Bituminous Material | Positive (Removed) | - | - | - | Item removed prior to RiskTech inspection. No asbestos removal documentation was available for review. | Yes |
KENC | Kensington Campus | K15 | Old Main | LG | LG06 & LG07C | - | Floor Covering | Vinyl Tiles | Positive (Removed) | - | - | - | Item Removed 18/06/2007. Refer to NAA Clearance Certificate 54547 and Air Monitoring Report 54547.001. | Yes |
RANC | Randwick Campus | R1 | Randwick R1 | 01 | - | Roof Space Throughout | - | Fibre Cement Sheet Debris & Dust | Positive (Removed) | - | - | - | Item removed. Refer to RiskTech Clearance Certificate dated 10/6/2016. | Yes |
KENC | Kensington Campus | C22 | Chancellery | 02 | 2Q1 | Stairwell | Fire Doors (tagged 'Cecon, 199_') | Core Insulation | Suspected Negative | - | - | - | - | No |
COFA | Paddington Campus | CFAA | Block A | G | AG11A | Throughout | Wall | Fibre Cement Sheeting | Positive (Removed) | - | - | - | Item removed by Aston Demolition. Refer to Airsafe Clearance Report dated 3/10/2016. Note: Room number discrepancies. | Yes |
COFA | Paddington Campus | CFAA | Block A | G | AG11B | Throughout | Wall | Fibre Cement Sheeting | Positive (Removed) | - | - | - | Item removed by Aston Demolition. Refer to Airsafe Clearance Report dated 3/10/2016. Note: Room number discrepancies. | Yes |
COFA | Paddington Campus | CFAA | Block A | G | AG11A | Throughout | Ceiling | Fibre Cement Sheeting | Positive (Removed) | - | - | - | Item removed by Aston Demolition. Refer to Airsafe Clearance Report dated 3/10/2016. Note: Room number discrepancies. | Yes |
COFA | Paddington Campus | CFAA | Block A | G | AG11B | Throughout | Ceiling | Fibre Cement Sheeting | Positive (Removed) | - | - | - | Item removed by Aston Demolition. Refer to Airsafe Clearance Report dated 3/10/2016. Note: Room number discrepancies. | Yes |
KENC | Kensington Campus | C22 | Chancellery | 02 | 2Q3 | Stairwell | Fire Doors (tagged 'Cecon, 199_') | Core Insulation | Suspected Negative | - | - | - | - | No |
KENC | Kensington Campus | F23 | Mathews Building | 6 | 623 | - | Fire Door | Core Insulation | Removed - Positive | - | - | - | Item Removed: Refer to Greencap-NAA Clearance Certificate dated 16 March 2015 (Ref: J131981.002). Removed by Pure Contracting. | Yes |
KENC | Kensington Campus | F23 | Mathews Building | 6 | 624 | - | Fire Door | Core Insulation | Removed - Positive | - | - | - | Item Removed: Refer to Greencap-NAA Clearance Certificate dated 16 March 2015 (Ref: J131981.002). Removed by Pure Contracting. | Yes |
KENC | Kensington Campus | C20 | Morven Brown | 1 | 103-107 | - | Bulkhead | Fibre Cement Sheeting | Positive - Removed | - | - | - | Item removed 16/6/2007. Refer to NAA Clearance Report SU0013:57545 and Air Monitoring Reports 57545.001 & 002 | Yes |
KENC | Kensington Campus | C20 | Morven Brown | 1 | 103-107 | - | Heater Bank | Millboard Insulation | Positive - Removed | - | - | - | Item removed 16/6/2007. Refer to NAA Clearance Report SU0013:57545 and Air Monitoring Reports 57545.001 & 002 | Yes |
Kenc | Kensington Campus | C6 | International House | G | G99 | Office - Ceiling Space | Hot Water Pipework | Insulation | Removed - Positive | - | - | - | Item Removed: No removal/clearance documentation was provided | Yes |
KENC | Kensington Campus | G27 | AGSM | 1 | 110 | Communications Riser Cupboard | Fire Door (no tag) | Core Insulation | Positive (Amosite & Chrysotile) | Friable | Low | P3 | Remedial works should be undertaken by a Class A Contractor within a planned control program. | No |
KENC | Kensington Campus | F21 | Library | 3 | 322 | Electrical Room Adjacent Fire Stairs (3Q14) | On Soffit Surrounding Column | Insulation Residue & Bituminous Coating (adhesive) | Removed - 'Positive (chrysotile & amosite) | - | - | - | Item Removed: Refer to RiskTech Clearance Certificate dated 25 May 2000. | Yes |
KENC | Kensington Campus | F12 | Dalton | G | - | Exterior of GQ2 | Window Frames (between frame and pane) | Mastic Sealant | Positive (chrysotile & amosite) | Non-Friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | F10 | Chemical Sciences | LG | LGQ2 | Substation No.9, Entrance | Fire Door - Double Doors (no tag) | Core Insulation | Removed - Positive (Chrysotile & Amosite) | - | - | - | Item Removed: Refer to RiskTech Compliance Clearance Certificate dated 3 December 2020. | Yes |
KENC | Kensington Campus | D23 | Mathews Theatres | 01 | 150 | North Entrance, Adjacent Room 1Q3 | Fire Door (tagged 'Metabilt, 1973') | Core Insulation | Removed -Positive (chrysotile & amosite) | - | - | - | Item Removed. Refer to RiskTech Compliance Asbestos Clearance Certificate dated. | Yes |
KENC | Kensington Campus | D23 | Mathews Theatres | 01 | 105 | Riser Entrance | Fire Door (tagged 'Metabilt, 1973') | Core Insulation | Removed -Positive (chrysotile & amosite) | - | - | - | Item Removed. Refer to RiskTech Compliance Asbestos Clearance Certificate dated. | Yes |
CCS | Cliffbrook Campus | CC1 | Cliffbrook House | G | - | Exterior, North-East | Communications Pit | Moulded Fibre Cement | Positive (Amosite & Chrysotile) | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | C22 | Chancellery | 02 | 2Q5 | Stairwell | Fire Doors (tagged 'Cecon, 199_') | Core Insulation | Removed | - | - | - | Item removed. Refer Risktech clearance cert dated 18th Sept 2023 | Yes |
Kenc | Kensington Campus | C6 | International House | 1 | 186A | Store - Riser | Access Panel | Fibre Cement Sheeting | Positive (Amosite & Chrysotile) - Removed | - | - | - | Item Removed: Refer to RiskTech Clearance Certificate dated 23rd December 2019 | Yes |
Kenc | Kensington Campus | C24 | Clancy Auditorium | LG | LG3 | Entrance | Fire Door (No Tag) | Core Insulation | Positive (chrysotile & amosite) | Friable | Low | P2 | Remedial works should be undertaken by a Class A Contractor within a planned control program. Note: Timber skin at base of door delaminating. | No |
Kenc | Kensington Campus | B21 | Repository | G | G01 | Exterior, Eastern Side, Surrounding Pipe Ends | Waterproof Membrane | Bituminous Membrane | Positive (Amosite & Chrysotile) | Non-friable | Low | P3 | Seal the membrane with an encapsulant / paint under controlled conditions by a Class A/B contractor. Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | K15 | Old Main | 02 | 232 | Ceiling Space | Toilet Cistern | Moulded Fibre Cement | Positive (chrysotile & amosite) | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment | No |
KENC | Kensington Campus | C22 | Chancellery | 02 | 2Q10 | Stairwell | Fire Doors (tagged 'Fire Systems Engineering, 199_') | Core Insulation | Suspected Negative | - | - | - | - | No |
KENC | Kensington Campus | F13 | Science Theatre | G | G16 | Stage Left | Flue | Moulded Fibre Cement Pipe | Removed: Positive (chrysotile & amosite) | - | - | - | Item Removed. Refer to Risktech Compliance Asbestos Clearance Certificate dated 26 August 2019. | Yes |
KENC | Kensington Campus | C22 | Chancellery | 02 | 2Q11 | Stairwell | Fire Doors (tagged 'Cecon, 199_') | Core Insulation | Suspected Negative | - | - | - | - | No |
KENC | Kensington Campus | C22 | Chancellery | 03 | 3Q1 | Stairwell | Fire Doors (tagged 'Cecon, 199_') | Core Insulation | Suspected Negative | - | - | - | - | No |
KENC | Kensington Campus | C22 | Chancellery | 03 | 3Q6 | Stairwell | Fire Doors (tagged 'Cecon, 199_') | Core Insulation | Suspected Negative | - | - | - | - | No |
Kenc | Kensington Campus | D18 | Phillip Baxter College | G-7 | - | Throughout | No asbestos materials identified | - | Negative | - | - | - | - | N/A |
Kenc | Kensington Campus | D18 | Phillip Baxter College | G-7 | - | Throughout, Electrical Cupboards | No asbestos materials identified | - | Negative | - | - | - | - | N/A |
Kenc | Kensington Campus | D18 | Phillip Baxter College | G-7 | - | Throughout, Communications Cupboards | No asbestos materials identified | - | Negative | - | - | - | - | N/A |
Kenc | Kensington Campus | D18 | Phillip Baxter College | G-7 | - | Throughout, Fire Stairs, Services Cupboards, Accommodation Rooms | Fire Doors (tagged 'Exodus, 2013') | Core Insulation | Suspected Negative | - | - | - | - | No |
Kenc | Kensington Campus | D18 | Phillip Baxter College | G-7 | - | Throughout, Kitchenettes and Cleaner's Rooms | Floor Covering | Sheet Vinyl | Suspected Negative | - | - | - | - | No |
Kenc | Kensington Campus | D23 | Bio Sciences North | LG | ELGQ01 | Biolink, | Fire Door | Insulation Core | Assumed Positive - Removed | - | - | - | Item Removed: No removal / clearance documentation provided. (Note: New fire door tagged 'Ikon Door - Manufactured 201-'). | Yes |
Kenc | Kensington Campus | D24 | Bio Sciences North | LG | ELGQ01A | Biolink, | Inside Electrical Distribution Cabinets | Electrical Backing Boards | Suspected Positive - Removed | - | - | - | Item Removed: No removal / clearance documentation provided. (Note: New switchboard electrical cabinets). | Yes |
Kenc | Kensington Campus | D25 | Bio Sciences North | LG | ELGQ01A | Biolink, | Fire Door | Insulation Core | Assumed Positive - Removed | - | - | - | Item Removed: No removal / clearance documentation provided. (Note: New fire door tagged 'Ikon Door - Manufactured 201-'). | Yes |
Kenc | Kensington Campus | D26 | Bio Sciences North | G | GQ12 | Biolink, | Fire Door (tagged 'Inglis, 1990') | Insulation Core | - | - | - | - | - | No |
Kenc | Kensington Campus | D26 | Bio Sciences North | 2 | 255 | Biolink | Ceiling Tiles | Fibre Cement Sheeting | Removed | - | - | - | Item removed. Refer Risktech Clearance cert dated 13/10/2021 | Yes |
Kenc | Kensington Campus | D26 | Bio Sciences North | G | G22 | Biolink, | Drainage Pipe (wrapped in black plastic sheeting) | Moulded Fibre Cement Pipe | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
Kenc | Kensington Campus | D26 | Bio Sciences North | 1 | 139 | Biolink | Drainage Pipe | Moulded Fibre Cement Pipe | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
Kenc | Kensington Campus | D26 | Bio Sciences North | 2 | 240 | Biolink | Drainage Pipe | Moulded Fibre Cement Pipe | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
Kenc | Kensington Campus | D26 | Bio Sciences North | 2 | 254 | Biolink | Drainage Pipe | Moulded Fibre Cement Pipe | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
Kenc | Kensington Campus | D26 | Bio Sciences North | 3 | 340 | Biolink | Drainage Pipe | Moulded Fibre Cement Pipe | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
Kenc | Kensington Campus | D26 | Bio Sciences North | 3 | 3Q7 | Biolink | Drainage Pipe | Moulded Fibre Cement Pipe (wrapped in black plastic sheeting) | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
Kenc | Kensington Campus | D26 | Bio Sciences North | 4 | 458 | Biolink | Drainage Pipe | Moulded Fibre Cement Pipe | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
Kenc | Kensington Campus | D26 | Bio Sciences North | 4 | 4Q7 | Biolink | Drainage Pipe | Moulded Fibre Cement Pipe (wrapped in black plastic sheeting) | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
Kenc | Kensington Campus | D26 | Bio Sciences North | 5 | 5Q10 | - | Drainage Pipe | Moulded Fibre Cement Pipe (wrapped in black plastic sheeting) | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
Kenc | Kensington Campus | D26 | Bio Sciences North | 6 | R01 | Plant Room | Drainage Pipe | Moulded Fibre Cement Pipe | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
Kenc | Kensington Campus | D26 | Bio Sciences North | G | GQ13 | Biolink | On Concrete Floor Slab (beneath floor covering) | Bituminous Adhesive | Positive - Removed | - | - | - | Item Removed: Refer to Risktech Clearance Certificate dated 10 September 2021 | Yes |
Kenc | Kensington Campus | D26 | Bio Sciences North | 1 | 134 | Biolink | On Concrete Floor Slab (beneath floor covering) | Bituminous Adhesive | Removed | - | - | - | Item removed. Refer Risktech Clearance cert dated 28/09/2021 | Yes |
Kenc | Kensington Campus | D26 | Bio Sciences North | 1 | 1Q12 | Biolink | On Concrete Floor Slab (beneath tiles) | Bituminous Adhesive | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
Kenc | Kensington Campus | D26 | Bio Sciences North | 1 | 138 | Biolink | On Concrete Floor Slab (suspected beneath carpet & tiles) | Bituminous Adhesive | Removed | - | - | - | Item removed. Refer Risktech Clearance cert dated 28/09/2021 | Yes |
Kenc | Kensington Campus | D26 | Bio Sciences North | 1 | 138A | Biolink | On Concrete Floor Slab (suspected beneath carpet & tiles) | Adhesive | Positive | - | - | - | Item removed. Refer Risktech Clearance cert dated 28/09/2021 | Yes |
Kenc | Kensington Campus | D26 | Bio Sciences North | 1 | 143 | Biolink | On Concrete Floor Slab (suspected beneath floor linoleum) | Bituminous Adhesive | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
Kenc | Kensington Campus | D26 | Bio Sciences North | 1 | 132A | Biolink, | Fire Door | Insulation Core | Removed | Friable | - | - | Item Removed: Refer to RiskTech Clearance Certificate dated 20200321. | Yes |
Kenc | Kensington Campus | D26 | Bio Sciences North | 2 | 240 | Biolink, | Walls | Fibre Cement Sheeting | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. (Note: No access at time of inspection - construction area). | No |
Kenc | Kensington Campus | D26 | Bio Sciences North | 3 | 340 | Biolink, | Walls | Fibre Cement Sheeting | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. (Note: No access at time of inspection - construction area). | No |
Kenc | Kensington Campus | D26 | Bio Sciences North | LG | LG024 | Biolink, | Drainage Pipe (wrapped in black plastic sheeting) | Moulded Fibre Cement Pipe | Positive | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
Kenc | Kensington Campus | D26 | Bio Sciences North | 2 | 254 | Biolink, | On Pipe | Loose Rpe Packing Insulation | Positive - Removed | - | - | - | Item Removed by RiskTech in 2017 (part of sampling process) | Yes |
FSFG | Fowlers Gap Field Station | FG22 | Fowlers Gap Greenhouse | G | - | Exterior, Approximately 50m East of Greenhouse | Protective Barriers | Moulded Fibre Cement Pipe Sections | Positive (Amosite & Chrysotile) | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment works. | No |
Kenc | Kensington Campus | C6 | International House | Roof | - | Above Men's Toilet Riser | Flues (assumed present - no access on roof) | Compressed Bituminous Pipes | Positive (chrysotile & amosite) | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
FSW | Wellington Field Station | WFS1 | Wellington Field Station Cottage | G | 1 | Main Residence, Exterior, All Sides | Walls & Gables | Profiled Fibre Cement Sheeting | Positive (Amosite & Chrysotile) | Non-friable | Low | P3 | Repair/seal the localised damage areas to the wall sheeting under controlled conditions within a planned control program. Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment works. | No |
FSW | Wellington Field Station | WFS4A | Wellington Field Station Cool Room | G | G01 | Throughout | Ceiling | Fibre Cement Sheeting | Positive (Amosite & Chrysotile) | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment works. | No |
FSSL | Smiths Lake Field Station | SL4 | Smiths Lake Boat Shed | G | - | Sub-Floor Space | On Top of Brick Piers, Packing Material | Fibre Cement Sheeting | Positive (Amosite & Chrysotile) | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment works. | No |
Kenc | Kensington Campus | D26 | Bio Sciences North | 5 | 565 | Between Room 565 & 565A | Partition Wall | Fibre Cement Sheeting | Positive - Removed | - | - | - | Item Removed: Refe to NAA Clearance Report (Ref: C107946:J105057) dated March 2012. | Yes |
Kenc | Kensington Campus | D26 | Bio Sciences North | 1 | 1Q12 | Biolink, | Floor Slab Penetrations | Packing Insulation | Positive - Removed | - | - | - | Item Removed: Refer to NAA Clearance Report C107859:J125585 dated March 2014. Material has been removed from accessible locations. | Yes |
KENC | Kensington Campus | F22 | Bank | 01 | - | Exterior, West, Covered Entry | Ceiling | Fibre Cement Sheeting | Positive (chrysotile & amosite) | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | D14 | UNSW Hall | G | MBGQ02 | Riser adjacent Room BG94A | Flue | Bituminous Cement | Positive (Amosite & Chrysotile) | - | - | - | Item removed. Refer Airsafe clearance cert dated 7/2/2023 | Yes |
FSH | Hay Field Station | HFS7 | Hay Field Station Quarters | G | - | Exterior, All Sides | Walls | Profiled Fibre Cement Sheeting | Positive (Amosite & Chrysotile) | Non-friable | Low | P3 | Repair/seal the localised damage areas to the wall sheeting under controlled conditions within a planned control program. Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment works. | No |
FSH | Hay Field Station | HFS8 | Hay Field Station Managers Office | G | - | Far SW Corner Room, Toilet (former uncovered awning) | Ceiling | Fibre Cement Sheeting | Positive (Amosite & Chrysotile) | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment works. | No |
FSH | Hay Field Station | HFS8 | Hay Field Station Managers Office | G | G01 | NW Corner Room, | Ceiling | Fibre Cement Sheeting | Positive (Amosite & Chrysotile) | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment works. | No |
Kenc | Kensington Campus | D26 | Bio Sciences North | 2 | 2Q7 | Biolink, | Floor Slab Penetrations | Packing Insulation | Positive - Removed | - | - | - | Item Removed: Refer to NAA Clearance Report C107859:J125585 dated March 2014. Material has been removed from accessible locations. | Yes |
Kenc | Kensington Campus | D26 | Bio Sciences North | 3 | 3Q6 | Biolink, | Floor Slab Penetrations | Packing Insulation | Positive - Removed | - | - | - | Item Removed: Refer to NAA Clearance Report C107859:J125585 dated March 2014. Material has been removed from accessible locations. | Yes |
FSH | Hay Field Station | HFS3 | Hay Field Station Machinery Shed | G | - | Approx. 20 Metres South East of Shed - Adjacent Scrap Metal Stockpile | Disused Pipe | Moulded Fibre Cement Material | Positive (Amosite & Chrysotile) | Non-friable | Low | P3 | Remove disused fibre cement pipe under controlled conditions within a planned control program. | No |
Kenc | Kensington Campus | D26 | Bio Sciences North | LG | LG06 | Biolink, | Debris | Fibre Cement Sheeting | Positive - Removed | - | - | - | Item Removed: No removal / clearance documentation provided. | Yes |
FSFG | Fowlers Gap Field Station | FG1 | Fowlers Gap Solarch House | G | - | Exterior Throughout | Walls | Fibre Cement Sheeting (pebble mix finish) | Positive (Amosite & Chrysotile) | Non-friable | Low | P4 | Removed between 26/08/2024 to 31/08/2023 as per Asbestos Clearance Certificate dated 03/09/2024 | Yes |
Kenc | Kensington Campus | D26 | Bio Sciences North | 1 | 138 | Biolink | Fibre Cement Sheeting | Fibre Cement Sheeting | Positive - Removed | - | - | - | Item Removed: No removal / clearance documentation provided. | Yes |
FSFG | Fowlers Gap Field Station | FG13 | Fowlers Gap Shearers Quarters | G | - | Exterior, North | (pebble mix finish) | Moulded Fibre Cement Material | Positive (Amosite & Chrysotile) | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment works | No |
FSFG | Fowlers Gap Field Station | FG14 | Fowlers Gap Laboratory | G | - | Exterior, All Sides | Walls | Profiled Fibre Cement Sheeting | Positive (Amosite & Chrysotile) | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment works. | No |
CCS | Cliffbrook Campus | CC4 | Building CC4 | 01 | - | Exterior, East | Windows (between Metal Framework & Glass) | Mastic Sealant | Positive (chrysotile) | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENE | Kensington Environs | AS22 | 22 Arthur Street | G | - | Exterior, Main Residence, Surrounding | FG001-38 | Fibre Cement Sheeting | Positive (Amosite & Chrysotile) | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment works. | No |
KENE | Kensington Environs | AS20 | 20 Arthur Street | G | - | Exterior, Garage | Positive | Corrugated Fibre Cement Sheeting | Positive (Amosite & Chrysotile) | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment works. | No |
KENE | Kensington Environs | AS12 | 12 Arthur Street | G | - | Exterior, North | (chrysotile & | Fibre Cement Sheeting | Positive (Amosite & Chrysotile) | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment works. | No |
KENE | Kensington Environs | AS10 | 10 Arthur Street | G | - | Exterior, West | amosite) | Moulded Fibre Cement | Positive (Amosite & Chrysotile) | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment works. | No |
KENE | Kensington Environs | AS2 | 2 Arthur Street | G | - | Exterior, Rear, South, East and West | 1 & 2 ~250 m² Fair-Good Non-friable Low Low Yes P4 | Fibre Cement Sheeting | Positive (Amosite & Chrysotile) | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment works. | No |
KENE | Kensington Environs | AS2 | 2 Arthur Street | G | - | Exterior, Garage, East and West | Gable | Fibre Cement Sheeting | Positive (Amosite & Chrysotile) | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment works. | No |
KENE | Kensington Environs | HS34 | 34 High Street | 2 | 105 | Interior, Unit 3, Kitchen | Service Riser, Wall Lining | Fibre Cement Sheeting | Positive (Amosite & Chrysotile) | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENE | Kensington Environs | HS34 | 34 High Street | 2 | 106 | Interior, Unit 4, Kitchen | Service Riser, Wall Lining | Fibre Cement Sheeting | Positive (Amosite & Chrysotile) | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENE | Kensington Environs | HS34 | 34 High Street | 1 | G06 | Interior, Unit 1, Kitchen | Service Riser, Wall Lining | Fibre Cement Sheeting | Positive (Amosite & Chrysotile) | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | K17 | Building K17 | 4 | 4Q02 | Communications Riser | Packing Material | Insulation | Removed | - | - | - | Item removed. Refer RiskTech Clearance Certificate 20210616 | Yes |
KENC | Kensington Campus | K17 | Building K17 | 5 | 5Q01 | Communications Riser | Packing Material | Insulation | Removed | - | - | - | Item removed.Refer Risktech clearance cert dated 20210616 | Yes |
KENC | Kensington Campus | K17 | Building K17 | 6 | 6Q01 | Fire Hose Cupboard | Packing Material | Insulation | Removed | - | - | - | Item removed. Refer RiskTech Clearance Certificate 20210616 | Yes |
KENC | Kensington Campus | K17 | Building K17 | 7 | 703 | Lift Motor Room, North & East Walls | Packing Material | Insulation | Removed | - | - | - | Item removed. Refer RiskTech Clearance Certificate 20210616 | Yes |
KENC | Kensington Campus | K17 | Building K17 | 7 | 702 | Plant Room, North, Ground Surface, Electrical Penetrations | Packing Material | Insulation | Removed | - | - | - | Item removed. Refer RiskTech Clearance Certificate 20210616 | Yes |
KENC | Kensington Campus | K17 | Building K17 | 7 | 702 | Plant Room, North Wall, Vent Pipe | Packing Material | Insulation | Removed | - | - | - | Item removed. Refer RiskTech Clearance Certificate 20210616 | Yes |
KENC | Kensington Campus | F23 | Mathews Building | 12 | 1227 | - | Fire Panel Above Door | Core Insulation | Removed - Positive (amosite) | - | - | - | Item Removed: Refer to RiskTech Compliance Clearance Certificate dated 1 May 2020. | Yes |
KENC | Kensington Campus | F23 | Mathews Building | 10 | 1027 | - | Fire Panel Above Door | Core Insulation | Positive (amosite) | Friable | Low | P3 | Remove fire panel by a Class A Contractor within a planned control program. | No |
KENC | Kensington Campus | F23 | Mathews Building | 7 | 730 | - | Fire Panel Above Door | Core Insulation | Positive (amosite) | Friable | Low | P3 | Remove fire panel by a Class A Contractor within a planned control program. | No |
KENC | Kensington Campus | F21 | Library | 10 | 10Q8 | SW Fire Stairs, West | Structural Steel Element (Angle) | Insulation (encapsulated) | Positive (amosite) | Friable | Med | P3 | Consider removal of asbestos insulation from the steel angle under controlled conditions by a Class A contractor as part of a planned control program. | No |
KENC | Kensington Campus | F21 | Library | LG | LGQ08 | Redundant Chiller Plant Room | Inside Cable Tray / Ducts | Insulation Debris | Removed - 'Positive (amosite) | - | - | - | Item Removed: Refer to RiskTech Clearance Certificate dated 22 June 2020 & 29 October 2021. | Yes |
KENC | Kensington Campus | F21 | Library | LG | LGQ08 | Redundant Chiller Plant Room | On Soffit & Adjacent Surfaces | Insulation Residue (mostly beneath white coloured encapsulant) | Removed - 'Positive (amosite) | - | - | - | Item Removed: Refer to RiskTech Clearance Certificate dated 22 June 2020 & 29 October 2021. | Yes |
KENC | Kensington Campus | F21 | Library | LG | LGQ08 | Redundant Chiller Plant Room | Hot Water Pipework | Insulation (calico covered) | Removed - 'Positive (amosite) | - | - | - | Item Removed: Refer to RiskTech Clearance Certificate dated 22 June 2020 & 29 October 2021. | Yes |
Kenc | Kensington Campus | D26 | Bio Sciences North | LG | LG06 | Biolink, | Fire Door | Insulation Core | Positive - Removed | - | - | - | Item Removed: No removal / clearance documentation provided. (Note: New fire door). | Yes |
Kenc | Kensington Campus | D26 | Bio Sciences North | LG | LG06 | Biolink, | Walls & Ceiling | Fibre Cement Sheeting | Positive - Removed | - | - | - | Item Removed: Refer to WSP Clearance Certificate dated May 2017. | Yes |
Kenc | Kensington Campus | D26 | Bio Sciences North | LG | LG01 | Biosciences North | Pipe System Flange Blanket | Woven Insulation | Positive - Removed | - | - | - | Item Removed: No removal / clearance documentation provided. | Yes |
Kenc | Kensington Campus | D26 | Bio Sciences North | G | G22 | Biolink | Fire Door | Insulation Core | Positive - Removed | - | - | - | Item Removed: Refer to Greencap NAA Asbestos Clearance Certificate (Ref: C107266:J134916.003) dated 28 September 2015. (Note: New fire door tagged 'TDF 2014'). | Yes |
Kenc | Kensington Campus | D26 | Bio Sciences North | G | GQ13 | Biolink | Ceiling Tiles | Fibre Cement Sheeting | Positive - Removed | - | - | - | Item Removed: No removal / clearance documentation provided. | Yes |
Kenc | Kensington Campus | C6 | International House | G | G3 | Accommodation Room - Bulkhead Ceiling Space / Wardrobe Cupboard (upper area) | Hot Water Pipework | Insulation (localised exposed insulation) | Removed -Positive (amosite) | - | - | - | Item Removed: Refer to RiskTech Asbestos Clearance Certificate dated 23 December 2019. Removed by Pure Contracting. | Yes |
Kenc | Kensington Campus | C6 | International House | G | GQ8 | Plumbing Riser Adjacent Room G2 | Hot Water Pipework | Insulation (no insulation covering present) | Removed -Positive (amosite) | - | - | - | Item Removed: Refer to RiskTech Asbestos Clearance Certificate dated 23 December 2019. Removed by Pure Contracting. | Yes |
Kenc | Kensington Campus | C6 | International House | 1 | 196 | Female Amenities / Toilets - Plumbing Riser | On Floor, Walls & Other Surfaces | Insulation Residue & Debris | Positive (Amosite) - Removed | - | - | - | Item Removed: Refer to RiskTech Clearance Certificate dated 23rd December 2019 | Yes |
Kenc | Kensington Campus | C6 | International House | 2 | 296 | Female Amenities / Toilets - Plumbing Riser | On Floor, Walls & Other Surfaces | Insulation Residue & Debris | Positive (Amosite) - Removed | - | - | - | Item Removed: Refer to RiskTech Clearance Certificate dated 23rd December 2019 | Yes |
Kenc | Kensington Campus | C6 | International House | 2 | 299 | Male Amenities / Toilets - Plumbing Riser | On Floor, Walls & Other Surfaces | Insulation Residue & Debris | Positive (Amosite) - Removed | - | - | - | Item Removed: Refer to RiskTech Clearance Certificate dated 23rd December 2019 | Yes |
Kenc | Kensington Campus | C6 | International House | 3 | 396 | Female Amenities / Toilets - Plumbing Riser | On Floor, Walls & Other Surfaces | Insulation Residue & Debris | Positive (Amosite) - Removed | - | - | - | Item Removed: Refer to RiskTech Clearance Certificate dated 23rd December 2019 | Yes |
Kenc | Kensington Campus | C6 | International House | 3 | 399 | Male Amenities / Toilets - Plumbing Riser | On Floor, Walls & Other Surfaces | Insulation Residue & Debris | Positive (Amosite) - Removed | - | - | - | Item Removed: Refer to RiskTech Clearance Certificate dated 23rd December 2019 | Yes |
Kenc | Kensington Campus | C24 | Clancy Auditorium | G | G2 | South | Fire Damper Panel | Core Insulation | Positive (amosite) | Friable | Low | P3 | Remediation works on fire panels should be undertaken by a Class A Contractor within a planned control program. | No |
KENC | Kensington Campus | F23 | Mathews Building | 15 | 1510A | Below Windows, Behind Plasterboard Wall Panelling | Façade Spandrel Panel Brackets | Insulation | Positive (amosite) | Friable | Low | P3 | Maintain in good condition. Remove under controlled conditions by a Class A contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | F23 | Mathews Building | 11 | 1123 | Below Windows, Behind Plasterboard Wall Panelling | Façade Spandrel Panel Brackets | Insulation | Positive (amosite) | Friable | Low | P3 | Maintain in good condition. Remove under controlled conditions by a Class A contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | F23 | Mathews Building | 14 | 1407 | Below Windows, Behind Plasterboard Wall Panelling | Façade Spandrel Panel Brackets | Insulation | Positive (amosite) | Friable | Low | P3 | Maintain in good condition. Remove under controlled conditions by a Class A contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | F13 | Science Theatre | G | G16 | Stage Left | Flue | Insulation (beneath metal sheet covering but localised exposed insulation) | Removed: Positive (amosite) | - | - | - | Item Removed. Refer to Risktech Compliance Asbestos Clearance Certificate dated 26 August 2019. | Yes |
KENC | Kensington Campus | F21 | Library | 2 | - | Old Northern Building Section, Eastern Shaft Openings (North, South & Centre) | On Soffit, Top of Ductwork & Adjacent Surfaces | Insulation Residue & Debris | Removed - Assumed Positive | - | - | - | Item Removed: Refer to RiskTech Clearance Certificate dated 25 March 2019. | Yes |
KENC | Kensington Campus | F21 | Library | 2 | - | Old Northern Building Section, | On Soffit & Adjacent Surfaces | Insulation Residue & Debris | Positive (Amosite) - Removed | - | - | - | Item Removed: Refer to RiskTech Clearance Certificate dated 11 February 2019. | Yes |
KENC | Kensington Campus | F21 | Library | 3 | - | Old Northern Building Section, Eastern Shaft Openings (North, South & Centre) | On Soffit, Top of Ductwork & Adjacent Surfaces | Insulation Residue & Debris | Removed - Assumed Positive | - | - | - | Item Removed: Refer to RiskTech Clearance Certificate dated 18 March 2019. | Yes |
KENC | Kensington Campus | F21 | Library | 3 | - | Old Northern Building Section, | On Soffit & Adjacent Surfaces | Insulation Residue & Debris | Positive (Amosite) - Removed | - | - | - | Item Removed: Refer to RiskTech Clearance Certificate dated 11 February 2019. | Yes |
KENC | Kensington Campus | F21 | Library | 4 | - | Old Northern Building Section, Western Shaft Openings (North, South & Centre) | On Soffit, Top of Ductwork & Adjacent Surfaces | Insulation Residue & Debris | Removed - Positive (amosite) | - | - | - | Item Removed: Refer to RiskTech Clearance Certificate dated 11 March 2019. | Yes |
KENC | Kensington Campus | F21 | Library | 4 | - | Old Northern Building Section, Eastern Shaft Openings (North, Centre & South) | On Soffit & Adjacent Surfaces | Insulation Residue & Debris | Removed - Assumed Positive | - | - | - | Item Removed: Refer to RiskTech Compliance Clearance Certificate dated 2 December 2020. | Yes |
Kenc | Kensington Campus | C6 | International House | G | G28 | Accommodation Room | Fire Door | Insulation Core | Removed Positive (amosite) | - | - | - | Item Removed: Refer to Asbestos Clearance Certificate - RiskTech dated 05 December 2018 | Yes |
Kenc | Kensington Campus | C6 | International House | G | G29 | Accommodation Room | Fire Door | Insulation Core | Removed - Positive (amosite) | - | - | - | Item Removed: Refer to Asbestos Clearance Certificate - RiskTech dated 05 December 2018 | Yes |
Kenc | Kensington Campus | C6 | International House | G | G30 | Accommodation Room | Fire Door | Insulation Core | Removed - Positive (amosite) | - | - | - | Item Removed: Refer to Asbestos Clearance Certificate - RiskTech dated 05 December 2018 | Yes |
Kenc | Kensington Campus | C6 | International House | 2 | 219 | Accommodation Room | Fire Panels Above Fire Door | Insulation Core | Positive (Amosite) - Removed | - | - | - | Item Removed: Refer to Clearance Certificate - RiskTech dated 05 December 2018 | Yes |
Kenc | Kensington Campus | C6 | International House | 2 | 220 | Accommodation Room | Fire Door | Insulation Core | Positive (Amosite) - Removed | - | - | - | Item Removed: Refer to Clearance Certificate - RiskTech dated 05 December 2018 | Yes |
Kenc | Kensington Campus | C6 | International House | 1 | 152 | Accommodation Room | Fire Door | Insulation Core | Positive (Amosite) - Removed | - | - | - | Item Removed: Refer to Clearance Certificate - RiskTech dated 05 December 2018 | Yes |
Kenc | Kensington Campus | C6 | International House | 1 | 120 | Accommodation Room | Fire Door | Insulation Core | Positive (Amosite) - Removed | - | - | - | Item Removed: Refer to Clearance Certificate - RiskTech dated 05 December 2018 | Yes |
Kenc | Kensington Campus | C6 | International House | 3 | 320 | Accommodation Room | Fire Panels Above Fire Door | Insulation Core | Positive (Amosite) - Removed | - | - | - | Item Removed: Refer to Clearance Certificate - RiskTech dated 05 December 2018 | Yes |
KENC | Kensington Campus | K17 | Building K17 | 1 | 1Q02 | Pipe Work Riser Adjacent Room 110A (Toilets), Top of Block Work Walls | Packing Material | Insulation | Positive (Amosite) - Removed | - | - | - | Item removed 30/3/2019 by Pure Contracting - RiskTech Clearance Certifcate dated 1/4/2019 | Yes |
KENC | Kensington Campus | F21 | Library | 1 | 107 | South of Fire Stair (1Q1) | On Soffit Adjacent Column (brick header wall section removed) | Insulation | Removed - Positive (amosite) | - | - | - | Item Removed: Refer to RiskTech Clearance Certificate dated 17 February 2019. | Yes |
KENC | Kensington Campus | F20 | Goodsell | LG | MLG Q02 | Service Tunnel off Room LG5 | Pipework | Insulation | Positive (Amosite) - Removed | - | - | - | Item Removed: Refer to RiskTech Clearance Certificate dated 15 April 2019. | Yes |
KENC | Kensington Campus | F21 | Library | 1 | 130A | Plant Room, Inside AHU No.5, Base of Return Air Shaft Duct | On Duct | Fibrous Insulation Debris | Removed - Positive (amosite) | - | - | - | Item Removed: Refer to RiskTech Clearance Certificate dated 25 February 2019. | Yes |
KENC | Kensington Campus | F21 | Library | 1 | 130A | Plant Room, Inside AHU No.5, Pre-Filter Area | On Filter Bags | Fibrous Insulation Debris | Removed - Positive (amosite) | - | - | - | Item Removed: Refer to RiskTech Clearance Certificate dated 25 February 2019. | Yes |
Kenc | Kensington Campus | C6 | International House | G | G19 | Accommodation Room | Fire Door | Insulation Core | Removed - Positive (amosite) | - | - | - | Item Removed: Refer to Asbestos Clearance Certificate - RiskTech dated 05 December 2018 | Yes |
Kenc | Kensington Campus | C6 | International House | 2 | 219 | Accommodation Room | Fire Door | Insulation Core | Positive (Amosite) - Removed | - | - | - | Item Removed: Refer to Clearance Certificate - RiskTech dated 05 December 2018 | Yes |
Kenc | Kensington Campus | C6 | International House | G | G30 | Accommodation Room | Fire Panels Above Fire Door | Insulation Core | Removed - Positive (amosite) | - | - | - | Item Removed: Refer to Asbestos Clearance Certificate - RiskTech dated 05 December 2018 | Yes |
Kenc | Kensington Campus | C6 | International House | G | G29 | Accommodation Room | Fire Panels Above Fire Door | Insulation Core | Removed - Positive (amosite) | - | - | - | Item Removed: Refer to Asbestos Clearance Certificate - RiskTech dated 05 December 2018 | Yes |
Kenc | Kensington Campus | C6 | International House | 3 | 319 | Accommodation Room | Fire Panels Above Fire Door | Insulation Core | Positive (Amosite) - Removed | - | - | - | Item Removed: Refer to Clearance Certificate - RiskTech dated 05 December 2018 | Yes |
Kenc | Kensington Campus | C6 | International House | 2 | 220 | Accommodation Room | Fire Panels Above Fire Door | Insulation Core | Positive (Amosite) - Removed | - | - | - | Item Removed: Refer to Clearance Certificate - RiskTech dated 05 December 2018 | Yes |
Kenc | Kensington Campus | C6 | International House | 1 | 119 | Accommodation Room | Fire Panels Above Fire Door | Insulation Core | Positive (Amosite) - Removed | - | - | - | Item Removed: Refer to Clearance Certificate - RiskTech dated 05 December 2018 | Yes |
Kenc | Kensington Campus | C6 | International House | G | G28 | Accommodation Room | Fire Panels Above Fire Door | Insulation Core | Removed - Positive (amosite) | - | - | - | Item Removed: Refer to Asbestos Clearance Certificate - RiskTech dated 05 December 2018 | Yes |
Kenc | Kensington Campus | C6 | International House | G | G18 | Accommodation Room | Fire Panels Above Fire Door | Insulation Core | Removed - Positive (amosite) | - | - | - | Item Removed: Refer to Asbestos Clearance Certificate - RiskTech dated 05 December 2018 | Yes |
KENC | Kensington Campus | F21 | Library | 14 | 1402 | Western Perimeter Wall Cavity, Behind Plasterboard Wall Lining | Sliding Fire Door ('Fire Control Pty Ltd' – Manufactured in 1974’) | Core Insulation | Positive (amosite) | Friable | Low | P3 | Maintain in good condition. Remove under controlled conditions by a Class A contractor prior to demolition or refurbishment. | No |
Kenc | Kensington Campus | C6 | International House | G | GQ3 | North Corridor, Adjacent Fire Stairs GQ2 | Fire Door | Insulation Core | Removed - Positive (amosite) | - | - | - | - | Yes |
Kenc | Kensington Campus | C6 | International House | 3 | 319 | Accommodation Room | Fire Door | Insulation Core | Positive (Amosite) - Removed | - | - | - | Item Removed: Refer to Clearance Certificate - RiskTech dated 05 December 2018 | Yes |
Kenc | Kensington Campus | C6 | International House | 3 | 320 | Accommodation Room | Fire Door | Insulation Core | Positive (Amosite) - Removed | - | - | - | Item Removed: Refer to Clearance Certificate - RiskTech dated 05 December 2018 | Yes |
Kenc | Kensington Campus | C6 | International House | 1 | 151 | Accommodation Room | Fire Door | Insulation Core | Positive (Amosite) - Removed | - | - | - | Item Removed: Refer to Clearance Certificate - RiskTech dated 05 December 2018 | Yes |
Kenc | Kensington Campus | C6 | International House | 1 | 119 | Accommodation Room | Fire Door | Insulation Core | Positive (Amosite) - Removed | - | - | - | Item Removed: Refer to Clearance Certificate - RiskTech dated 05 December 2018 | Yes |
Kenc | Kensington Campus | C6 | International House | G | GQ21 | Fire Stairs | Fire Door (tag 'Padde Fire Control 1972') | Insulation Core | Removed - Positive (amosite) | - | - | - | Item Removed: No removal/clearance documentation was provided | Yes |
Kenc | Kensington Campus | C6 | International House | 3 | 3Q2 | Fire Stairs | Fire Door (tag 'Advanced Metal Door Frames, 2015') | Insulation Core | Positive (Amosite) - Removed | - | - | - | Item Removed: No removal/clearance documentation was provided | Yes |
Kenc | Kensington Campus | C6 | International House | 3 | 3Q6 | Fire Stairs | Fire Doors (tag 'Padde Fire Control 1972') | Insulation Core | Positive (Amosite) - Removed | - | - | - | Item Removed: No removal/clearance documentation was provided | Yes |
Kenc | Kensington Campus | C6 | International House | 3 | 303 | Accommodation Room | Fire Door (tag 'Advanced Metal Door Frames, 2015') | Insulation Core | Positive (Amosite) - Removed | - | - | - | Item Removed: No removal/clearance documentation was provided | Yes |
Kenc | Kensington Campus | C6 | International House | 3 | 3Q11 | Fire Stairs | Fire Door (tag 'Advanced Metal Door Frames, 2015') | Insulation Core | Positive (Amosite) - Removed | - | - | - | Item Removed: No removal/clearance documentation was provided | Yes |
Kenc | Kensington Campus | C6 | International House | 2 | 2Q11 | Fire Stairs | Fire Door (tag 'Advanced Metal Door Frames, 2015') | Insulation Core | Positive (Amosite) - Removed | - | - | - | Item Removed: No removal/clearance documentation was provided | Yes |
Kenc | Kensington Campus | C6 | International House | 2 | 2Q6 | Fire Stairs | Fire Doors (tag 'Padde Fire Control 1972') | Insulation Core | Positive (Amosite) - Removed | - | - | - | Item Removed: No removal/clearance documentation was provided | Yes |
Kenc | Kensington Campus | C6 | International House | 1 | 1Q13 | Fire Stairs | Fire Door (tag 'Advanced Metal Door Frames, 2015') | Insulation Core | Positive (Amosite) - Removed | - | - | - | Item Removed: No removal/clearance documentation was provided | Yes |
Kenc | Kensington Campus | C6 | International House | 1 | 1Q11 | Fire Stairs | Fire Door (tag 'Padde Fire Control 1972') | Insulation Core | Positive (Amosite) - Removed | - | - | - | Item Removed: No removal/clearance documentation was provided | Yes |
Kenc | Kensington Campus | C6 | International House | 1 | 1Q5 | Fire Stairs | Fire Doors (tag 'Padde Fire Control 1972') | Insulation Core | Positive (Amosite) - Removed | - | - | - | Item Removed: No removal/clearance documentation was provided | Yes |
Kenc | Kensington Campus | C6 | International House | G | GQ22 | North Corridor, East End | Fire Door | Insulation Core | Removed - Positive (amosite) | - | - | - | Item Removed: Refer to Asbestos Clearance Certificate - RiskTech dated 05 December 2018 | Yes |
Kenc | Kensington Campus | C6 | International House | G | GQ15 | South Corridor to G84 | Fire Door (tag 'Advanced Metal Door Frames, 2015') | Insulation Core | Removed - Positive (amosite) | - | - | - | Item Removed: No removal/clearance documentation was provided | Yes |
KENC | Kensington Campus | F21 | Library | 1 | 1Q9 | Corridor (Outside Room 127), Localised Areas | On Top of Brick Wall & Ductwork | Insulation Debris | Removed - Positive (amosite) | - | - | - | Item Removed: Refer to RiskTech Clearance Certificate dated 17 February 2019. | Yes |
KENE | Kensington Environs | AS24 | 24 Arthur Street | G | Ceiling Space, Throughout | Pipework Lagging | Insulation | Positive (Amosite) - Removed | - | - | - | No removal/clearance documentation was provided. | Yes | |
KENE | Kensington Environs | AS24 | 24 Arthur Street | G | - | Ceiling Space, Adjacent Ceiling Access Panel | Pipework Lagging | Insulation | Positive (Amosite) - Removed | - | - | - | No removal/clearance documentation was provided. | Yes |
Kenc | Kensington Campus | C6 | International House | 1 | 196 | Female Amenities / Toilets - Plumbing Riser | Hot Water Pipework | Insulation | Positive (Amosite) - Removed | - | - | - | Item Removed: No removal/clearance documentation was provided | Yes |
Kenc | Kensington Campus | C6 | International House | 1 | 199 | Male Amenities / Toilets - Plumbing Riser | Hot Water Pipework | Insulation | Removed - Positive (amosite) | - | - | - | Item Removed: No removal/clearance documentation was provided | Yes |
Kenc | Kensington Campus | C6 | International House | 2 | 296 | Female Amenities / Toilets - Plumbing Riser | Hot Water Pipework | Insulation | Positive (Amosite) - Removed | - | - | - | Item Removed: No removal/clearance documentation was provided | Yes |
Kenc | Kensington Campus | C6 | International House | 2 | 299 | Male Amenities / Toilets - Plumbing Riser | Hot Water Pipework | Insulation | Positive (Amosite) - Removed | - | - | - | Item Removed: No removal/clearance documentation was provided | Yes |
Kenc | Kensington Campus | C6 | International House | 3 | 396 | Female Amenities / Toilets - Plumbing Riser | Hot Water Pipework | Insulation | Positive (Amosite) - Removed | - | - | - | Item Removed: No removal/clearance documentation was provided | Yes |
Kenc | Kensington Campus | C6 | International House | 3 | 399 | Male Amenities / Toilets - Plumbing Riser | Hot Water Pipework | Insulation | Positive (Amosite) - Removed | - | - | - | Item Removed: No removal/clearance documentation was provided | Yes |
Kenc | Kensington Campus | C6 | International House | 1 | 120 | Accommodation Room | Fire Panels Above Fire Door | Insulation Core | Positive (Amosite) - Removed | - | - | - | Item Removed: Refer to Clearance Certificate - RiskTech dated 05 December 2018 | Yes |
Kenc | Kensington Campus | C6 | International House | G | G94 | Plumbing Riser | Hot Water Pipework | Insulation | Removed - Positive (amosite) | - | - | - | Item Removed: No removal/clearance documentation was provided | Yes |
Kenc | Kensington Campus | C6 | International House | G | G95 | Office - Ceiling Space | Hot Water Pipework | Insulation | Removed - Positive (amosite) | - | - | - | Item Removed: No removal/clearance documentation was provided | Yes |
Kenc | Kensington Campus | C6 | International House | G | G97 | Office - Ceiling Space | Hot Water Pipework | Insulation | Removed - Positive (amosite) | - | - | - | Item Removed: No removal/clearance documentation was provided | Yes |
Kenc | Kensington Campus | D26 | Bio Sciences North | 1 | 130 | Biolink | Fire Door | Insulation Core | Positive - Removed | - | - | - | Item Removed: No removal / clearance documentation provided. (Note: New fire door tagged 'Bismac 2006'). | Yes |
FSW | Wellington Field Station | WFS1 | Wellington Field Station Cottage | G | 1 | Main Residence, Exterior, All Sides | Eaves & Awning Ceiling | Fibre Cement Sheeting | Positive (Amosite, Chrysotile and Crocidolite) | Non-friable | Low | P3 | Repair/seal the localised damage areas and secure loose sheeting under controlled conditions within a planned control program. Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment works. | No |
CCS | Cliffbrook Campus | CC1 | Cliffbrook House | G | - | Exterior, North-East | Cable Conduit | Moulded Fibre Cement | Positive (Amosite, Chrysotile and Crocidolite) | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | B15 | Old Tote | 01 | - | Exterior, West Above Main Entrance | Wall Cladding | Fibre Cement Sheeting | Positive - Removed | - | - | - | Item Removed: Refer to RiskTech Clearance Certificate dated 16th December | Yes |
KENC | Kensington Campus | B14D | Fig Tree Theatre | G | - | Exterior, North Side, under Roof Edge | Fascia Panelling | Fibre Cement Sheeting | Positive (Amosite, Chrysotile and Crocidolite) | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
MISC | Miscellaneous | BC34 | Woolley House | 04 | - | Sub-Floor Space off Room G09 (Bed 3), Adjacent Hot Water Heater Unit | On Ground | Fibre Cement Sheet Debris | Positive (Amosite, Chrysotile and Crocidolite) | Non-friable | Low | P3 | Restrict access to the sub-floor space to authorised persons only. Remove debris under controlled conditions by a Class A/B contractor or competent person within a planned control programs. | No |
MISC | Miscellaneous | BC34 | Woolley House | 04 | - | Sub-Floor Space off Room G09 (Bed 3), Adjacent Hot Water Heater Unit | On Ground | Insulation Board Debris | Positive (Amosite, Chrysotile and Crocidolite) | Friable | Med | P2 | Restrict access to the sub-floor space to authorised persons only. Remove debris under controlled conditions by a Class A contractor as soon as practicable. | No |
KENC | Kensington Campus | D14 | UNSW Hall | G | EAGQ01 | GQ14 Corridor, Electrical Cupboard (DB-1) | Conduit | Moulded Fibre Cement | Positive (Amosite, Chrysotile and Crocidolite) | - | - | - | Item removed. Refer Airsafe clearance cert dated 7/2/2023 | Yes |
KENC | Kensington Campus | D14 | UNSW Hall | G | BG95 | Main Switch Room, South-East Corner | Electrical Conduits | Moulded Fibre Cement | Positive (Amosite, Chrysotile and Crocidolite) | - | - | - | Item removed. Refer Airsafe clearance cert dated 7/2/2023 | Yes |
Kenc | Kensington Campus | D26 | Bio Sciences North | 1 | 1Q12 | Biolink | Ceiling Tiles | Fibre Cement Sheeting | Positive - Removed | - | - | - | Item Removed: No removal / clearance documentation provided. | Yes |
KENE | Kensington Environs | BS30 | 30 Botany Street | 1 | 102 | Bathroom | Ceiling | Fibre Cement Sheeting | Positive (Amosite, Chrysotile and Crocidolite) | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENE | Kensington Environs | AS20 | 20 Arthur Street | G | - | Exterior, Garage, Surrounding | Eaves | Fibre Cement Sheeting | Positive (Amosite, Chrysotile and Crocidolite) | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment works. | No |
KENE | Kensington Environs | AS20 | 20 Arthur Street | G | - | Exterior, Garage | Wall Cladding | Fibre Cement Sheeting | Positive (Amosite, Chrysotile and Crocidolite) | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment works. | No |
KENE | Kensington Environs | AS10 | 10 Arthur Street | G | G08 | Shower Cubicle | Wall | Fibre Cement Sheeting | Positive (Amosite, Chrysotile and Crocidolite) | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment works. | No |
KENC | Kensington Campus | SST1 | Main Service Tunnel | G | - | Service Tunnel below Building G14 (Access provided through Branch F13) | Electrical Conduit | Fibre Cement | Positive (Chrysotile and Crocidolite) | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | F21 | Library | 1 | 1Q23 | Service Tunnel, East End, North Wall | Conduits | Moulded Fibre Cement Pipes | Positive (chrysotile & crocidolite) | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | B14D | Fig Tree Theatre | G | - | Exterior, North East, Entrance | Wall Cladding Around Doorway | Fibre Cement Sheeting | Positive (Chrysotile and Crocidolite) | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
Kenc | Kensington Campus | D26 | Bio Sciences North | 1 | 137 | Biolink | Walls | Fibre Cement Sheeting | Positive - Removed | - | - | - | Item Removed: No removal / clearance documentation provided. | Yes |
KENE | Kensington Environs | WR41 | 41 Wansey Road | LG | - | Exterior, Backyard, North-East, to Neighbouring Property Shed | Wall | Fibre Cement Sheeting | Positive (Chrysotile and Crocidolite) | Non-friable | Low | P3 | Repair/seal localised damage under controlled conditions. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment works. | No |
KENE | Kensington Environs | AS10 | 10 Arthur Street | G | GQ4 | Exterior, Garage, South | Gable End | Fibre Cement Sheeting | Positive (Chrysotile and Crocidolite) | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment works. | No |
KENC | Kensington Campus | SST1 | Main Service Tunnel | G | - | North Wall Adjacent Entrance to F12 Branch | Gas Pipe Work Flange Joints | Gaskets | Positive (Chrysotile) | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
Kenc | Kensington Campus | D26 | Bio Sciences North | 1 | 144 | Biolink | Fire Door | Insulation Core | Positive - Removed | - | - | - | Item Removed: No removal / clearance documentation provided. | Yes |
FSSL | Smiths Lake Field Station | SL6 | Smiths Lake COLA | G | - | Exterior, East | Inside Electrical Cabinet | Electrical Backing Board | Positive (Chrysotile) | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment works. | No |
Kenc | Kensington Campus | D26 | Bio Sciences North | 5 | 535 | Biosciences North | Fire Door | Insulation Core | Positive - Removed | - | - | - | Item Removed: No removal / clearance documentation provided. | Yes |
KENC | Kensington Campus | N8 | House at Pooh Corner | G | G7 | Electrical Cupboard | Conduit | Moulded Fibre Cement Pipe | Positive (Chrysotile) | Non-friable | Low | P4 | Maintain in good condition. Confirm status and if contains asbestos, remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | K17 | Building K17 | 6 | 6Q01 | Communications Riser | Debris | Loose Insulation | Removed | - | - | - | Item removed. Refer RiskTech Clearance Certificate 20210616 | Yes |
KENC | Kensington Campus | K17 | Building K17 | 7 | 706 | Roof Area, South, Electrical Box | Inside Electrical Cabinet | Electrical Backing Board | Positive (Chrysotile) | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | K17 | Building K17 | 7 | 702 | Throughout | Ductwork Joints | Mastic Sealant | Positive (Chrysotile) | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
Kenc | Kensington Campus | D26 | Bio Sciences North | 5 | 541 | Biosciences North | Fire Door | Insulation Core | Positive - Removed | - | - | - | Item Removed: No removal / clearance documentation provided. | Yes |
Kenc | Kensington Campus | J14 | Keith Burrows Theatre | G | - | Exterior, North Side | Window Frames (between frame and pane) | Mastic Sealant | Positive (chrysotile) | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | J12 | Newton | G | G12 | Stairwell to Mezzanine Level (Room GM6A & GM6B) | Wall Lining | Fibre Cement Sheeting | Positive (Chrysotile) | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | J12 | Newton | G | G12 | Mezzanine Area (Room GM6A & GM6B) | Wall Lining | Fibre Cement Sheeting | Positive (Chrysotile) | Non-friable | Low | P3 | Remove fibre cement sheet south upper wall section in Room GM6A under controlled conditions by a Class A/B contractor as part of a program of works or prior to demolition or refurbishment. | No |
KENC | Kensington Campus | J12 | Newton | R | R02 | Plant Room | Duct Work Joints | Mastic Sealant | Positive (Chrysotile) | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | J12 | Newton | G | G03 | Exterior, East Side of Building, Entrance to Electrical Switch Room | Wall Expansion Joints Around Door Frame | Mastic Sealant | Positive (Chrysotile) | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENE | Kensington Environs | HS46 | 46 High Street | 01 | - | South-East Entry Stairs | Vertical Expansion Joint Between Brickwork & Concrete Section | Mastic Sealant | Positive (Chrysotile) | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
Kenc | Kensington Campus | D26 | Bio Sciences North | 5 | 533 | Biosciences North | Walls | Fibre Cement Sheeting | Positive - Removed | - | - | - | Item Removed: No removal / clearance documentation provided. | Yes |
Kenc | Kensington Campus | D26 | Bio Sciences North | 3 | 301 | Biosciences North | Fume Cupboard, Internal Lining | Fibre Cement Sheeting | Positive - Removed | - | - | - | Item Removed: No removal / clearance documentation provided. | Yes |
KENC | Kensington Campus | H20 | Civil Engineering | 2 | 210B | Store Room (Formerley a Cool Room), East Wall | Duct Heater Bank | Millboard | Positive (Chrysotile) | Friable | Low | P3 | Maintain in good condition. Remove under controlled conditions by a Class A contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | H20 | Civil Engineering | 8 | RQ01 | Concrete Plinths, Beneath Metal Capping | Floor Covering | Bituminous Membrane | Positive (Chrysotile) | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
FSW | Wellington Field Station | WFS1 | Wellington Field Station Cottage | G | 1 | Main Residence, Exterior, West Side | Inside Electrical Cabinet | Electrical Backing Board | Positive (Chrysotile) | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment works. | No |
FSH | Hay Field Station | HFS8 | Hay Field Station Managers Office | G | - | Exterior, Sub-Floor Space | On Ground, Debris | Fibre Cement Sheeting | Positive (Chrysotile) | Non-friable | Low | P3 | Restrict access to the sub-floor space area to authorised personnel only. Remove fibre cement sheet debris under controlled conditions within a planned control program. | No |
KENC | Kensington Campus | F23 | Mathews Building | 17 | 1704 | Cooling Tower Room | Floor & Support Structures | Bituminous Membrane (beneath new non-asbestos membrane) | Removed - Positive (chrysotile) | - | - | - | Item Removed: Refer to RiskTech Compliance Clearance Certificate dated 2 December 2019. Removed by Pure Contracting. | Yes |
KENC | Kensington Campus | F23 | Mathews Building | 1 | M1Q04 | Service Tunnel Access off Room 116, East End | Inside Electrical Cabinet | Electrical Backing Board | Positive (chrysotile) | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | F23 | Mathews Building | 1 | M1Q04 | Service Tunnel Access off Room 116, East End, East & South Walls | Conduits | Moulded Fibre Cement Pipes | Positive (chrysotile) | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | F23 | Mathews Building | 3 | 313 | Between East Wall & Perimeter South Wall | Expansion Joint | Sealant Mastic | Positive (Chrysotile) - removed | - | - | - | Item removed. Refer Airsafe clearance cert dated 13-17/10/23 | Yes |
KENC | Kensington Campus | F23 | Mathews Building | 12 | 1228 | - | Fire Panel Above Door | Core Insulation | Removed - Assumed Positive (amosite) | - | - | - | Item Removed: Refer to RiskTech Compliance Clearance Certificate dated 1 May 2020. | Yes |
KENC | Kensington Campus | F23 | Mathews Building | 5 | 5Q5 | Plant Room (access via Fire Stairs 4Q7) | Ductwork Flange Joins | Sealant Mastic | Positive (chrysotile) | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | F21 | Library | 10 | 10Q8 | Duct (Shaft) off SW Fire Stairs, North | Ducwork Flange Joins | Mastic Sealant | Positive (chrysotile) | Non-friable | Low | P3 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | F21 | Library | 1 | 1Q12 | Electrical Room off Fire Stairs (1Q2) | On Soffit Surrounding Column | Insulation Residue & Bituminous Coating (adhesive) | Removed -Positive (chrysotile) | - | - | - | Item Removed: Refer to RiskTech Clearance Certificate dated 25 May 2000. | Yes |
KENC | Kensington Campus | F21 | Library | LG | LGQ05 | Plant Room - Air Handling Unit | Air Handling Unit, Panel Joins | Mastic Sealant | Positive (chrysotile) | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | Yes |
KENC | Kensington Campus | F21 | Library | 15 | 1501 | Plant Room | Toilet Exhaust Ductwork, Joints & Joins | Mastic Sealant | Positive (chrysotile) | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | F20 | Goodsell | G | GQ6A | Electrical Cupboard Adjacent Room G24A Toilets | - | Electrical Backing Board | Positive (Chrysotile) | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | F20 | Goodsell | G | - | Exterior, East Side, North East Corner, Outside Room G2A, Covered Exit | Awning Roof | Bituminous Membrane | Positive (Chrysotile) | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | F20 | Goodsell | 02 | 221 | South Side, Below Window | Vertical Expansion Wall Joint | Sealant Mastic | Positive (Chrysotile) | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | F17 | Rex Vowels Theatre | 1 | LGQ5 | Plant Room, Level 1 | Duct Work Joints | Mastic Sealant | Positive - removed | Item removed. Refer RiskTech clearance cert dated Dec 23 | Yes | |||
KENC | Kensington Campus | F13 | Science Theatre | G | - | Exterior, Eastern Façade | Window Frames (between frame & pane) | Mastic Sealant | Positive (chrysotile) | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | F13 | Science Theatre | G | G11 | East | Window Frames (between frame & pane) | Mastic Sealant | Positive (Chrysotile) | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | F13 | Science Theatre | G | G07 | Electrical Cupboard | Floor | Fibre Cement Sheeting | Positive (Chrysotile) | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | F10 | Chemical Sciences | 1 | - | Exterior, Façade | Windows (between frame and façade wall) | Mastic Sealant | Positive (Chrysotile) | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | F10 | Chemical Sciences | 3 | - | Exterior, Façade (access via room 318) | Windows (between frame and façade wall) | Mastic Sealant | Positive (Chrysotile) | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
Kenc | Kensington Campus | D26 | Bio Sciences North | 3 | 301B | Biosciences North | Fume Cupboard, Internal Lining | Fibre Cement Sheeting | Positive - Removed | - | - | - | Item Removed: No removal / clearance documentation provided. | Yes |
Kenc | Kensington Campus | D26 | Bio Sciences North | 4 | 416 | Biosciences North | Fume Cupboard, Internal Lining | Fibre Cement Sheeting | Positive - Removed | - | - | - | Item Removed: No removal / clearance documentation provided. | Yes |
Kenc | Kensington Campus | D26 | Bio Sciences North | 5 | 510 | Biosciences North | Fume Cupboard, Internal Lining | Fibre Cement Sheeting | Positive - Removed | - | - | - | Item Removed: No removal / clearance documentation provided. | Yes |
KENC | Kensington Campus | D23 | Mathews Theatres | 01 | - | Exterior, West Side | Expansion Joint between Brickwork Wall Sections | Mastic Sealant | Positive (chrysotile) | Non-Friable | Low | P4 | Maintain in good condition. Remove under controlled conditions prior to demolition or refurbishment. | No |
KENC | Kensington Campus | D23 | Mathews Theatres | 01 | 101 | Ductwork Service Risers | Ductwork Joins | Mastic Sealant (red colour) | Positive (chrysotile) | Non-Friable | Low | P4 | Maintain in good condition. Remove under controlled conditions prior to demolition or refurbishment. | No |
KENC | Kensington Campus | D23 | Mathews Theatres | 01 | 101 | Ductwork Service Risers | Ductwork Flange Joints | Mastic Sealant (black colour) | Positive (chrysotile) | Non-Friable | Low | P4 | Maintain in good condition. Remove under controlled conditions prior to demolition or refurbishment. | No |
KENC | Kensington Campus | D14 | UNSW Hall | G | FAGQ01 | GQ14 Corridor, North Fire Hydrant Cupboard, Ceiling Height | Loose Penetration Cover | Fibre Cement Sheeting | Positive (Chrysotile) | - | - | - | Item removed. Refer Airsafe clearance cert dated 7/2/2023 | Yes |
Kenc | Kensington Campus | D14 | UNSW Hall | G | A90 | Exterior, East | Window Frames (between frame and pane) | Mastic Sealant | Positive (Chrysotile) | - | - | - | Item removed. Refer Airsafe clearance cert dated 7/2/2023 | Yes |
Kenc | Kensington Campus | D26 | Bio Sciences North | 3 | 301A | Biosciences North | Walls | Fibre Cement Sheeting | Positive - Removed | - | - | - | Item Removed: No removal / clearance documentation provided. | Yes |
Kenc | Kensington Campus | D26 | Bio Sciences North | 5 | 5Q7 | Fire Hose Reel Cupboard, | Wall | Fibre Cement Sheeting | Positive (Amosite & Chrysotile) | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
Kenc | Kensington Campus | D26 | Bio Sciences North | 1 | 131A | Biolink, | Walls | Fibre Cement Sheeting | Removed | - | - | - | Item removed. Refer RiskTech Clearance cert dated 28/09/2021 | Yes |
Kenc | Kensington Campus | G15 | Robert Webster Theatres | 02 | 290A | Lecture Theatre B, East Side Projector Room, Roof Space | Ductwork Joints & Joins | Mastic Sealant (black colour) | Positive (chrysotile) | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
Kenc | Kensington Campus | D26 | Bio Sciences North | 3 | 352 | Biolink, | Walls | Fibre Cement Sheeting | Positive (Amosite & Chrysotile) - removed | - | - | - | Item removed. Refer Risktech Clearance Cert dated 17th November 2021 | Yes |
Kenc | Kensington Campus | D16 | Goldstein Hall | G | GQ13 | Main Switch Room | Electrical Distribution Board Cabinet | Electrical Backing Board | Positive (chrysotile) | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to refurbishment. | No |
Kenc | Kensington Campus | C24 | Clancy Auditorium | G | G4B | Female Toilet, Riser | Ductwork Joints & Joins | Mastic Sealant (red colour) | Positive (chrysotile) | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
Kenc | Kensington Campus | C24 | Clancy Auditorium | LG | LG1 | Air Handling Unit | Joins | Mastic Sealant | Positive (chrysotile) | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
Kenc | Kensington Campus | C24 | Clancy Auditorium | 01 | - | Roof Space | Old Ductwork Joins | Mastic Sealant (white colour) | Positive (chrysotile) | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | C20 | Morven Brown | G | - | Exterior, Eastern Side of Building, Southern End | Window Sill Expansion Joint | Mastic Sealant | Positive (Chrysotile) | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | C20 | Morven Brown | LG | - | Exterior, West Side of Building | Wall Expansion Joint | Mastic Sealant | Positive (Chrysotile) | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | C20 | Morven Brown | LG | - | Exterior, North-West Corner of Building | Window Sill Expansion Joint | Mastic Sealant | Positive (Chrysotile) | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | K15 | Old Main | 02 | 2Q24 | Exterior, South | Windows (between frame and pane) | Mastic Sealant | Positive (chrysotile) | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment | No |
KENC | Kensington Campus | F23 | Mathews Building | 5 | 5Q17 | South Roof Section (beneath concrete plinths supporting plant & equipment) | Roof | Bituminous Membrane | Positive (chrysotile) | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | F21 | Library | 11 | - | Roof Above Lounge (roof above former Room 1111, 1113, 1114 & 1115 and Covered Terrace) | Roof Covering (beneath new membrane) | Bituminous Membrane | Removed - Positive (Chrysotile) | - | - | - | Item Removed: Refer to RiskTech Compliance Clearance Certificate dated 21 October 2019. | yes |
KENC | Kensington Campus | F13 | Science Theatre | 2 | - | Throughout, Above Stage (G17, G18 & G19) & Auditorum (G9) and Roof Space | Former Roof Cladding (below new metal roof cladding & support structure) | Bituminous Felt Coated Metal Sheeting ('galbestos') | Positive (Chrysotile) | Non-friable | Low | P4 | Pure Contracting undertook set up works involving segregating of the work area, laying plastic sheeting beneath and adjacent to the covered walkway and installing warning signage. The removal of the asbestos containing membrane was undertaken using hand tools and hammer drills fitted with lifting blades, where necessary. Following the removal works, the work area was cleaned with Type H HEPA vacuum cleaners and wet wiping methods. Asbestos waste was placed in labelled 200 μm asbestos waste bags and then transported from site. | Yes |
KENC | Kensington Campus | F13 | Science Theatre | G | G16 | Stage Left | Ceiling | Fibre Cement Sheeting | Positive (chrysotile) | Non-friable | Low | P3 | Consider sealing the edges of the ceiling sheets under controlled conditions by a Class A/B contractor as part of a planned control program. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
MISC | Miscellaneous | BC34 | Woolley House | 02 | UGQ02 | Exterior, Level 2, Deck, Common to Room G06 (Bed 1) | Windows (between glass & internal timber framework) | Caulking Mastic | Positive (Chrysotile) | Non-friable | Low | P3 | Repair or remove deteriorating window caulking under controlled conditions by a Class A/B contractor or competent person within a planned control programs. | No |
MISC | Miscellaneous | BC34 | Woolley House | 02 | G05 | Living (common to Deck UGQ02) | Windows (between glass & internal timber framework) | Caulking Mastic | Positive (Chrysotile) | Non-friable | Low | P3 | Repair or remove deteriorating window caulking under controlled conditions by a Class A/B contractor or competent person within a planned control programs. | No |
MISC | Miscellaneous | BC34 | Woolley House | 02 | G06 | Bed 1 | Windows (between glass & internal timber framework) | Caulking Mastic | Positive (Chrysotile) | Non-friable | Low | P3 | Repair or remove deteriorating window caulking under controlled conditions by a Class A/B contractor or competent person within a planned control programs. | No |
RANC | Randwick Campus | R1 | Randwick R1 | LG | - | Tunnel or Former Open Pit, Northern Section, East of Access Point (via floor manhole cover) | Stockpile Demolition Material | Fibre Cement Sheeting | Positive (chrysotile) | Non-Friable | Low | P3 | Restrict access to the tunnel (former pit) to authorised personnel. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | F23 | Mathews Building | 3 | - | Exterior, Façade, North Open Balcony | Vertical Joint Between Base of Metal Window Framework & Concrete Façade Panel | Sealant Mastic (dark grey colour) | Positive (chrysotile) | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | F23 | Mathews Building | 3 | - | Exterior, Façade, Covered Verandah U3Q02 | Horizontal Joint Between Base of Metal Window Framework & Concrete Façade Panel | Sealant Mastic (dark grey colour) | Positive (chrysotile) | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | F23 | Mathews Building | 14 | 1410 | North | Vertical Expansion Wall Joints | Sealant Mastic (grey colour) | Positive (chrysotile) | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | F23 | Mathews Building | 4 | - | Exterior, Façade, North, 2nd Bay from East Side | Vertical Joint (joint closest to window) Between Metal Window Framework & Column | Sealant Mastic (dark grey colour) | Positive (chrysotile) | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | F23 | Mathews Building | 4 | - | Exterior, Façade, North, 2nd Bay from East Side | Vertical Joint (joint closest to column) Between Metal Window Framework & Column | Sealant Mastic (dark grey colour) | Positive (chrysotile) | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | F23 | Mathews Building | 4 | - | Exterior, Façade, North, 2nd Bay from East Side | Horizontal Joint Between Base of Metal Window Framework & Concrete Façade Panel | Sealant Mastic (dark grey colour) | Positive (chrysotile) | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | F23 | Mathews Building | 6 | - | Exterior, Façade, South | Vertical Joint (joint closest to column) Between Metal Window Framework & Column | Caulking Sealant (grey colour) | Positive (chrysotile) | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | F23 | Mathews Building | 12 | 1219 | South | Between Lower Metal Window Framework & Glass | Sealant Mastic (grey & black colour) | Positive (chrysotile) | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | F23 | Mathews Building | 8 | 818 | South | Between Lower Metal Window Framework & Glass | Sealant Mastic (grey colour) | Positive (chrysotile) | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | F23 | Mathews Building | 14 | 1410 | North | Between Lower Metal Window Framework & Glass | Sealant Mastic (grey & black colour) | Positive (chrysotile) | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | F23 | Mathews Building | 15 | 1503 | North | Between Lower Metal Window Framework & Glass | Sealant Mastic (grey & black colour) | Positive (Chrysotile) | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | F23 | Mathews Building | 15 | 1512 | South | Between Lower Metal Window Framework & Glass | Sealant Mastic (grey & black colour) | Positive (chrysotile) | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | F23 | Mathews Building | 1 | - | Exterior, Façade, South, Far SE Corner | Vertical Joint Between Metal Window Framework & Concrete Façade Panel | Sealant Mastic (dark grey colour) | Positive (chrysotile) | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | F23 | Mathews Building | 1 | - | Exterior, Façade, East, Far SE Corner | Horizontal Joint Between Base of Metal Window Framework & Concrete Façade Panel | Sealant Mastic (dark grey colour) | Positive (chrysotile) | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | F23 | Mathews Building | 5 | - | Exterior, Façade, South | Vertical Joint (joint closest to column) Between Metal Window Framework & Column | Caulking Sealant (grey colour) | Positive (chrysotile) | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | F21 | Library | 11 | - | Roof Area, Exterior, Façade | Between Metal Window Framework & Glass | Mastic Sealant (dark grey/black colour) | Positive (chrysotile) | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | F23 | Mathews Building | 5 | - | Exterior, Façade, South | Vertical Joint (joint closest to window) Between Metal Window Framework & Column | Caulking Sealant (grey colour) | Positive (chrysotile) | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | F21 | Library | 1 | - | Exterior, Façade, Old Low Rise Northern Brick Section | Between Metal Window Framework & Glass | Caulking Mastic (brown colour) | Positive (chrysotile) | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | F23 | Mathews Building | 5 | - | Exterior, Façade, South | Between Lower Metal Window Framework & Glass | Caulking Sealant (grey colour) | Positive (chrysotile) | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | F21 | Library | 1 | - | Exterior, Façade, Tower Section, East (Section Adjoining Rear of Bank Building) | Vertical Joint Between Metal Window Framework & Concrete Façade Panel | Sealant Mastic (grey colour) | Positive (chrysotile) | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | F21 | Library | 1 | - | Exterior, Façade, Tower Section, East | Vertical Joint Between Brick Wall & Concrete Façade Panel | Sealant Mastic (grey colour) | Positive (chrysotile) | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | F23 | Mathews Building | 5 | - | Exterior, Façade, South | Between Lower Metal Window Framework & Glass | Sealant Mastic (dark grey colour) | Positive (chrysotile) | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | F21 | Library | 1 | - | Exterior, Façade, South Tower Section, South | Vertical Joint Between Concrete Façade Panel & Column | Sealant Mastic (grey colour) | Positive (chrysotile) | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | F21 | Library | 1 | - | Exterior, Façade, South Tower Section, South | Between Metal Window Framework & Glass | Mastic Sealant (dark grey/black colour) | Positive (chrysotile) | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | F21 | Library | 1 | - | Exterior, Façade, South Tower Section, South | Horizontal Joint Between Metal Window Framework & Concrete Façade Panel | Sealant Mastic (grey colour) | Positive (chrysotile) | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | F23 | Mathews Building | 1 | - | Exterior, Façade, South, Far SE Corner | Joint Between Metal Window Framework & Façade | Sealant Mastic (dark grey colour) | Positive (chrysotile) | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
Kenc | Kensington Campus | D26 | Bio Sciences North | 5 | 5Q7 | East & West | Walls | Fibre Cement Sheeting | Removed | - | - | - | Item removed. Refer Risktech clearance cert dated 02/02/2022 | Yes |
Kenc | Kensington Campus | D26 | Bio Sciences North | 5 | 5Q8 | South, East & West | Walls | Fibre Cement Sheeting | Removed | - | - | - | Item removed. Refer Risktech clearance cert dated 02/02/2022 | Yes |
Kenc | Kensington Campus | D26 | Bio Sciences North | 4 | 4Q6 | Biolink, | Walls | Fibre Cement Sheeting | Removed | - | - | - | Item removed. Refer Risktech clearance cert dated 17/12/21 | Yes |
Kenc | Kensington Campus | D26 | Bio Sciences North | 3 | 3Q6 | Biolink, | Walls | Fibre Cement Sheeting | Positive (Amosite & Chrysotile) - removed | - | - | - | Item removed. Refer Risktech Clearance cert dated 17/11/2021. | Yes |
Kenc | Kensington Campus | D26 | Bio Sciences North | 5 | 564 | North, South , East & West | Walls | Fibre Cement Sheeting | Removed | - | - | - | Item removed. Refer Risktech clearance cert dated 02/02/2022 | Yes |
Kenc | Kensington Campus | D26 | Bio Sciences North | 5 | 567 | North, South & West | Walls | Fibre Cement Sheeting | Removed | - | - | - | Item removed. Refer RiskTech clearance cert dated 02/02/2022 | Yes |
Kenc | Kensington Campus | D26 | Bio Sciences North | 5 | 570 | South & West | Walls | Fibre Cement Sheeting | Removed | - | - | - | Item removed. Refer RiskTech clearance cert dated 02/02/2022 | Yes |
Kenc | Kensington Campus | D26 | Bio Sciences North | 5 | 569A | North & West | Walls | Fibre Cement Sheeting | Removed | - | - | - | Item removed. Refer Risktech clearance cert dated 02/02/2022 | Yes |
Kenc | Kensington Campus | D26 | Bio Sciences North | 5 | 566 | North, South, East & West | Walls | Fibre Cement Sheeting | Removed | - | - | - | Item removed. Refer Risktech clearance cert dated 02/02/2022 | Yes |
Kenc | Kensington Campus | D26 | Bio Sciences North | 5 | 568 | North, South & West | Walls | Fibre Cement Sheeting | Removed | - | - | - | Item removed. Refer RiskTech clearance cert dated 02/02/2022 | Yes |
Kenc | Kensington Campus | D26 | Bio Sciences North | 5 | 565 | North, South & West | Walls | Fibre Cement Sheeting | Removed | - | - | - | Item removed. Refer RiskTech clearance cert dated 02/02/2022 | Yes |
Kenc | Kensington Campus | D26 | Bio Sciences North | 5 | 562 | North, East & West | Walls | Fibre Cement Sheeting | Removed | - | - | - | - | Yes |
Kenc | Kensington Campus | D26 | Bio Sciences North | 1 | 142 | Biolink, | Walls (north side and northern section of west side) | Fibre Cement Sheeting | Removed | item Removed: Refer to RiskTech Clearance Certificate dated 30 October 2020 | Yes | |||
Kenc | Kensington Campus | D26 | Bio Sciences North | 4 | 449 | Biolink, | Walls | Fibre Cement Sheeting | Removed | - | - | - | Item removed. Refer RiskTech clearance cert dated 17/12/2021 | Yes |
Kenc | Kensington Campus | D26 | Bio Sciences North | 4 | 448B | Biolink, | Walls | Fibre Cement Sheeting | Removed | - | - | - | Item removed. Refer RiskTech clearance cert dated 17/12/2021 | Yes |
Kenc | Kensington Campus | D26 | Bio Sciences North | 4 | 448 | South & East | Walls | Fibre Cement Sheeting | Removed | - | - | - | Item removed. Refer Risktech clearance cert dated 17/12/21 | Yes |
FSFG | Fowlers Gap Field Station | FG14 | Fowlers Gap Laboratory | G | G02 | Store | Walls | Fibre Cement Sheeting | Positive (Chrysotile) | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment works. | No |
Kenc | Kensington Campus | D26 | Bio Sciences North | 4 | 455A | Biolink, | Walls | Fibre Cement Sheeting | Removed | - | - | - | Item removed. Refer RiskTech clearance cert dated 17/12/2021 | Yes |
FSFG | Fowlers Gap Field Station | FG13 | Fowlers Gap Shearers Quarters | G | - | Exterior, All Sides | Eaves (Note: Localised damage area on north side, NW corner) | Fibre Cement Sheeting | Positive (Chrysotile) | Non-friable | Low | P3 | Remedial works should be undertaken by a Class A/B Contractor or competent person within a planned control program. | No |
Kenc | Kensington Campus | D26 | Bio Sciences North | 3 | 357A | Biolink, | Walls | Fibre Cement Sheeting | Positive (Amosite & Chrysotile) - removed | - | - | - | Item removed. Refer Risktech Clearance Cert dated 17/11/2021 | Yes |
Kenc | Kensington Campus | D26 | Bio Sciences North | 1 | 138A | Biolink, | Walls | Fibre Cement Sheeting | Removed | - | - | - | Item removed. Refer Risktech Clearance cert dated 28/09/2021 | Yes |
Kenc | Kensington Campus | D26 | Bio Sciences North | 3 | 343 | Biolink, | Pipe Penetrations | Rope Packing Insulation | Positive (Amosite & Chrysotile) - removed | - | - | - | Item removed. Refer Risktech Clearance cert dated 17/11/2021. | Yes |
KENE | Kensington Environs | O14 | Kangas House | G | 8B | Below Windows & Sink | Walls | Fibre Cement Sheeting | Positive (Chrysotile) | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENE | Kensington Environs | O14 | Kangas House | G | 9 | Northern Side, Adjacent Skylights | Ceiling | Fibre Cement Sheeting | Positive (Chrysotile) | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENE | Kensington Environs | O14 | Kangas House | G | 9A | Northern Side, Adjacent Skylights | Ceiling | Fibre Cement Sheeting | Positive (Chrysotile) | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENE | Kensington Environs | MS48A | Owls House Building 2 | G | - | Exterior, Southern Side | Gable Sections | Fibre Cement Sheeting | Positive (Chrysotile) | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | G6 | Blockhouse | 2 | M2Q01 | Plant Room | Ductwork Joins | Sealant Mastic | Positive (chrysotile) | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | G6 | Blockhouse | G | G10D | Mezzanine Above G10D | Former Generator Plant | Gaskets | Positive (chrysotile) | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
FSW | Wellington Field Station | WFS1 | Wellington Field Station Cottage | G | 2 | Laundry, All Sides | Walls | Fibre Cement Sheeting | Positive (Chrysotile) | Non-friable | Low | P3 | Repair/seal the localised damage areas to the wall sheeting under controlled conditions within a planned control program. Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment works. | No |
FSW | Wellington Field Station | WFS2A | Wellington Field Station Accommodation | G | G01 | Throughout | Walls | Fibre Cement Sheeting | Positive (Chrysotile) | Non-friable | Low | P3 | Repair/seal the localised damage areas to the wall sheeting under controlled conditions within a planned control program. Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment works. | No |
FSW | Wellington Field Station | WFS2A | Wellington Field Station Accommodation | G | G02 | Throughout | Walls | Fibre Cement Sheeting | Positive (Chrysotile) | Non-friable | Low | P3 | Repair/seal the localised damage areas to the wall sheeting under controlled conditions within a planned control program. Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment works. | No |
FSW | Wellington Field Station | WFS2A | Wellington Field Station Accommodation | G | G03 | Throughout | Walls | Fibre Cement Sheeting | Positive (Chrysotile) | Non-friable | Low | P3 | Repair/seal the localised damage areas to the wall sheeting under controlled conditions within a planned control program. Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment works. | No |
FSW | Wellington Field Station | WFS2A | Wellington Field Station Accommodation | G | G04 | Throughout | Walls | Fibre Cement Sheeting | Positive (Chrysotile) | Non-friable | Low | P3 | Repair/seal the localised damage areas to the wall sheeting under controlled conditions within a planned control program. Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment works. | No |
FSW | Wellington Field Station | WFS2A | Wellington Field Station Accommodation | G | G05 | Throughout | Walls | Fibre Cement Sheeting | Positive (Chrysotile) | Non-friable | Low | P3 | Repair/seal the localised damage areas to the wall sheeting under controlled conditions within a planned control program. Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment works. | No |
FSW | Wellington Field Station | WFS2A | Wellington Field Station Accommodation | G | - | Exterior, All Sides | Walls | Fibre Cement Sheeting | Positive (Chrysotile) | Non-friable | Low | P3 | Repair/seal the localised damage areas to the wall sheeting under controlled conditions within a planned control program. Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment works. | No |
FSW | Wellington Field Station | WFS2 | Wellington Field Station Shearing Shed | G | G01 | West Side, Toilets & Shower Room, Corridor, Laboratory & SW Corner Room | Floor Covering | Vinyl Tiles (white colour) | Positive (Chrysotile) | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment works. | No |
FSW | Wellington Field Station | WFS2 | Wellington Field Station Shearing Shed | G | G01 | West Side, NW Corner Room & Adjacent Kitchen | Floor Covering | Vinyl Tiles (white colour) | Positive (Chrysotile) | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment works. | No |
FSSL | Smiths Lake Field Station | SL1 | Smiths Lake Laboratory | G | UGQ2 | Exterior, South | Eaves | Fibre Cement Sheeting | Positive (Chrysotile) | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment works. | No |
Kenc | Kensington Campus | D26 | Bio Sciences North | 2 | 2Q7 | Biolink, | Walls | Fibre Cement Sheeting | Removed | - | - | - | Item removed. Refer Risktech Clearance cert dated 13/10/2021 | Yes |
FSSL | Smiths Lake Field Station | SL1 | Smiths Lake Laboratory | G | - | Exterior, East | Inside Electrical Cabinet | Electrical Backing Board | Positive (Chrysotile) | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment works. | No |
Kenc | Kensington Campus | D26 | Bio Sciences North | 1 | 142A | Biolink, | Wall | Fibre Cement Sheeting | Removed | - | - | - | item removed. Refer Risktech Clearance cert dated 28/09/2021 | Yes |
RANC | Randwick Campus | R5 | Randwick R5 | G | - | Exterior, North, Ground Surfaces (assumed present beneath vegetation / leaf litter) | Debris | Fibre Cement Sheeting | Positive (chrysotile) | Non-Friable | Low | P3 | Restrict access to north side ground surfaces. Undertake removal/remedial works of fibre cement sheeting debris within a planned control program. | No |
RANC | Randwick Campus | R1f | Randwick R1f | G | - | Exterior, South & West of Building, Ground Surface | Debris | Fibre Cement Sheeting | Positive (chrysotile) (Removed) | - | - | - | Item Removed: RiskTech Compliance removed fibre cement debris as part of the inspection process. | Yes |
RANC | Randwick Campus | R1 | Randwick R1 | G | G28 | Under New Vinyl Floor Sheet | Floor Covering (suspected present beneath sheet vinyl) | Vinyl Tiles (tan colour) | Positive (chrysotile) | Non-Friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
MANV | Manly Vale | MV12 | Cool Room | G | G01 | - | Floor Covering Underlay (beneath sheet vinyl floor covering) | Bituminous Material | Positive (chrysotile) | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | K15 | Old Main | LG | LG42 | Electrical Switch Room | Floor Covering (suspected beneath grey sheet vinyl) | Vinyl Tiles (beige colour) | Positive (chrysotile) | Non-friable | Low | P4 | Confirm presence and extent of asbestos containing vinyl floor tiles beneath grey sheet vinyl and if present, remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment | No |
KENC | Kensington Campus | K14 | Physics Theatre | LG | LG13 | - | Floor Covering | Vinyl Tiles (grey colour) | Positive (chrysotile) | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
Kenc | Kensington Campus | J14 | Keith Burrows Theatre | G-1 | - | Exterior, North, West & East Sides | Vertical Wall Expansion Joints | Mastic Sealant | Positive (chrysotile) | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | H25 | Botany Street Parking Station | 01 | 1Q1 | Stairwell, South | Windows (between frame and glazing) | Mastic Sealant | Positive (chrysotile) | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
Kenc | Kensington Campus | G15 | Robert Webster Theatres | 01-02 | - | Exterior, West Side | Façade Wall Panel Joints | Pointing | Positive (chrysotile) | Non-friable | Low | P3 | Remediate (remove and/or seal) under controlled conditions by a Class A/B contractor within a planned control program. | No |
KENC | Kensington Campus | F13 | Science Theatre | 2 | - | Stage, Mezzanine Level, North | Service Riser Panelling | Fibre Cement Sheeting | Positive (Chrysotile) | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | F13 | Science Theatre | G | G07 | Electrical Cupboard, East and West | Walls | Fibre Cement Sheeting | Positive (Chrysotile) | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENC | Kensington Campus | F13 | Science Theatre | G | - | Exterior, South | Walkway Roof Covering | Bitumen Membrane | Removed: Positive (chrysotile) | - | - | - | Item Removed. Refer to RiskTech Compliance Asbestos Clearance Certificate dated 12 February 2024. | Yes |
KENC | Kensington Campus | F12 | Dalton | G | - | Exterior, East of Building, Covered Walkway | Roof Covering | Bituminous Membrane | Positive (chrysotile) | - | - | - | Item Removed - Refer to RiskTech Compliance Asbestos Clearance Certificate dated 12 February 2024. | No |
KENC | Kensington Campus | F12 | Dalton | 02 | 2Q2 | North-East & South-East | Window Frames (between frame and pane) | Mastic Sealant | Positive (chrysotile) | Non-Friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
Kenc | Kensington Campus | D26 | Bio Sciences North | 1 | 141A | Biolink, | Wall | Fibre Cement Sheeting | Removed | - | - | - | Item removed. Refer RiskTech Clearance cert dated 28/09/2021 | Yes |
KENC | Kensington Campus | D23 | Mathews Theatres | 01 | 150 | Plant Room, Western Section | Ductwork Flange Joints | Mastic Sealant (grey colour) | Positive (chrysotile) | Non-Friable | Low | P4 | Maintain in good condition. Remove under controlled conditions prior to demolition or refurbishment. | No |
FSH | Hay Field Station | HFS8 | Hay Field Station Managers Office | G | - | Exterior, East & West | Eaves | Fibre Cement Sheeting | Positive (Chrysotile) | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment works. | No |
FSH | Hay Field Station | HFS7 | Hay Field Station Quarters | G | - | Exterior, All Sides | Eaves | Fibre Cement Sheeting | Positive (Chrysotile) | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment works. | No |
FSH | Hay Field Station | HFS7 | Hay Field Station Quarters | G | G09 | Kitchen | Floor Covering | Vinyl Tiles | Positive (Chrysotile) | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment works. | No |
FSH | Hay Field Station | HFS7 | Hay Field Station Quarters | G | GQ7 | Mens Toilet & Amenities | Walls | Fibre Cement Sheeting | Positive (Chrysotile) | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment works. | No |
FSH | Hay Field Station | HFS7 | Hay Field Station Quarters | G | GQ2 | Corridor | Ceiling | Fibre Cement Sheeting | Positive (Chrysotile) | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment works. | No |
FSH | Hay Field Station | HFS7 | Hay Field Station Quarters | G | GQ2 | Corridor | Walls | Fibre Cement Sheeting | Positive (Chrysotile) | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment works. | No |
FSH | Hay Field Station | HFS7 | Hay Field Station Quarters | G | G07A | Pantry | Ceiling | Fibre Cement Sheeting | Positive (Chrysotile) | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment works. | No |
FSH | Hay Field Station | HFS7 | Hay Field Station Quarters | G | G07 | Kitchen | Walls | Fibre Cement Sheeting | Positive (Chrysotile) | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment works. | No |
FSH | Hay Field Station | HFS7 | Hay Field Station Quarters | G | G07A | Pantry | Floor Covering | Vinyl Tiles | Positive (Chrysotile) | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment works. | No |
FSH | Hay Field Station | HFS7 | Hay Field Station Quarters | G | G07 | Kitchen | Floor Covering | Vinyl Tiles | Positive (Chrysotile) | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment works. | No |
FSH | Hay Field Station | HFS8 | Hay Field Station Managers Office | G | - | Carport, South & East | Walls | Fibre Cement Sheeting | Positive (Chrysotile) | Non-friable | Low | P3 | Repair/seal the localised damage areas under controlled conditions within a planned control program. Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment works. | No |
FSH | Hay Field Station | HFS8 | Hay Field Station Managers Office | G | - | Far SW Corner Room, Toilet (former uncovered awning) | Walls | Fibre Cement Sheeting | Positive (Chrysotile) | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment works. | No |
FSH | Hay Field Station | HFS8 | Hay Field Station Managers Office | G | G01 | Far NW Corner Room, | Ceiling | Fibre Cement Sheeting | Positive (Chrysotile) | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment works. | No |
Kenc | Kensington Campus | D26 | Bio Sciences North | 2 | 256 | North, South & West | Walls | Fibre Cement Sheeting | Removed | - | - | - | Item removed. Refer Risktach Clearance cert dated 13/10/2021 | Yes |
Kenc | Kensington Campus | D26 | Bio Sciences North | 2 | 255 | Biolink, | Walls | Fibre Cement Sheeting | Removed | - | - | - | Item removed. Refer Risktech Clearance cert dated 13/10/2021 | Yes |
FSH | Hay Field Station | HFS8 | Hay Field Station Managers Office | G | UCA | Exterior, Northern Side, Uncovered Awning Area | Awning Ceiling | Fibre Cement Sheeting | Positive (Chrysotile) | Non-friable | Low | P3 | Repair/seal the localised damage areas under controlled conditions within a planned control program. Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment works. | No |
FSH | Hay Field Station | HFS8 | Hay Field Station Managers Office | G | UCA | Exterior, Southern Side, Uncovered Awning Area | Awning Ceiling | Fibre Cement Sheeting | Positive (Chrysotile) | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment works. | No |
FSH | Hay Field Station | HFS2 | Hay Field Station Workshop | G | - | Exterior, West Side (Outside Room G04) - On Ground | Disused Pipe Collar | Moulded Fibre Cement Material | Positive (Chrysotile) | Non-friable | Low | P3 | Remove disused fibre cement pipe collar under controlled conditions within a planned control program. | No |
FSFG | Fowlers Gap Field Station | FG1 | Fowlers Gap Solarch House | G | G12 | Southern Store Room Adjacent Carport | Flooring | Compressed Fibre Cement Sheeting | Positive (Chrysotile) | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment works. | No |
FSFG | Fowlers Gap Field Station | FG1 | Fowlers Gap Solarch House | G | G13 | Southern Store Room Adjacent Carport | Flooring | Compressed Fibre Cement Sheeting | Positive (Chrysotile) | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment works. | No |
FSFG | Fowlers Gap Field Station | FG4 | Fowlers Gap Cottage 5 | G | - | Exterior, Subfloor Space | On Top of Brick Suppport Piers - Packing | Fibre Cement Sheeting | Positive (Chrysotile) | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment works. | No |
FSFG | Fowlers Gap Field Station | FG15 | Fowlers Gap Cottage 1 | G | - | Exterior, Verandah, North, East and West Sides | Flooring | Compressed Fibre Cement Sheeting | Positive (Chrysotile) | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment works. | No |
Kenc | Kensington Campus | D26 | Bio Sciences North | 2 | 272 | Biolink, | Wall | Fibre Cement Sheeting | Positive (Amosite & Chrysotile) | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
Kenc | Kensington Campus | D26 | Bio Sciences North | 1 | 132A | Biolink, | Walls | Fibre Cement Sheeting | Removed | - | - | - | Item removed. Refer Risktech Clearance cert dated 28/09/2021 | Yes |
FSFG | Fowlers Gap Field Station | FG18 | Fowlers Gap Cottage 4 | G | G05 | Laundry | Floor Covering | Sheet Vinyl | Positive (Chrysotile) | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment works. | No |
FSFG | Fowlers Gap Field Station | FG19 | Fowlers Gap Cottage 3 | G | - | Exterior, All Sides | Walls | Profiled Fibre Cement Sheeting | Positive (Chrysotile) | Non-friable | Low | P4 | Removed between 26/08/2024 to 31/08/2023 as per Asbestos Clearance Certificate dated 03/09/2024 | Yes |
FSFG | Fowlers Gap Field Station | FG13 | Fowlers Gap Shearers Quarters | G | G05 | Near SE Corner, Entrance Area to Laundry | Floor Covering | Vinyl Tiles | Positive (Chrysotile) | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment works | No |
FSFG | Fowlers Gap Field Station | FG13 | Fowlers Gap Shearers Quarters | G | G17 | Northern Toilets & Showers | Walls | Fibre Cement Sheeting | Positive (Chrysotile) | Non-friable | Low | P3 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment works | No |
FSFG | Fowlers Gap Field Station | FG13 | Fowlers Gap Shearers Quarters | G | G18 | Northern Toilets & Showers | Walls (Note: Localised damaged area - temporarily covered) | Fibre Cement Sheeting | Positive (Chrysotile) | Non-friable | Low | P3 | Remedial works should be undertaken by a Class A/B Contractor or competent person within a planned control program. | No |
FSFG | Fowlers Gap Field Station | FG14 | Fowlers Gap Laboratory | G | G04 | Laboratory Store | Floor Covering | Vinyl Tiles (green and brown colour) | Positive (Chrysotile) | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment works. | No |
Kenc | Kensington Campus | D26 | Bio Sciences North | 1 | 132B | Biolink, | Walls | Fibre Cement Sheeting | Removed | - | - | - | Item removed. Refer Risktech Clearance cert dated 28/09/2021 | Yes |
KENE | Kensington Environs | BS30 | 30 Botany Street | 1 | 114 | North-East, Low Level | Infill Panels | Fibre Cement Sheeting | Positive (Chrysotile) | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENE | Kensington Environs | BS30 | 30 Botany Street | G | UGQ01 | South Entrance to Level 1 | Ceiling | Fibre Cement Sheeting | Positive (Chrysotile) | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
KENE | Kensington Environs | AS22 | 22 Arthur Street | G | - | Exterior, Main Residence, Rear, South, East and West | Wall Cladding | Fibre Cement Sheeting | Positive (Chrysotile) | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment works. | No |
KENE | Kensington Environs | AS22 | 22 Arthur Street | G | - | Verandah | Ceiling | Fibre Cement Sheeting | Positive (Chrysotile) | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment works. | No |
KENE | Kensington Environs | AS8 | 8 Arthur Street | G | - | Exterior, Garage, North and South | Gable | Fibre Cement Sheeting | Positive (Chrysotile) | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment works. | No |
KENE | Kensington Environs | AS4 | 4 Arthur Street | G | G12 | Exterior, Garage, North | Gable | Fibre Cement Sheeting | Positive (Chrysotile) | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment works. | No |
KENE | Kensington Environs | AS4 | 4 Arthur Street | G | - | Exterior, Verandah, South | Eaves | Fibre Cement Sheeting | Positive (Chrysotile) | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment works. | No |
KENE | Kensington Environs | AS2 | 2 Arthur Street | G | - | Rear Sunroom, South, East and West | Wall Lining | Fibre Cement Sheeting | Positive (Chrysotile) | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment works. | No |
KENC | Kensington Campus | F13 | Science Theatre | LG | LG1 | Plant Room | Air Conditioning Ductwork Flange Joints | Mastic Sealant | Positive (Chrysotile) | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
Kenc | Kensington Campus | C6 | International House | 1 | 199 | Male Amenities / Toilets - Plumbing Riser | Flues x 2 | Compressed Bituminous Pipes | Removed - Positive (visually confirmed) | - | - | - | Item Removed: No removal/clearance documentation was provided | Yes |
Kenc | Kensington Campus | C6 | International House | 2 | 299 | Male Amenities / Toilets - Plumbing Riser | Flues x 2 | Compressed Bituminous Pipes | Positive - Removed (visually confirmed) | - | - | - | Item Removed: No removal/clearance documentation was provided | Yes |
Kenc | Kensington Campus | C6 | International House | 3 | 399 | Male Amenities / Toilets - Plumbing Riser | Flues x 2 | Compressed Bituminous Pipes | Positive - Removed (visually confirmed) | - | - | - | Item Removed: No removal/clearance documentation was provided | Yes |
Kenc | Kensington Campus | D26 | Bio Sciences North | 1 | 132 | Biolink, | Walls | Fibre Cement Sheeting | Removed | - | - | - | Item removed. Refer Risktech Clearance cert dated 28/09/2021 | Yes |
Kenc | Kensington Campus | D26 | Bio Sciences North | 1 | 138 | Biolink, | Wall | Fibre Cement Sheeting | Removed | - | - | - | Item removed. Refer Risktech Clearance cert dated 28/09/2021 | Yes |
Kenc | Kensington Campus | D26 | Bio Sciences North | 1 | 134 | Biolink, | Walls | Fibre Cement Sheeting | Removed | - | - | - | Item removed. Refer Risktech Clearance cert dated 28/09/2021 | Yes |
Kenc | Kensington Campus | D26 | Bio Sciences North | G | GQ13 | Biolink, | Walls | Fibre Cement Sheeting | Positive - Removed | - | - | - | Item Removed: Refer to Risktech Clearance Certificate dated 10 September 2021 | Yes |
Kenc | Kensington Campus | D26 | Bio Sciences North | G | G21 | Biolink, | Pipe Penetrations | Rope Packing Insulation | Positive - Removed | - | - | - | Item Removed: Refer to Risktech Clearance Certificate dated 10 September 2021 | Yes |
Kenc | Kensington Campus | D26 | Bio Sciences North | LG | LG30 | Biosciences North, | Inside Electrical Cabinet | Electrical Backing Board Debris | Positive (Chrysotile) | Non-friable | Med | P3 | Remove under controlled conditions by a Class A/B contractor as part of a planned control program or prior to demolition or refurbishment. | No |
Kenc | Kensington Campus | D26 | Bio Sciences North | LG | LG30 | Biosciences North, | Inside Electrical Cabinet | Electrical Backing Board | Positive (Chrysotile) | Non-friable | Low | P4 | Remediate under controlled conditions by a Class A/B contractor as part of a planned control program or prior to demolition or refurbishment. | No |
Kenc | Kensington Campus | D26 | Bio Sciences North | 6 | R01 | Plant Room, Throughout | Old Air Conditioning Ductwork - Flange Joints & Joins | Sealant Mastic | Positive (Chrysotile) | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
Kenc | Kensington Campus | D26 | Bio Sciences North | 3 | 352 | Biolink | Ceiling | Fibre Cement Sheeting | Positive (Chrysotile) - removed | - | - | - | Item removed. Refer Risktech Clearance Cert dated 17th November 2021 | Yes |
Kenc | Kensington Campus | D26 | Bio Sciences North | 5 | 554A | - | Ceiling | Fibre Cement Sheeting | Removed | - | - | - | Item removed. Refer RiskTech clearance cert dated 02/02/2022 | Yes |
Kenc | Kensington Campus | D26 | Bio Sciences North | 5 | 555 | - | Ceiling Tiles | Fibre Cement Sheeting | Removed | - | - | - | Item removed. Refer Risktech clearance cert dated 02/02/22 | Yes |
Kenc | Kensington Campus | D26 | Bio Sciences North | 5 | 561 | - | Fume Cupboard, Internal Lining | Fibre Cement Sheeting | Removed | - | - | - | Item removed. Refer Risktech clearance cert dated 02/02/2022 | Yes |
Kenc | Kensington Campus | D26 | Bio Sciences North | 4 | 450 | Biolink, | Walls | Fibre Cement Sheeting | Removed | - | - | - | Item removed. Refer RiskTech clearance cert dated 17/12/2021 | Yes |
Kenc | Kensington Campus | D26 | Bio Sciences North | 4 | 457 | Biolink, | Walls | Fibre Cement Sheeting | Removed | - | - | - | Item removed. Refer Risktech clearance cert dated 17/12/21 | Yes |
Kenc | Kensington Campus | D26 | Bio Sciences North | 3 | 349 | Biolink, | Walls | Fibre Cement Sheeting | Positive (Chrysotile) - removed | - | - | - | Item removed. Refer Risktech clearance cert dated 17/11/2021 | Yes |
Kenc | Kensington Campus | D26 | Bio Sciences North | 2 | 260 | Biolink, | Pipe Penetrations | Rope Packing Insulation (suspected beneath sealant covering) | Removed | - | - | - | Item removed. Refer Risktech Clearance cert dated 13/10/2021 | Yes |
Kenc | Kensington Campus | D26 | Bio Sciences North | 4 | 4Q7 | Biolink, | Pipe Penetrations | Rope Packing Insulation | Removed | - | - | - | Item removed. Refer Risktech clearance cert dated 17/12/21 | Yes |
Kenc | Kensington Campus | D26 | Bio Sciences North | 4 | 450 | Biolink, | Pipe Penetrations | Rope Packing Insulation | Removed | - | - | - | Item removed. Refer Risktech clearance cert dated 17/12/21 | Yes |
Kenc | Kensington Campus | D26 | Bio Sciences North | 2 | 257 | Biolink | Fume Cupboard, Internal Lining | Fibre Cement Sheeting | Positive (Chrysotile) | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
Kenc | Kensington Campus | D26 | Bio Sciences North | 2 | 260 | Biolink, | Walls | Fibre Cement Sheeting | Removed | - | - | - | Item removed. Refer Risktech Clearance cert dated 13/10/2021 | Yes |
Kenc | Kensington Campus | D26 | Bio Sciences North | 2 | 258 | Biolink, | Walls | Fibre Cement Sheeting | Removed | - | - | - | Item removed. Refer Risktech Clearance cert dated 13/10/2021 | Yes |
Kenc | Kensington Campus | D26 | Bio Sciences North | 2 | 257 | Biolink, | Walls | Fibre Cement Sheeting | Removed | - | - | - | Item removed. Refer Risktech Clearance cert dated 13/10/2021 | Yes |
Kenc | Kensington Campus | D26 | Bio Sciences North | 1 | 138A | Biolink, | Ceiling | Fibre Cement Sheeting | Removed | - | - | - | Item removed. Refer Risktech Clearance cert dated 28/09/2021 | Yes |
Kenc | Kensington Campus | D26 | Bio Sciences North | 1 | 141A | Biolink, | Pipe Penetrations | Rope Packing Insulation | Removed | - | - | - | Item removed. Refer RiskTech Clearance cert dated 28/09/2021 | Yes |
Kenc | Kensington Campus | D26 | Bio Sciences North | 1 | 139 | Biolink | Air Conditioning Ductwork - Flange Joints | Sealant Mastic | Positive (Chrysotile) | Non-friable | Low | P4 | Maintain in good condition. Remove under controlled conditions by a Class A/B contractor prior to demolition or refurbishment. | No |
Kenc | Kensington Campus | D26 | Bio Sciences North | G | G23 | Biolink, | Wall | Fibre Cement Sheeting | Positive - Removed | - | - | - | Item Removed: Refer to Risktech Clearance Certificate dated 10 September 2021 | Yes |
Kenc | Kensington Campus | D26 | Bio Sciences North | 3 | 343 | Biolink | Floor Covering | Vinyl Floor Tiles (mustard coloured) | Assumed Negative | - | - | - | - | N/A |
Kenc | Kensington Campus | N13 | Barker Apartments | 1 | 101 | Laundry | Walls | Fibre Cement Sheeting | Assumed Negative | - | - | - | - | No |
Kenc | Kensington Campus | N13 | Barker Apartments | 1 | 101 | Laundry | Ceiling | Fibre Cement Sheeting | Assumed Negative | - | - | - | - | No |
Kenc | Kensington Campus | N13 | Barker Apartments | 1 | 102 | Garbage Bin Room | Ceiling | Fibre Cement Sheeting | Assumed Negative | - | - | - | - | No |
Kenc | Kensington Campus | N13 | Barker Apartments | 1 | 105 | Laundry | Walls | Fibre Cement Sheeting | Assumed Negative | - | - | - | - | No |
Kenc | Kensington Campus | N13 | Barker Apartments | 1 | 105 | Laundry | Ceiling | Fibre Cement Sheeting | Assumed Negative | - | - | - | - | No |
Kenc | Kensington Campus | N13 | Barker Apartments | 1 | 107 | Garbage Bin Room | Walls | Fibre Cement Sheeting | Assumed Negative | - | - | - | - | No |
Kenc | Kensington Campus | N13 | Barker Apartments | 1 | 107 | Garbage Bin Room | Ceiling | Fibre Cement Sheeting | Assumed Negative | - | - | - | - | No |
Kenc | Kensington Campus | N13 | Barker Apartments | 1 | 110 | Laundry | Walls | Fibre Cement Sheeting | Assumed Negative | - | - | - | - | No |
Kenc | Kensington Campus | N13 | Barker Apartments | 1 | 110 | Laundry | Ceiling | Fibre Cement Sheeting | Assumed Negative | - | - | - | - | No |
Kenc | Kensington Campus | N13 | Barker Apartments | 1 | 114 | Laundry | Ceiling | Fibre Cement Sheeting | Assumed Negative | - | - | - | - | No |
Kenc | Kensington Campus | D26 | Bio Sciences North | 3 | 360 | Biolink | Floor Covering | Vinyl Floor Tiles (mustard coloured) | Assumed Negative | - | - | - | - | No |
Kenc | Kensington Campus | J14 | Keith Burrows Theatre | G | G03 | Male Toilet, Ceiling Space | Ductwork Joins | Mastic Sealant (red colour) | Assumed Negative | - | - | - | - | No |
KENC | Kensington Campus | J12 | Newton | 1 | 1Q2 | Opposite Lifts | Windows | Mastic Sealant | Assumed Negative | - | - | - | - | No |
KENC | Kensington Campus | J12 | Newton | 3 | 3Q1 | Opposite Lifts | Windows | Mastic Sealant | Assumed Negative | - | - | - | - | No |
KENC | Kensington Campus | G27 | AGSM | LG | LG04 | Plant Room, Adjacent Entrance | Air Conditioning Ductwork Heater Bank | Insulation Board | Assumed Negative | - | - | - | - | No |
Kenc | Kensington Campus | D26 | Bio Sciences North | 3 | 3Q6 | Biolink | Floor Covering | Vinyl Floor Tiles (mustard coloured) | Assumed Negative | - | - | - | - | No |
Kenc | Kensington Campus | D26 | Bio Sciences North | 3 | 3Q9 | Biolink | Floor Covering | Vinyl Floor Tiles (green coloured) | Assumed Negative | - | - | - | - | No |
KENC | Kensington Campus | F21 | Library | 15 | 1501 | Plant Room | Vertical Wall Stiffeners (behind metal cover) | Insulation | Assumed Negative | - | - | - | - | No |
KENC | Kensington Campus | F21 | Library | 15 | 1501 | Plant Room | On Top of Blockwork Walls | Insulation Packing | Assumed Negative | - | - | - | - | No |
KENC | Kensington Campus | F13 | Science Theatre | 1 | 110A | Throughout | Cubicle Partitions | Compressed Fibre Cement Sheeting | Assumed Negative | - | - | - | - | No |
KENC | Kensington Campus | F13 | Science Theatre | G | G12A/G13A | Male and Female Toilets | Cubicle Partitions | Compressed Fibre Cement Sheeting | Assumed Negative | - | - | - | - | No |
KENC | Kensington Campus | F13 | Science Theatre | 1 | 101A | Throughout | Cubicle Partitions | Compressed Fibre Cement Sheeting | Assumed Negative | - | - | - | - | No |
Kenc | Kensington Campus | D26 | Bio Sciences North | 4 | 448 | Biolink | Floor Covering | Vinyl Floor Tiles (green coloured) | Assumed Negative | - | - | - | - | No |
Kenc | Kensington Campus | D26 | Bio Sciences North | 4 | 448B | Biolink | Floor Covering | Vinyl Floor Tiles (green coloured) | Assumed Negative | - | - | - | - | No |
Kenc | Kensington Campus | D26 | Bio Sciences North | 4 | 449 | Biolink | Floor Covering | Vinyl Floor Tiles (green coloured) | Assumed Negative | - | - | - | - | No |
Kenc | Kensington Campus | D26 | Bio Sciences North | 4 | 450C | Biolink | Floor Covering | Vinyl Floor Tiles (green coloured) | Assumed Negative | - | - | - | - | No |
DPFS | David Phillips Field | DP1 | Central Amenities | G | GQ4, GQ5, GQ6, GQ7, G07, G08 | Throughout | Wall Lining | Fibre Cement Sheeting | Assumed Negative | - | - | - | - | No |
DPFS | David Phillips Field | DP1 | Central Amenities | G | GQ10, GQ11, GQ12, GQ13, G12, G14, G15 | Throughout | Cubicle Partitions | Compressed Fibre Cement Sheeting | Assumed Negative | - | - | - | - | No |
DPFS | David Phillips Field | DP1 | Central Amenities | G | GQ10, GQ11, GQ12, GQ13, G12 G14, G15 | Throughout | Wall Lining | Fibre Cement Sheeting | Assumed Negative | - | - | - | - | No |
KENC | Kensington Campus | B15 | Old Tote | G | - | Exterior, Surrounding | Windows | Mastic sealant | Assumed Negative | - | - | - | - | No |
KENC | Kensington Campus | B15 | Old Tote | 02 | - | Exterior, Surrounding | Windows | Mastic sealant | Assumed Negative | - | - | - | - | No |
KENC | Kensington Campus | B14D | Fig Tree Theatre | G | 2 | Make Up/Preparation Rooms | Floor Covering under Carpet Tiles | Vinyl Tiles (Cream colour) | Assumed Negative | - | - | - | - | No |
KENC | Kensington Campus | B14D | Fig Tree Theatre | G | 1 | Hallway (only) | Floor Covering under Carpet Tiles | Vinyl Tiles (cream colour) | Assumed Negative | - | - | - | - | No |
KENC | Kensington Campus | B14D | Fig Tree Theatre | G | 2 | Make Up/Preparation Rooms | Floor Covering under Carpet Tiles | Vinyl Tiles (Brown colour) | Assumed Negative | - | - | - | - | No |
KENC | Kensington Campus | B14D | Fig Tree Theatre | G | 1 | Hallway (only) | Floor Covering under Carpet Tiles | Vinyl Tiles (Brown colour) | Assumed Negative | - | - | - | - | No |
Kenc | Kensington Campus | D26 | Bio Sciences North | 4 | 450E | Biolink | Floor Covering | Vinyl Floor Tiles (green coloured) | Assumed Negative | - | - | - | - | No |
Kenc | Kensington Campus | N18 | Barker Street Parking Station | 05 | 5Q4 | Exterior, Surrounding | Eaves | Fibre Cement Sheeting | Assumed Negative | - | - | - | - | No |
Kenc | Kensington Campus | D26 | Bio Sciences North | 4 | 450F | Biolink | Floor Covering | Vinyl Floor Tiles (green coloured) | Assumed Negative | - | - | - | - | No |
KENC | Kensington Campus | H8 | Sam Cracknell Pavilion | G | G02 | Throughout | Cubicle Partitions | Compressed Fibre Cement Sheeting | Assumed Negative | - | - | - | - | No |
KENC | Kensington Campus | H8 | Sam Cracknell Pavilion | G | G11A | Change Room adjacent Female Bathroom | Cubicle Partitions | Compressed Fibre Cement Sheeting | Assumed Negative | - | - | - | - | No |
KENC | Kensington Campus | H8 | Sam Cracknell Pavilion | G | G09 | Male Bathroom | Ceiling | Fibre Cement Sheeting | Assumed Negative | - | - | - | - | No |
KENC | Kensington Campus | H8 | Sam Cracknell Pavilion | G | G09A | Male Bathroom | Ceiling | Fibre Cement Sheeting | Assumed Negative | - | - | - | - | No |
KENC | Kensington Campus | H8 | Sam Cracknell Pavilion | G | G10 | Female Bathroom | Ceiling | Fibre Cement Sheeting | Assumed Negative | - | - | - | - | No |
KENC | Kensington Campus | H8 | Sam Cracknell Pavilion | G | G10A | Female Bathroom | Ceiling | Fibre Cement Sheeting | Assumed Negative | - | - | - | - | No |
KENC | Kensington Campus | H8 | Sam Cracknell Pavilion | G | G12 | Equipment Store 1 | Ceiling | Fibre Cement Sheeting | Assumed Negative | - | - | - | - | No |
KENC | Kensington Campus | E6 | Roundhouse | G | - | Exterior, Surrounding | Awning Ceiling | Fibre Cement Sheeting | Assumed Negative | - | - | - | - | No |
KENC | Kensington Campus | E15 | Quadrangle | LG | - | Various Toilet Riser Ducts | Waste Pipe | Moulded Fibre Cement | Assumed Negative | - | - | - | - | No |
KENC | Kensington Campus | E15 | Quadrangle | G | - | Various Toilet Riser Ducts | Waste Pipe | Moulded Fibre Cement | Assumed Negative | - | - | - | - | No |
KENC | Kensington Campus | E15 | Quadrangle | 01 | - | Various Toilet Riser Ducts | Waste Pipe | Moulded Fibre Cement | Assumed Negative | - | - | - | - | No |
KENC | Kensington Campus | E15 | Quadrangle | 02 | - | Various Toilet Riser Ducts | Waste Pipe | Moulded Fibre Cement | Assumed Negative | - | - | - | - | No |
KENC | Kensington Campus | E15 | Quadrangle | 03 | - | Various Toilet Riser Ducts | Waste Pipe | Moulded Fibre Cement | Assumed Negative | - | - | - | - | No |
KENC | Kensington Campus | E12 | UNSW Business School | G-6 | - | Toilets Throughout | Wall Linings | Fibre Cement Sheeting | Assumed Negative | - | - | - | - | No |
KENC | Kensington Campus | E12 | UNSW Business School | 6 | 6Q13 | Male Toilet | Wall Linings | Fibre Cement Sheeting | Assumed Negative | - | - | - | - | No |
DPFS | David Phillips Field | DP4 | Grounds Depot | G | G02 | Shower | Walls | Fibre Cement Sheeting | Assumed Negative | - | - | - | - | No |
DPFS | David Phillips Field | DP4 | Grounds Depot | G | G02 | Shower | Ceiling | Fibre Cement Sheeting | Assumed Negative | - | - | - | - | No |
DPFS | David Phillips Field | DP4 | Grounds Depot | G | G02 | Toilet | Walls | Fibre Cement Sheeting | Assumed Negative | - | - | - | - | No |
Kenc | Kensington Campus | D16 | Goldstein Hall | 01 | 1Q7 | - | Ceiling | Fibre Cement Sheeting | Assumed Negative | - | - | - | - | No |
Kenc | Kensington Campus | D16 | Goldstein Hall | 01 | 1Q7 | Behind Ceramic Walls Tiles | Wall Linings | Fibre Cement Sheeting | Assumed Negative | - | - | - | - | No |
Kenc | Kensington Campus | D16 | Goldstein Hall | 01 | 1Q10 | Throughout, Behind Ceramic Walls Tiles | Wall Linings | Fibre Cement Sheeting | Assumed Negative | - | - | - | - | No |
Kenc | Kensington Campus | D16 | Goldstein Hall | 01 | 1Q11 | Throughout, Behind Ceramic Walls Tiles | Wall Linings | Fibre Cement Sheeting | Assumed Negative | - | - | - | - | No |
Kenc | Kensington Campus | D16 | Goldstein Hall | G | GQ10 | - | Wall Linings | Fibre Cement Sheeting | Assumed Negative | - | - | - | - | No |
Kenc | Kensington Campus | D10 | Building D10 | G | GQ1 | Exterior, at Entrance | Ceiling | Fibre Cement Sheeting | Assumed Negative | - | - | - | - | No |
COFA | Paddington Campus | CFAF | Block F | G | - | Exterior, West | Ceiling Panels | Fibre Cement Sheeting | Assumed Negative | - | - | - | - | No |
COFA | Paddington Campus | CFAF | Block F | 01 | - | Exterior, North-East Terrace | Ceiling Panels | Fibre Cement Sheeting | Assumed Negative | - | - | - | - | No |
COFA | Paddington Campus | CFAF | Block F | 04 | - | Exterior, North-West Terrace | Ceiling Panels | Fibre Cement Sheeting | Assumed Negative | - | - | - | - | No |
COFA | Paddington Campus | CFAE | Block E | G | JEGQ01 | Exterior | Ceiling Panels | Fibre Cement Sheeting | Assumed Negative | - | - | - | - | No |
COFA | Paddington Campus | CFAD | Block D | 03 | D3Q3 | Cooling Tower Plant Room | Within Electrical Cabinet | Electrical Backing Board | Suspected Negative | - | - | - | - | No |
Kenc | Kensington Campus | C24 | Clancy Auditorium | G | G13A | Behind Ceramic Walls Tiles | Wall Linings | Fibre Cement Sheeting | Assumed Negative | - | - | - | - | No |
KENC | Kensington Campus | C20 | Morven Brown | G | - | Interior Throughout Level, Various Rooms, Under Carpet | Floor Covering | Vinyl Floor Tiles (white colour) | Assumed Negative | - | - | - | - | No |
KENC | Kensington Campus | C20 | Morven Brown | 1 | - | Interior Throughout Level, Various Rooms, Under Carpet | Floor Covering | Vinyl Floor Tiles (white colour) | Assumed Negative | - | - | - | - | No |
KENC | Kensington Campus | C20 | Morven Brown | 2 | - | Interior Throughout Level, Various Rooms, Under Carpet | Floor Covering | Vinyl Floor Tiles (white colour) | Assumed Negative | - | - | - | - | No |
KENC | Kensington Campus | C20 | Morven Brown | 3 | - | Interior Throughout Level, Various Rooms, Under Carpet | Floor Covering | Vinyl Floor Tiles (white colour) | Assumed Negative | - | - | - | - | No |
KENC | Kensington Campus | C20 | Morven Brown | G | - | Interior Throughout Level, Various Rooms, Under Carpet | Floor Covering | Vinyl Floor Tiles (cream colour) | Assumed Negative | - | - | - | - | No |
KENC | Kensington Campus | C20 | Morven Brown | 1 | - |
Asbestos Register
The UNSW Asbestos Register is in place to identify and minimise risks for contractors, staff and consultants.
Learn more about asbestos management at UNSW here.